Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of New Haven, MI
Macomb County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
The construction, arrangement and manner of installation of all oil burners and oil-burner equipment hereafter installed for use in connection with heating systems, and the alteration replacement or repair hereafter of all oil burners and oil-burner equipment used or to be used in connection with heating systems, shall conform to the provisions of this chapter.
The Inspector may approve any oil burner listed by the Underwriters Laboratory or any other nationally recognized inspection board or laboratory. Oil burners not listed by the Underwriters Laboratory or any other nationally recognized board or laboratory shall not be approved until they have been inspected and tested by some recognized laboratory capable of making such a test and inspection and the certificate showing such inspection and test shall be forwarded to the Inspector. This inspection and test shall cover arrangement of parts, suitability of material, strength of parts, electrical control, thermostatic arrangement, reliability of automatic features, positiveness of ignition and safeguards against flooding.
Any person licensed to install, alter, repair or replace oil burners in the Village of New Haven shall install a used burner for use in connection with a heating system only after he shall have furnished the Inspector with a statement that said oil burner has been put in first class operating condition.
The grade of fuel oil used with any burner shall be one which tests and experience show to be suitable for use with that burner. The oil shall have a flash point not less than 110° F. when tested by the Pensky-Martins Closed Cup Testing Method and shall be free from acid, grit, and fibrous or other foreign matter likely to clog or injure the burners or valves.
The burner shall be designed to prevent excessive carbonization and shall be securely attached and supported.
Gravity feed shall be used only with burners equipped with approved automatic devices to prevent abnormal discharge of oil in the burner.
Complete instructions in regard to care and operation of the oil-burning equipment shall be posted near the apparatus installed. The instruction sheet so posted shall include the specifications for the gravity and limiting flash point of the oil suitable for use in the burner. All instruction cards must be posted at the time of installation.
In single residences, every oil-burner installation shall have near the entrance to the furnace room, and readily accessible for convenient use in an emergency, a hand fire extinguisher of at least a quart capacity approved by the National Board of Fire Underwriters for extinguishing combustible oil fires; provided, however, that in installations of oil-burning equipment in multiple dwellings and commercial establishments of any kind or description where the public congregates or persons are permitted to be present on invitation or otherwise, such installation shall have accessible in the furnace room for immediate and convenient use in emergency a fire extinguisher of at least 2 1/2 gallons' capacity, approved by the National Board of Fire Underwriters, and which shall be of a foam type or its equivalent; provided further that in case of great hazard or danger to the public, the Chief of the Fire Department of the Village of New Haven may, in writing, require further or additional fire-extinguishing apparatus in order to safeguard public property and life.
The use of acetylene or any other gas possessing a wider range of explosiveness in admixture with air than coal gas or water gas is prohibited for use in the gas pilot of any fuel oil burner.
A. 
Ventilation shall be provided to prevent the accumulation of any trapped vapors below the combustion chamber.
B. 
Rooms in which oil-burning equipment is located shall be provided with adequate ventilation to assure continuous complete combustion of the oil.
A name plate designating the trade name of the burner, the model, or size number and the name and address of the burner manufacturer, shall be securely attached to each fuel oil burner and oil-burning space heater.
No damper shall be permitted in the smoke pipe or chimney from the device heated that may restrict the passage of fumes or gases by more than 40%.
Each oil-fired heating unit covered by this chapter shall be connected to a chimney flue.
A. 
Flue specifications.
(1) 
Chimney flues and flue pipes shall freely conduct the flue gases to the outer air.
(2) 
The chimney or flue shall be properly constructed in accordance with the requirements of the Official Building Code of the Village of New Haven.[1]
[1]
Editor's Note: See Ch. 160, Building Construction.
B. 
The flue pipe shall not enter the chimney or flue beyond its inner wall and shall be so cemented to the chimney as to prevent infiltration of air. In entering the chimney or flue, the connection shall be made at least six inches above the extreme bottom.
A. 
Vent connections.
(1) 
The vent connection shall not be smaller than the size indicated by the vent collar of the appliance when same is oil-designed.
(2) 
The horizontal vent connection shall not be longer than 1/2 the effective height of the chimney.
B. 
Vent pipes.
(1) 
The vent pipe shall maintain a pitch or rise of 1/4 inch per foot of the horizontal run from the equipment to the flue or chimney.
(2) 
The vent pipe shall be so installed as to avoid sharp turns or other constructive features which would create excess resistance to flow of the gaseous products of combustion.
(3) 
Interconnections.
(a) 
Vent pipes from one or more oil-fired space heating appliances may be interconnected, provided that the cross-sectional area of the manifold shall be equal to the sum of the cross-sectional areas of the vent collar connections of the appliances.
(b) 
No vent from an oil-fired space heating appliance shall be interconnected with a vent pipe from an appliance burning other fuels or designed for other uses except with the specific approval of the Inspector.
(4) 
A vent pipe from an oil-fired heating appliance and vent pipes from other appliances, burning the same or other fuels, may be connected into the same chimney through separate openings located at different levels, provided that the operation of any of the equipment is not adversely affected.
