Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Sullivan, MO
Franklin County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Ord. No. 3823, 11-20-2018[1]]
A. 
An ordinance of the City of Sullivan adopting the 2018 International Residential Code.
1. 
The City of Sullivan, by and through its Board of Aldermen, had determined that the Residential Code of the City of Sullivan needs to be updated so as to promote the health, safety and welfare of the citizens of Sullivan, Missouri, and
2. 
Section 67.280, RSMo., allows Cities to incorporate by reference certain technical codes.
[1]
Editor's Note: Former Article VII, International Residential Code, containing Sections 500.190 through 500.210, was repealed 11-20-2018 by Ord. No. 3822.
[Ord. No. 3823, 11-20-2018]
Three (3) copies of the 2018 International Residential Code, including Appendixes E, J and M, are on file with the City Clerk of the City of Sullivan, Missouri, at City Hall, 210 West Washington, Sullivan, Missouri, 63080, and are hereby adopted by reference and made a part of the Code of Ordinances as fully as if set forth in its entirety.
[Ord. No. 3823, 11-20-2018]
A. 
The code adopted by this Article is hereby amended by substituting the following Sections or portions of Sections for and in lieu of those Sections or portions of Sections with corresponding numbers in the 2018 International Residential Code or where there is no corresponding Section in the code, the following Sections shall be enacted as additions to the code.
1. 
R105.2 Work Exempt From Permit. Exemption from permit requirements of this code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be required for the following:
Building:
1.
One-story detached accessory structures, provided that the floor area does not exceed two hundred (200) square feet.
2.
Fences not over seven (7) feet (2,134 mm) high.
3.
Retaining walls that are not over four (4) feet (1,219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge.
4.
Water tanks supported directly upon grade if the capacity does not exceed five thousand (5,000) gallons (18,927 L) and the ratio of height to diameter or width does not exceed two (2) to one (1).
5.
Sidewalks and driveways.
6.
Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work.
7.
Prefabricated swimming pools that are less than thirty-six (36) inches deep.
8.
Swings and other playground equipment.
9.
Window awnings supported by an exterior wall that do not project more than fifty-four (54) inches (1,372 mm) from the exterior wall and do not require additional support.
10.
Deleted in its entirety.
11.
Replacing siding or residing an existing residential structure.
12.
Replacing windows in an existing residential structure.
2. 
R105.5 Expiration. Every permit issued shall become invalid unless the work authorized by such permit is commenced within one hundred eighty (180) days after its issuance or after commencement of work if more than ninety (90) days pass between inspections. The Building Official is authorized to grant, in writing, one (1) or more extensions of time, for periods not more than ninety (90) days each. The extension shall be requested in writing and justifiable cause demonstrated.
3. 
R106.1 Submittal Documents. Submittal documents consisting of construction documents, and other data shall be submitted in two (2) or more sets with each application for a permit. The construction documents shall be prepared by a registered design professional where required by the Statutes of the jurisdiction in which the project is to be constructed. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional. All construction drawing shall be required to be drawn to scale.
Exception: The Building Official is authorized to waive the submission of construction documents and other data not required to be prepared by a registered design professional if it is found that the nature of the work applied for is such that reviewing of construction documents is not necessary to obtain compliance with this code.
4. 
R106.2 Site Plan Or Plot Plan. The construction documents submitted with the application for permit shall be accompanied by a site plan, drawn to scale, showing the size and location of new construction and existing structures on the site and distances from lot lines. In the case of demolition, the site plan shall show construction to be demolished and the location and size of existing structures and construction that are to remain on the site or plot. The Building Official is authorized to waive or modify the requirement for a site plan where the application for permit is for alteration or repair or where otherwise warranted.
5. 
R106.2.1 Boundary Survey (New Section). All lots to be developed shall have a boundary survey performed by a licensed Professional Land Surveyor prior to requesting a site location inspection. A copy of the survey shall be submitted to the Building Department at the time the request for inspection is made. The owner/contractor shall be present at the site location inspection and shall indicate the location of all corners necessary for the Building Official to determine the proper setbacks.
Exceptions:
1.
When the improvement is an addition that would remain sufficiently within the required setbacks to the extent that there would be no doubt that the improvement was within the setbacks.
2.
When in the case that the size of the tract is sufficiently large compared to the structure that the improvement would be more than a distance of three (3) times the required setback on all sides.
