[Ord. 29, 9/24/1973, § 1008.1]
Every park shall contain an electrical wiring system consisting
of wiring, fixtures, equipment and appurtenances which shall be installed
and maintained in accordance with local electric power company's
specifications regulating such systems.
[Ord. 29, 9/24/1973, § 1008.2]
All utilities shall be buried at least 18 inches below the ground
surface and shall be insulated and specially designed for the purpose.
Such conductors shall be located not less than one foot radial distance
from water, sewer, gas or communications lines.
[Ord. 29, 9/24/1973, § 1008.3]
Each mobile home lot shall be provided with an approved disconnecting
device and overcurrent protective equipment. The minimum service per
outlet shall be 120/240 volts AC, 100 amperes.
[Ord. 29, 9/24/1973, § 1008.4]
All exposed non-current-carrying metal parts of mobile homes
and all other equipment shall be grounded by means of an approved
grounding conductor run with branch circuit conductor or other approved
method of grounded metallic wiring. The neutral conductor shall not
be used as an equipment ground for mobile homes or other equipment.