(5) 
The material used for vent pipes shall be such as to resist the corrosive action of flue gases and condensate.
In the case of conversion burners, the fuel door shall be arranged so as to relieve pressure due to puffs or back-fire caused by delayed ignition, and shall be provided with an approved self-enclosing device.
Electric wiring in connection with oil-burning equipment shall be installed in accordance with the regulations of the National Electric Code and local electrical rules as enforced by Chapter 230, Electrical Standards.
A. 
The minimum clearance of oil-fired heating units from combustible partitions and materials shall be as set forth in Table No. 1,[1] except in the case of equipment especially designed for burning fuel oil and tested and listed for lesser clearances by a national recognized testing laboratory.
[1]
Editor's Note: Table No. 1 is included at the end of this chapter.
B. 
The clearance to combustible construction may be reduced as specified in Table No. 2[2] where the combustible construction is protected in accordance with this table.
[2]
Editor's Note: Table No. 2 is included at the end of this chapter.
A. 
Where metal smoke pipes of 12 inches or less in diameter pass through a wood or plastered stud partition, they shall be surrounded either by a body of brick, hollow tile, or other incombustible fireproof material of a thickness of at least four inches around such smoke pipes; or they shall be surrounded by a sheet metal thimble of two concentric rings at least two inches apart, with the entire thimble so constructed that there will be a free circulation of air between the two rings forming the same. Smoke pipes of a diameter of six inches or less may have thimbles with one-inch air space.
B. 
Where a new smoke pipe is installed, it shall be lock-seamed or riveted, with all joints lapped not less than 1 1/2 inches and rigidly secured, and shall have a proper thimble for making tight connections to the chimney flue.
Oil-fired floor furnaces shall be specifically approved by the Department for services in direct contact with combustible floors in which they may be installed.
A. 
Combustion air. Fixed ventilation by means of a duct or grille arranged to supply air from a permanently ventilated attic or underfloor space shall be provided to any confined space which encloses the floor furnace. The duct or grille shall be screened and have a free area at least twice the free area of the vent collar of the floor furnace or one square inch per 1,000 BTUs per hour of oil input, whichever is the greater, and shall be installed in such a manner as to ensure proper combustion.
B. 
Placement. The following are requirements that will serve in properly placing the furnace or furnaces to serve one story:
(1) 
No floor furnace shall be installed in the floor of any aisle or passageway of any auditorium, public hall, or place of assembly, or in an exitway of any such room or space.
(2) 
Walls and corners. With the exception of wall-register models, a floor furnace shall not be placed closer than six inches to the nearest wall, and wall-register models shall not be placed closer than six inches to a corner.
(3) 
Draperies. The furnace shall be so placed that a door, drapery, or similar object cannot be nearer than 12 inches to any portion of the register of the furnace.
(4) 
Central location. Generally speaking, the more central the location the better, favoring slightly the sides exposed to the prevailing winter winds.
C. 
Bracing. The floor around the furnace shall be braced and headed with a framework of material not lighter than the joists.
D. 
Support. Means shall be provided to support the furnace when the floor grille is removed.
E. 
Clearance. The lowest portion of the floor furnace shall have at least a six-inch clearance from the general ground level, except that where the lower six-inch portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the clearance may be reduced to not less than two inches. When these clearances are not present, the ground below and to the sides shall be excavated to form a "basin-like" pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A twelve-inch clearance shall be provided on all sides except the control side, which shall have an eighteen-inch clearance.
F. 
Access. Provisions shall be made for an access door to the floor furnace by means of an opening in the foundation wall of at least 18 inches by 24 inches and a trap door of at least 24 inches by 24 inches, located at some convenient point, and a clear and unobstructed passageway to the floor furnace at least 18 inches high by 24 inches wide.
G. 
Seepage pan. Whenever the excavation exceeds 12 inches or water seepage is likely, a pit made of concrete, waterproof, not less than 3 3/4 inches thick and extending four inches above grade level, shall be used. The pit shall be not less than six feet by six feet inside dimension, with at least 2 1/2 feet of clearance on the control side and clearance on all other sides not less than six inches.
H. 
Wind protection. Floor furnaces shall be protected, where necessary, against severe wind conditions.
I. 
Upper floor installations. Listed oil floor furnaces may be installed in an upper floor, provided the furnace assembly projects below into a utility room, closet, garage, or similar nonhabitable space. In such installations, the floor furnace shall be enclosed completely (entirely separated from the nonhabitable space) with means for air intake to meet the provisions of Subsection A, with access facilities for servicing on the control side, with minimum furnace clearance of six inches to all sides and bottom, and with the enclosure constructed of portland cement plaster on metal lath or material of equal fire resistance.
J. 
Registers shall not be covered with combustible materials, and the floor immediately surrounding the furnace shall be reasonably level.
K. 
All floor furnaces, including those having single or dual wall register outlets, shall be installed as approved without alterations, extensions or changes of any kind (in the furnace).