Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Ocean Beach, NY
Suffolk County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
The purpose of this article is:
A. 
To protect the public potable water supply of the Village from the possibility of contamination by isolating within its customers' internal distribution system(s) or its customers' private water systems(s) such contaminations or pollutants which could backflow into the public water supply system; and
B. 
To comply with the requirements of the New York State Sanitary Code 5-1.31.
The Village Superintendent shall be responsible for the protection of the water distribution system from contamination due to the backflow of contaminants through the water service connection. If, in the judgment of said Superintendent, an acceptable backflow prevention device is required at the district's water service connection to any customer's premises, for the safety of the water system, the Superintendent or his designated agent shall give notice in writing to said customer to install such an acceptable backflow prevention device at each service connection to this premises. The customer shall immediately install such an acceptable backflow prevention device at each service connection to this premises. The customer shall immediately install such approved device or devices at his own expense, and failure, refusal or inability on the part of the customer to install said device or devices immediately shall constitute a ground for discontinuing water service to the premises until such device or devices have been properly installed.
As used in this article, the following terms shall have the meanings indicated:
ACCEPTABLE BACKFLOW PREVENTION DEVICE
An acceptable air gap, reduced pressure zone device or double check valve assembly as used to contain potential contamination within a facility. In order for the reduced pressure zone device or the double check valve assembly to be acceptable, it must be listed on the most current version of the New York State Department of Health list of acceptable devices.
AESTHETICALLY OBJECTIONABLE FACILITY
One in which substances are present which if introduced into the public water supply system could be a nuisance to other water customers but would not adversely affect human health. Typical examples of such substances are food-grade dyes, hot water, stagnant water from fire lines in which no chemical additives are used, etc.
AIR GAP
The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture or other device and the flood level rim of said vessel. An approved air gap shall be at least double the diameter of the supply pipe, measured vertically, above the top of the rim of the vessel and in no case less than one inch.
APPROVED
Accepted by the Village Superintendent as meeting an applicable specification stated or cited in this article or as suitable for the proposed use.
AUXILIARY WATER SUPPLY
Any water supply on or available to the premises other than the Village public water supply. These auxiliary waters may include water from another purveyor's public potable water supply or any natural source(s), a well, spring, river, stream, harbor, etc., or used waters. These waters may be contaminated or they may be objectionable and constitute an unacceptable water source over which the water purveyor does not have sanitary control.
BACKFLOW
A flow condition, induced by a differential in pressure, that causes the flow of water or other liquids and/or gases into the distribution pipes of the Village's supply system from any source other than its intended source.
CERTIFIED TESTER
That individual or firm approved to accomplish the necessary inspections and operational tests of backflow prevention devices.
CONTAMINATION
The presence in water of a substance that tends to degrade its quality.
CUSTOMER
A water user served by the Village supply system.
CUSTOMER'S WATER SYSTEM
The piping used to convey water supplied by the Village water supply system throughout a customer's facility. The system shall include all those parts of the piping beyond the control point of the Village. The control point is either the curb valve or the main valve located in the public right-of-way that isolates the customer's facilities from the Village distribution system.
DEGREE OF HAZARD
Whether a facility is rated as hazardous, aesthetically objectionable or nonhazardous.
DOUBLE CHECK VALVE ASSEMBLY, ACCEPTABLE
An assembly composed of two single, independently acting check valves, including tightly closing shutoff valves located at each end of the assembly and suitable connections for testing the watertightness of each check valve.
HAZARDOUS FACILITY
One in which substances may be present which if introduced into the public water system would or may endanger or have an adverse effect on the health of other water customers. Typical examples are laboratories, sewage treatment plants, chemical plants, hospitals and mortuaries.
NONHAZARDOUS FACILITY
One which does not require the installation of an acceptable backflow prevention device.
PUBLIC WATER SUPPLY SYSTEM
The Village water system, including the source, treatment works, transmission mains, distribution system and storage facilities serving the public. This includes the distribution system up to its connection with the customer's water system.
REDUCED PRESSURE ZONE DEVICE, ACCEPTABLE
A device containing a minimum of two independently acting check valves, together with an automatically operated pressure differrential relief valve located between the two check valves. During normal flow and at the cessation of normal flow, the pressure between these two checks shall be less than the upstream (supply) pressure. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure. The unit must include tightly closing shutoff valves located at each end of the device, and each device shall be fitted with properly located test cocks.
SUPERINTENDENT
The Manager of the Village.
The customer's water system shall be open for inspection at all reasonable times to authorized representatives of the Village.
The Superintendent shall rate a customer's water system according to its degree of hazard to the public water supply system. Some of the factors to be considered are the use and availability of contaminants, the availability of an auxiliary water supply and the type of fire-fighting system in use.
An acceptable backflow prevention device shall be installed on each service line to a customer's water system at or near the property line or immediately inside the building being served but, in all cases, before the first branch line leading off the service line, as follows:
A. 
Whenever a customer's water system is rated hazardous, an acceptable reduced pressure zone device or air gap shall be installed.
B. 
Whenever a customer's water system is rated aesthetically objectionable, as a minimum, an acceptable double check valve assembly shall be installed.
The design of the installation of an acceptable backflow prevention device must be prepared in accordance with New York State laws and regulations. The design must be approved by the Superintendent and all agencies required by the applicable New York State and Suffolk County laws and regulations.
It shall be the duty of the customer at any premises where backflow prevention devices are installed to have certified inspections and an operational test made at least once a year. In those instances where the Superintendent deems the hazard to be great enough, he may require certified inspections at more frequent intervals. Certified inspections and operational tests must also be made when any backflow prevention device is to be installed, repaired, overhauled or replaced, in addition to the requirement of an annual certified inspection and operational test. All inspections and tests shall be at the expense of the customer and shall be performed by the device manufacturer's representative, Village personnel or by a certified tester approved by the Village Superintendent. The Village shall make available the names, addresses and telephone numbers of those persons who are certified as testers for backflow prevention devices. It shall be the duty of the Superintendent to see that certified inspection and operational tests of the backflow prevention devices are made. The customer shall notify the Superintendent in advance, in writing, when the tests are to be undertaken, so that he or his representative may witness the tests if it is so desired. These devices shall be repaired, overhauled or replaced at the expense of the customer whenever said devices are found to be defective. Records of such tests, repairs and overhaul shall be kept and made available to the Water District Superintendent. Copies of all testing and maintenance records shall be sent to the Superintendent immediately after the work is performed.
All presently installed prevention devices which do not meet the requirements of this article but were approved devices for the purposes described herein at the time of installation and which have been properly maintained shall, except for the inspection and maintenance requirements under this section and § 160-25, be excluded from the requirements of these rules so long as the Superintendent is assured that they will satisfactorily protect the utility system. Whenever the existing device is moved from the present location or requires more than minimum maintenance or constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this article.
No water service connection to any customer's water system shall be installed or maintained by the Village unless the water supply is protected as required by state laws and regulations and this article. Service of water to any premises shall be discontinued by the Superintendent if a backflow prevention device required by this article is not installed, tested and maintained or if it is found that a backflow prevention device has been removed or bypassed. Service will not be restored until such conditions or defects are corrected.
A violation of the provisions of this chapter shall, upon conviction, be subject to the penalties set forth in Chapter 1, General Provisions, § 1-14.