Section R112 Board of Adjustment
6. 
R112.1 General. In order to hear and decide appeals of orders, decisions or determinations made by the Building Official relative to the application and interpretation of this code, there shall be and is hereby created a Board of Adjustment. The Building Official shall be an ex officio member of said board but shall not have a vote on any matter before the board. The Board of Adjustment shall be appointed by the governing body and shall hold office at its pleasure. The board shall adopt rules of procedure for conducting its business, and shall render decisions and findings, in writing, to the appellant with a duplicate copy to the Building Official.
7. 
R112.2 Limitations On Authority. An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply or an equally good or better form of construction is proposed. The board shall not have authority to waive requirements of this code.
8. 
R112.3 Qualifications. Delete in its entirety.
9. 
R112.4 Administration. The Building Official shall take immediate action in accordance with the decision of the board.
Chapter 2 Definitions
Chapter 3 Building Planning
10. 
R301.2 Climate And Geographic Design Criteria. Buildings shall be constructed in accordance with the provisions of this code as limited by the provisions of this Section. Additional criteria shall be established by the local jurisdiction and set forth in Table R301.2(1).
Table 301.2(1)
Ground Snow Load - 20 psf
Wind design - Speed 115 mph
Seismic Design Category - Category C
Weathering - Severe
Frost Line Depth - 30 inches
Termite - Moderate to Heavy
Winter Design Temperature - 0 to 10 degrees Fahrenheit
Ice Barrier Underlayment Required - No
Flood Hazards - Firm Oct 18, 2011 & FIRM/LOMR Jan 09, 2014
Air Freezing Index - 767
Mean Annual Temperature - 55.3
11. 
R302.5.1 Opening Protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than one and three-eighths (1 3/8) inches (35 mm) in thickness, solid or honeycomb-core steel doors not less than one and three-eighths (1 3/8) inches (35 mm) thick, or 20-minute fire-rated doors.
12. 
Table R302.6.
Table R302.6
Dwelling-Garage Separation
Separation
Material
From the residence and attics
Not less than five-eighths (5/8) inch gypsum board or equivalent applied to the garage side
From habitable rooms above the garage
Not less than five-eighths (5/8) inch Type X gypsum board or equivalent
Structure(s) supporting floor/ceiling assemblies used for separation required by this Section
Not less than one-half (1/2) inch gypsum board or equivalent
13. 
R302.11 Fireblocking. In combustible construction, fireblocking shall be provided to cut off both vertical and horizontal concealed draft openings and to form an effective fire barrier between stories, and between a top story and the roof space.
Fireblocking shall be provided in wood-frame construction in the following locations:
1.
In concealed spaces of stud walls and partitions, including furred spaces and parallel rows of studs or staggered studs, as follows:
1.1
Vertically at the ceiling and floor levels.
1.2
Horizontally at intervals not exceeding ten (10) feet (3,048 mm).
2.
At interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings and cove ceilings.
3.
In concealed spaces between stair stringers at the top and bottom of the run. Enclosed spaces under stairs shall comply with Section R302.7.
4.
At openings around vents, pipes, ducts, cables and wires at ceiling and floor level, with an approved material to resist the free passage of flame and products of combustion. The material filling this annular space shall not be required to meet the ASTM E136 requirements.
5.
For the fireblocking of chimneys and fireplaces, see Section R1003.19.
6.
Fireblocking of cornices of a two-family dwelling is required at the line of dwelling unit separation.
7.
In concealed spaces of stud walls and partitions of common walls between the living space and the garage area.
14. 
R303.3 Bathrooms. Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in two (2) windows of not less than three (3) square feet (0.3 m), one-half (1/2) of which shall be openable.
Exception: The glazed areas shall not be required where artificial light and a local exhaust system are provided. The minimum local exhaust rates shall be determined in accordance with Section M1505. Exhaust air from the space shall be exhausted directly to the outdoors. The outside will be considered as the gable vent, ridge vent and soffit vent.
15. 
R308.4.2 Glazing Adjacent To Doors. Glazing in an individual fixed or operable panel adjacent to a door shall be considered to be a hazardous location where the bottom exposed edge of the glazing is less than sixty (60) inches (1,524 mm) above the floor or walking surface and it meets either of the following conditions:
1.
Where the glazing is within twenty-four (24) inches (610 mm) of either side of the door in the plane of the door in a closed position.
2.
Delete in its entirety.
16. 
R312.3 Opening Limitations. Required guards shall not have openings from the walking surface to the required guard height that allow passage of a sphere four (4) inches (102 mm) in diameter.
Exceptions:
1.
The triangular openings at the open side of stair, formed by the riser, tread and bottom rail of a guard, shall not allow passage of a sphere six (6) inches (153 mm) in diameter.
2.
Guards on the open side of stairs shall not have openings that allow passage of a sphere four (4) inches (111 mm) in diameters
17. 
R312.2 Window Fall Protection. Delete Entire Section.
18. 
R313 Automatic Fire Sprinkler Systems. Delete Entire Section.
19. 
R315.3 Location. Carbon monoxide alarms in dwelling units shall be installed outside of each sleeping area in the immediate vicinity of the bedrooms and on each level. Where a fuel-burning appliance is located within a bedroom or its attached bathroom, a carbon monoxide alarm shall be installed within the bedroom.
20. 
R317.1 Location Required. Protection of wood and wood-based products from decay shall be provided in the following location by the use of naturally durable wood or wood that is preservative-treated in accordance with AWPA U1.
1.
Wood joists or the bottom of a wood structural floor where closer than eighteen (18) inches (457 mm) or wood girders where closer than twelve (12) inches (305 mm) to the exposed ground in crawl spaces or unexcavated area located within the periphery of the building foundation.
2.
Wood framing members that rest on concrete or masonry exterior foundation walls and are less than eight (8) inches (203 mm) from the exposed ground.
3.
Sills and sleepers on a concrete or masonry slab that is in direct contact with the ground.
4.
The ends of wood girders entering exterior masonry or concrete walls having clearances of less than one-half (1/2) inch (12.7 mm) on tops, sides and ends.
5.
Wood siding, sheathing and wall framing on the exterior of a building having a clearance of less than six (6) inches (152 mm) from the ground or less than two (2) inches (51 mm) measured vertically from concrete steps, porch slabs, patio slabs and similar horizontal surfaces exposed to the weather.
6.
Wood structural members supporting moisture-permeable floors or roofs that are exposed to the weather, such as concrete or masonry slabs, unless separated from such floors or roofs by an impervious moisture barrier.
7.
Wood furring strips or other wood framing members attached directly to the interior of exterior masonry walls or concrete walls below grade except where an approved vapor retarder is applied between the wall and the furring strips or framing members.
Chapter 4 Foundations
21. 
R401.5 Cold Weather Requirements (New Section). No concrete shall be poured or installed when the temperature is twenty-five degrees Fahrenheit (25° F.) and the temperature is predicted to go lower throughout the day.
22. 
R401.6 Hot Weather Requirements (New Section). No concrete shall be poured or installed when the temperature is one hundred and five degrees Fahrenheit (105° F.).
23. 
R402.1 Wood Foundations. Delete in its entirety.
24. 
R402.1.1 Fasteners. Delete in its entirety.
25. 
R402.1.2 Wood Treatment. Delete in its entirety.
26. 
R403.1 General. All exterior walls shall be supported on continuous solid or fully grouted masonry or concrete footings, or other approved structural systems which shall be of sufficient design to accommodate all loads according to Section R301 and to transmit the resulting loads to the soil within the limitations as determined from the character of the soil. Footings shall be supported on undisturbed natural soils or engineered fill. Concrete footing shall be designed and constructed in accordance with the provisions of Section R403 or in accordance with ACI 332.
27. 
Table R403.1(1) Delete in its entirety.
Table R403.1(2). Delete in its entirety.
Table R403.1(3). Delete in its entirety.
28. 
Table R403.1 Minimum Width Of Concrete, Precast Or Masonry Footings.
Load-Bearing Value of Soil (psf) 1,500 to 4,000
1-Story
8" thick x 24" wide
2-Story
8" thick x 24" wide
3-Story
10" thick x 24" wide
Footing design is for foundation walls up to ten (10) feet tall. Foundation walls over ten (10) feet tall will require an engineered design for the footing.
29. 
Delete Figure R403.1(1), R403.1(2) & R403.1(3).
30. 
R403.1.4.1 Frost Protection. Except where otherwise protected from frost, foundation walls, piers and other permanent supports of buildings and structures shall be protected from frost by one (1) or more of the following methods:
1.
Extended below the frost line specified in Table R301.2.(1).
2.
Constructed in accordance with Section R403.3.
3.
Constructed in accordance with ASCE 32.
4.
Erected on solid rock.
Footings shall not bear on frozen soil unless the frozen condition is permanent.
Exceptions:
1.
Protection of free-standing accessory structures with an area of two hundred (200) square feet (56 m) or less, of light-frame construction, with an eave height of ten (10) feet (3,048 mm) or less shall not be required.
2.
Protection of free-standing accessory structures with an area of two hundred (200) square feet (37 m) or less, of other than light-frame construction, with an eave height of ten (10) feet (3,048 mm) or less shall not be required.
3.
Delete in its entirety.
31. 
R403.4.1 Crushed Stone Footings. Delete in its entirety.
32. 
R403.2 Footings For Wood Foundations. Delete in its entirety.
33. 
Delete Tables R404.1.1(1), R404.1.1(2), R404.1.1(3), R404.1.1(4), R404.1.2(1), R404.1.2(2), R404.1.2(3), R404.1.2(4), R404.1.2(5), R404.1.2(6), R404.1.2(7), R404.1.2(8) & R404.1.2(9) and replace with new Table R404.1.1(1)
34. 
Table R404.1.1(1) Concrete Foundation Walls (New Section).
4 ft.
Verticals - #4's @ 4 ft. O.C.
Horizontals - #4's @ 2 ft. O.C.
8 ft.
Verticals - #4's @ 2 ft. O.C.
Horizontals - #4's @ 2 ft. O.C.
9 ft.
Verticals - #4's @ 2 ft. O.C.
Horizontals - #4's @ 2 ft. O.C.
10 ft. or taller
Design Professional Required.
Note:
a)
Mortar shall be Type M and S, and shall be laid in running bond.
b)
Vertical/horizontal reinforcement shall be grade forty (40) minimum. The distance from the face of the soil side of the wall to the center of vertical reinforcement shall be at least five (5) inches for eight (8) inch walls, six and seventy-six hundredths (6.75) inches for ten (10) inch walls, and eight and seventy-five hundredths (8.75) inches for twelve (12) inch walls.
c)
Vertical rebar shall extend to within six (6) inches from the top of foundation walls.
35. 
R404.1.3.2 Reinforcement For Foundation Walls. Concrete foundation walls shall be laterally supported at the top and bottom. Horizontal reinforcement shall be provided in accordance with Table R404.1.1(1). Vertical reinforcement shall be provided in accordance with Table R404.1.1(1) Vertical reinforcement for flat basement walls retaining four (4) feet (1,219 mm) or more of unbalanced backfill is permitted to be determined in accordance with Table R404.1.1(1). For basement walls supporting above-grade concrete walls, vertical reinforcement shall be the greater of that required by Table R404.1.1(1).
36. 
R404.2 Wood Foundation Walls. Delete entire section thru R404.2.6.
37. 
R405.2 Wood Foundations. Delete entire section thru R405.2.3.
38. 
R406.3 Dampproofing For Wood Foundations. Delete entire section thru R406.3.4.
39. 
R408.4 Access. Access shall be provided to all under-floor spaces. Access openings through the floor shall be not smaller than eighteen (18) inches by twenty-four (24) inches (457 mm by 610 mm). Openings through a perimeter wall shall be not less than eighteen (18) inches by twenty-four (24) inches (407 mm by 610 mm). Where any portion of the through-wall access is below grade, an areaway not less than eighteen (18) inches by twenty-four (24) inches (407 mm by 610 mm) shall be provided. The bottom of the areaway shall be below the threshold of the access opening. Through wall access openings shall not be located under a door to the residence. See Section M1305.1.4 for access requirements where mechanical equipment is located under floors.
Chapter 5 Floors
40. 
Table R502.3.1 Floor Joist Spans For Common Lumber Species. Delete this Section.
41. 
Table R503.2.1.1(1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor Sheathing and Combination Subfloor Underlayment.
Span Rating
Minimum Nominal Panel Thickness
(inch)
Allowable Live Loadh, l
(psf)
Maximum Span
(inches)
Load (pounds per square foot, at maximum span)
Maximum Span
(inches)
SPAN @ 16" o.c.
SPAN @ 24" o.c.
With edge supportc
Without edge support
Total load
Live load
Sheathinge
Rooff
Subfloorj
16/0
3/8
30
16
16
40
30
0
20/0
7/16
50
20
20
40
30
0
24/0
7/16
100
30
24
20g
40
30
0
24/16
7/16
100
40
24
24
50
40
16
32/16
15/32 1/2
180
70
32
28
40
30
16
40/20
19/32 5/8
305
130
40
32
40
30
20h, i
48/24
23/32 3/4
175
48
36
45
35
24
60/32
7/8
305
60
48
45
35
32
Underlayment, C-C plugged, single floore
Rooff
Combination subfloor underlay-mentk
16 o.c.
23/32, 3/4
100
40
24
24
50
40
16
20 o.c.
23/32, 3/4
150
60
32
32
40
30
20i, j
24 o.c.
3/4
240
100
48
36
35
25
24
32 o.c.
7/8
185
48
40
50
40
32
48 o.c.
1 3/32, 1 1/8
290
60
48
50
40
48
42. 
R504 Pressure Preservative-Treated Wood Floors (on ground). Delete entire Section thru R504.3.
Chapter 6 Wall Construction
43. 
Figure R602.10.6.3 Portal Frame at Garage Door Opening in Seismic Design Categories A, B & C.
Exception: The steel tension strap may be substituted by a continuous two (2) inches by four (4) inches from the top of the double plate to the top of the foundation.
Chapter 7 Wall Covering
44. 
R702.3.7 Water-Resistant Gypsum Backing Board. Gypsum board used as the base or backer for adhesive application of ceramic tile or other required non-absorbent finish material shall conform to ASTM C1178, C1278 or C1396. Use of water-resistant gypsum backing board shall be permitted on ceilings. Water-resistant gypsum board shall not be installed over a Class I or II vapor retarder in a shower or tub compartment. Cut or exposed edges, including those at wall intersections, shall be sealed as recommended by the manufacturer. Water resistant gypsum board shall be extended at least twenty-four (24) inches past any tub or shower enclosure area.
Chapter 8 Roof-Ceiling Construction
Chapter 9 Roof Assemblies
Chapter 10 Chimneys and Fireplaces
45. 
R1005.4.1 Factory-Built Fireplace Flue Chase (New Section). The flue chase for factory-built fireplaces shall have one (1) layer of five-eighths (5/8) Type "X" drywall applied to the inside of the chase to the roof sheathing. Drywall shall be fire taped or caulked.
Chapter 11 Energy Efficiency
46. 
Delete Chapter 11 from the 2018 IRC and replace with Chapter 11 from the 2009 IRC plus the following amendments. Table N1102.1 Insulation and Fenestration Requirements by Component. Add note k to Basement wall R-value. Note k to state "Basement wall R-value requirements are only applicable to basements with habitable space. N1102.4.2.1 Testing option. Delete this entire Section. N1103.2.2 Sealing. Delete duct tightness testing requirements. Both postconstruction test and rough-in test.
Chapter 12 Mechanical Administration
Chapter 13 General Mechanical system Requirements
Chapter 14 Heating and Cooling Equipment
47. 
M-1401.4.1 Height Limitation (New Section). Equipment installed outdoors shall be installed a maximum of three (3) feet above finish grade to the bottom of the equipment.
Chapter 15 Exhaust Systems
48. 
M1505 Duct Material (New Section). All single wall ventilation ducts serving toilet rooms and bathrooms shall be constructed of an approved rigid or flexible metal material. Vinyl duct is not allowed.
Chapter 16 Duct Systems
Chapter 17 Combustion Air
Chapter 18 Chimneys and Vents
Chapter 19 Special Appliances, Equipment and Systems
Chapter 20 Boilers and Water Heaters
Chapter 21 Hydronic Piping
Chapter 22 Special Piping and Storage Systems
Chapter 23 Solar Thermal Energy Systems
Chapter 24 Fuel Gas
49. 
G2412.5 (401.5) Identification. Exposed piping shall be identified by a yellow label marked "Gas" in black letters. The marking shall be spaced at intervals not exceeding five (5) feet (1,524 mm).
50. 
G2414.4.2 (403.4.2) Steel. Steel, stainless steel and wrought-iron pipe shall not be lighter than Schedule 40 and shall comply with the dimensional standards of ASME B36.10, 10M and one (1) of the following standards:
1.
ASTM A53/A53M.
2.
ASTM A106.
3.
ASTM A312.
51. 
G2414.10.1 (403.10.1) Pipe Joints. Schedule 40 and heavier pipe joints shall be threaded, flanged, brazed, welded or assembled with press-connect fittings listed in accordance with ANSI LC4/CSA 6.32. Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of one thousand degrees Fahrenheit (1,000° F.) (538° C.). Brazing alloys shall not contain more than five hundredths percent (0.05%) phosphorus.
52. 
G2420.5.3 Located At Manifold: Delete this Section.
53. 
G2427.10.2.2 (503.10.2.2) Vent connectors located in unconditioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties.
Exception: Delete in its entirety.
Chapter 25 Plumbing Administration
54. 
P2503.5.1 Rough Plumbing. DWV systems shall be tested on completion of the rough piping installation by water or by air without evidence of leakage. Either test shall be applied to the drainage system in its entirety or in sections after rough-in piping has been installed, as follows:
55. 
P2503.7 Water-Supply System Testing. Upon completion of the water-supply system or a section of it, the system or portion completed shall be tested and proved tight under a water pressure of not less than the working pressure of the system or, for piping systems other than plastic, by an air test of not less than eighty (80) psi (345 kPa). This pressure shall be held for not less than fifteen (15) minutes. The water used for tests shall be obtained from a potable water source.
Chapter 26 General Plumbing Requirements
Chapter 27 Plumbing Fixtures
Chapter 28 Water Heaters
56. 
P2804.1 Water Heater Sizing Table.
Fuel
Gas
Elect
Oil
Gas
Elect
Oil
Gas
Elect
Oil
Gas
Elect
Oil
Number of Bedrooms
1
2
3
1 to 1 1/2 Baths
Storage (gal)
20
20
30
30
30
30
30
40
30
Input (Btu/h or kw)
27K
2.5
70K
36K
3.5
70K
36K
4.5
70K
Draw (gph)
43
30
89
60
44
89
60
58
89
Recovery (gph)
23
10
59
30
14
59
30
18
59
Number of Bedrooms
2
3
4
5
2 to 2 1/2 Baths
Storage (gal)
30
40
30
40
50
30
40
50
30
50
66
30
Input (Btu/h or kw)
36K
4.5
70K
36K
5.5
70K
38K
5.5
70K
47K
5.5
70K
Draw (gph)
60
58
89
70
72
89
72
72
89
90
88
89
Recovery (gph)
30
18
59
30
22
59
32
22
59
40
22
59
Number of Bedrooms
3
4
5
6
3 to 3 1/2 Baths
Storage (gal)
40
50
30
50
66
30
50
66
30
50
80
40
Input (Btu/h or kw)
38K
5.5
70K
38K
5.5
70K
47K
5.5
70K
50K
5.5
70K
Draw (gph)
72
72
89
82
88
89
90
88
89
92
102
99
Recovery (gph)
32
22
59
32
22
59
40
22
59
42
22
59
For SI: 1 gallon = 3.785 L, 1 gallon per hour = 1.05 mL/s, 1 Btu/h = 0.2931 W, ° F. = 1.8° C. + 32.
NOTE: Storage capacity, input and the recovery requirements indicated in the table are typical and may vary with each individual manufacturer. Any combinations of these requirements to produce the one-hour draw stated will be satisfactory. Recovery is based on one hundred degree Fahrenheit (100° F.) water temperature rise.
Chapter 29 Water Supply & Distribution
57. 
P2902.5.3 Lawn Irrigation Systems. The potable water supply to lawn irrigation systems shall be protected against backflow by a reduced pressure principle backflow prevention assembly. Valves shall not be installed downstream from an atmospheric vacuum breaker.
58. 
P2906.4 Water Service Pipe. Water service pipe shall conform to NSF 61 and shall conform to one (1) of the standards indicated in Table P2906.4. Water service pipe or tubing, installed underground and outside of the structure, shall have a working pressure rating of not less than one hundred sixty (160) pounds per square inch at seventy-three degree Fahrenheit (73° F.) (1103 kPa at twenty-three degrees Celsius (23° C.). Where the water pressure exceeds one hundred sixty (160) pounds per square inch (1103 kPa), piping material shall have a rated working pressure equal to or greater than the highest available pressure. Water service piping materials not third-party certified for water distribution shall terminate at or before the full open valve located at the entrance to the structure. Ductile iron water service piping shall be cement mortar lined in accordance with AWWA C104/A21.4.
Table P2906.4 Water Service Pipe
Material
Standard
Copper or copper-alloy pipe
ASTM B42; ASTM B43; ASTM B302
Copper or copper-alloy tubing (Type K)
ASTM B75/B75M; ASTM B88; ASTM B251; ASTM B447
Polyethylene (PE) plastic tubing
ASTM D2737; AWWA C901; CSA B137.1
Stainless steel (Type304/304L) pipe
ASTM A312; ASTM A778
Stainless steel (Type 316/316L) pipe
ASTM A312; ASTM A778
59. 
P2906.5 Water Distribution Pipe. Water distribution piping within dwelling units shall conform to NSF 61 and shall conform to one (1) of the standards indicated in Table P2906.5. Water distribution pipe and tubing shall have a pressure rating of not less than one hundred (100) psi at one hundred eighty degrees Fahrenheit (180° F.) (689 kPa at 82° C.).
Table P2906.5 Water Distribution Pipe
Material
Standard
Chlorinated polyvinyl chloride (CPVC) plastic pipe and tubing
ASTM D2846; ASTM F441; ASTM F442/F442M; CSA B137.6
Copper or copper-alloy pipe
ASTM B42; ASTM B43; ASTM B302
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)
ASTM B75/B75M; ASTM B88; ASTM
B251; ASTM B447
Cross-linked polyethylene (PEX) plastic tubing
ASTM F876; CSA B137.5
Stainless steel (Type 304/304L) pipe
ASTM A312; ASTM A778
60. 
P2906.6 Fittings. Pipe fittings shall be approved for installation with the piping material installed and shall comply with the applicable standards indicated in Table P2906.6. Pipe fittings used in water supply systems shall comply with NSF 61.
Table P2906.6 Pipe Fittings
Material
Standard
Chlorinated polyvinyl chloride (CPVC) plastic
ASSE 1061; ASTM D2846; ASTM F437; ASTM F438; ASTM F439; CSA B137.6
Copper or copper alloy
ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.26; ASME B16.51; ASSE 1061
Fittings for cross-linked polyethylene (PEX) plastic tubing
ASSE 1061; ASTM F877; ASTM F1807; ASTM F1960; ASTM F2080; ASTM F2098; ASTM F2159; ASTM F2434; ASTM F2735; CSA B137.5
Stainless steel (Type 304/304L) pipe
ASTM A312; ASTM A778
Stainless steel (Type 316/316L) pipe
ASTM A312; ASTM A778
Chapter 30 Sanitary Drainage
61. 
P3002.1 Piping Within Buildings. Drain, waste and vent (DWV) piping in buildings shall be as indicated in Tables P3002.1(1) and P3002.1(2) except that galvanized wrought-iron or galvanized steel pipe shall not be used underground and shall be maintained not less than six (6) inches (152 mm) above ground. Allowance shall be made for the thermal expansion and contraction of plastic piping.
Table P3002.1(1) Above-Ground Drainage And Vent Pipe
Material
Standard
Cast-iron pipe
ASTM A74; ASTM A888; CISPI 301
Copper or copper-alloy pipe
ASTM B42; ASTM B43; ASTM B302
Copper or copper-alloy tubing (Type K, L, M or DWV)
ASTM B75/B75M; ASTM B88; ASTM B251; ASTM B306
Galvanized steel pipe
ASTM A53
Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including schedule 40, DR 22 (PS 200)
ASTM D2665; ASTM F891; ASTM F1488; CSA B181.2
Stainless steel drainage systems, Types 304 and 316L
ASME A112.3.1
For SI: 1 inch = 25.4 mm.
Table P3002.1(2) Underground Building Drainage And Vent Pipe
Material
Standard
Cast-iron pipe
ASTM A74; ASTM A888; CISPI 301
Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including schedule40, DR 22 (PS 200)
ASTM D2665; ASTM F891; ASTM F1488; CSA B181.2
For SI: 1 inch = 25.4 mm.
62. 
P3002.2 Building Sewer. Building sewer piping shall be as indicated in Table P3002.2. Forced main sewer piping shall conform to one (1) of the standards for PVC plastic pipe or pressure-rated pipe indicated in Table P3002.2.
Table P3002.2 Building Sewer Pipe
Material
Standard
Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including schedule 40, DR 22 (PS 200)
ASTM D2665; ASTM D2949; ASTM D3034; ASTM F1412; CSA B182.2; CSA B182.4
For SI: 1 inch = 25.4 mm.
63. 
P3002.3 Fittings. Pipe fittings shall be approved for installation with the piping material installed and shall comply with the applicable standards indicated in Table P3002.3.
Table P3002.3 Pipe Fittings
Pipe Material
Fitting Standard
Copper or copper alloy
ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29
Polyvinyl chloride (PVC) plastic in IPS diameters
ASTM D2665; ASTM D3311; ASTM F1866
64. 
P3003.9.2 Solvent Cementing. Joint surfaces shall be clean and free from moisture. A purple primer, or other approved primer, that conforms to ASTM F656 shall be applied. Solvent cement not purple in color and conforming to ASTM D2564, CSA B137.3 or CSA B181.2 shall be applied to all joint surfaces. The joint shall be made while the cement is wet, and shall be in accordance with ASTM D2855. Solvent-cement joints shall be installed above or below ground.
Exception: Delete exception and Subsections (1) and (2) following same.
65. 
P3005.2.2 Building Sewers. Building sewers smaller than eight (8) inches (203 mm) shall have a minimum of one (1) cleanout capable of cabling both up and down stream, and at intervals of not more than one hundred (100) feet (30,480 mm) thereafter. Building sewers eight (8) inches (203 mm) and larger shall have a manhole located not more than two hundred (200) feet (60,960 mm) from the junction of the building drain and building sewer and at intervals of not more than four hundred (400) feet (122 m). The interval length shall be measured from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting providing access for cleaning, a manhole or the end of the building sewer.
66. 
P3005.4.1 Branch And Stack Sizing. Branches and stacks shall be sized in accordance with Table P3005.4.1. Below grade drain pipes shall be not less than two (2) inches in diameter. Drain stacks shall be not smaller than the largest horizontal branch connected.
Exceptions:
1.
A 4-inch by 3-inch (102 mm by 76 mm) closet bend or flange.
2.
A 4-inch (102 mm) closet bend connected to a 3-inch (76 mm) stack tee shall not be prohibited.
Chapter 31 Vents
67. 
P3102.1 Required Vent Extension. Every building shall have a main vent a minimum of three (3) inches in diameter that is either vent stack or a stack vent. Such vent shall run undiminished in size and as directly as possible from the building drain through to the open air above the roof. All other vents thru the roof shall be no less than two (2) inches in diameter.
68. 
P3103.1.3 Roof Extension Covered. Delete this Section.
69. 
P3104.1 Connection. Individual branch and circuit vents shall connect to a vent stack, stack vent or extend to the open air.
Exception. Delete the exception.
70. 
P3113.1 Size Of Vents. The required diameter of individual vents, branch vents, circuit vents, vent stacks and stack vents shall be not less than one-half (1/2) the required diameter of the drain served. The required size of the drain shall be determined in accordance with Chapter 30. Vent pipes shall be not less than one and one-fourths (1 1/4) inches (32 mm) in diameter. Vents exceeding forty (40) feet (12,192 mm) in developed length shall be increased by one (1) nominal pipe size for the entire developed length of the vent pipe. Water closets shall be required to have a minimum of a two (2) inch vent.
71. 
P3114.1 General. Vent systems using air admittance valves shall comply with this Section. Individual and branch-type air admittance valves shall conform to ASSE 1051. Stack-type air admittance valves shall conform to ASSE 1050. Air admittance valves are only allowed to be used when approved by the Building Official.
Chapter 32 Traps
Chapter 33 Storm Drainage
72. 
P3303.1.5 Discharge Piping Location (New Section). All sump pump piping shall be piped to discharge to the exterior of the building no closer than ten (10) feet from the property line. Discharging into the sanitary sewer is prohibited.
73. 
Chapters 34 thru 43 Electrical. Delete these chapters in their entirety and reference the 2017 NEC.
74. 
Adopt the following Appendixes — Appendix E Manufactured Housing Used as Dwellings, Appendix J Existing Buildings and Structures and Appendix M Home Day Care — R-3 Occupancy.