[Adopted 3-16-1976 by L.L. No. 2-1976,
as published in the Book of Ordinances of the Village of Sands Point
and as last supplemented 8-25-1981]
It is the intent of the Village of Sands Point
(hereinafter referred to as "Village") that this Part 3 shall apply
in situations of potential major health hazard, such as swimming pools,
automatic sprinklers, private wells, fish and garden pools and in
such additional situations as in the discretion of the Village must
be subject to the requirements of this Part 3.
[Amended 8-28-2001 by L.L. No. 6-2001]
A.Â
All backflow prevention devices installed shall be
tested annually. All new devices shall be tested when initially installed.
Testing shall be conducted by a New York State Department of Health
certified backflow prevention device tester. The tester shall file
the required New York State forms and results within 30 days of conducting
the tests. Any device that fails the test shall be repaired and required
to pass the test.
B.Â
It shall be the responsibility of the owner of the
building or premises to have the devices tested annually. Failure
to comply shall be punishable by a fine of $500 and/or the shutoff
of the water service line.
[Amended 3-22-2022 by L.L. No. 5-2022]
The Superintendent or his designated agent shall
have the right of entry to premises or into any building, during reasonable
hours, for the purpose of making inspection of the plumbing systems
installed in such buildings or premises, provided that, with respect
to the inspection of any single-family dwelling, consent to such inspection
shall first be obtained from a person of suitable age and discretion
therein or in control thereof. Failure to give consent to a reasonable
request to inspect shall be considered a violation of this Part 3.
As used in this Part 3, the following terms
shall have the meanings indicated:
The unobstructed vertical distance through the free atmosphere
between the lowest opening from any pipe or faucet supplying water
to a tank or plumbing fixture, including but not limited to a swimming
pool, wading pool, garden pool, fish tank or other device, and the
flood-level rim of the receptacle.
Accepted by the Village Board of Trustees and by the Nassau
County Department of Health, where required, as meeting an applicable
specification stated or cited in this Part 3 or as suitable for the
proposed use.
Any water source or system other than the potable water supplied
by the Village of Sands Point that may be available in the building
or on the premises.
The flow of water or other liquids, mixtures or substances
into the distributing pipes of a potable supply of water from any
source or sources other than its intended source.
A device or means to prevent backflow.
Backflow resulting from negative pressures in the distributing
pipes of the potable water supply.
The Board of Trustees of the Village of Sands Point.
A self-closing device which is designed to permit the flow
of fluids in one direction and to close if there is a reversal of
flow.
See "pollution."
Any physical connection between a potable water supply and
any waste pipe, soil pipe, sewer drain or any unapproved source or
system. Furthermore, it is any potable water supply outlet which is
submerged or can be submerged in wastewater and or any other source
of contamination. See "backflow" and "backsiphonage."
Any pipe that carries wastewater or waterborne wastes within
the drainage system of a building.
Installed receptacles, devices or appliances supplied with
water or that receive or discharge liquids or liquid-borne wastes.
The edge of the receptacle from which water overflows, which
shall include but not be limited to the overflow rim of a swimming
pool, wading pool or garden pool.
Any arrangement of plumbing, including piping and fixtures,
whereby a cross-connection is created.
Any condition, devices or practices in the water supply system
and its operation which create or, in the judgment of the Superintendent,
may create a danger to the health and well-being of the water consumer.
An example of a health hazard is a structural defect in the water
supply system, whether of location, design or construction, that regularly
or occasionally may prevent satisfactory purification of the water
supply or cause it to be polluted from extraneous sources.
A pressure vessel in which air pressure acts upon the surface
of the water contained within the vessel, pressurizing the water distribution
piping connected to the vessel.
The open end of the water supply pipe through which the water
is discharged into the plumbing fixture.
Water flowing in an opposite direction to the direction intended
(backflow).
Includes the water supply and distribution pipes, plumbing
fixtures and traps; soil, waste and vent pipes; building drains and
building sewers, including their respective connections, devices and
appurtenances within the property lines of the premises; and water-treating
or water-using equipment.
The presence of any foreign substance (organic, inorganic,
radiological or biological) in water that tends to degrade its quality
so as to constitute a hazard or impair the usefulness of the water.
An assembly of differential valves and check valves, including
an automatically opened spillage port to the atmosphere, designed
to prevent backflow.
That pressure measured in any waterline without flow.
The Superintendent of the Village of Sands Point Water Department.
The receiving nonpressure vessel forming part of the air
gap separation between a potable and an auxiliary supply.
Any pressure less than that exerted by the atmosphere.
A vacuum breaker designed so as not to be subjected to static
line pressure.
A vacuum breaker designed to operate under conditions of
static line pressure.
The Incorporated Village of Sands Point.
Water that is not safe for human consumption or which is
of questionable potability.
Any water which complies with the provisions of Part 72,
Drinking Water Standards, of the Administrative Rules and Regulations
of the New York State Commissioner of Health.
A.Â
General. A potable water supply system shall be designed,
installed and maintained in such manner as to prevent contamination
from nonpotable water, liquids, solids or gases from being introduced
into the potable water supply through cross-connections or any other
piping connecting to the system.
B.Â
Cross-connections prohibited. Cross-connections between
potable water systems and other systems or equipment containing water
or other substances of unknown or questionable safety are prohibited
except where and when, as approved by the authority having jurisdiction,
suitable protective devices such as the reduced-pressure backflow
presenter or equal are installed, tested and maintained to ensure
proper operation on a continuing basis.
C.Â
Interconnections. Interconnection between two or more
public water supplies shall be permitted only with the written approval
of the Village and the Nassau County Department of Health.
D.Â
Individual water supplies. Cross-connections between
an individual water supply and a potable public supply shall not be
made unless specifically approved in writing by the Village and the
Nassau County Department of Health.
E.Â
Connections to boilers. Potable water connections
to boiler-fed water systems where chemical treatment is applied shall
be made through an air gap or provided with an approved backflow preventer.
F.Â
Prohibited connections to fixtures and equipment. Connection to the potable water supply system for the following is prohibited unless protected against backflow in accordance with § 168-76 or as set forth as follows:
(1)Â
Bidets.
(2)Â
Operating or dissection tables or similar equipment.
In such installation, the hose used for water supply shall terminate
at least 12 inches away from every point of the table or attachments.
(3)Â
Pumps for nonpotable water, chemicals or other substances.
Priming connections may be made only through an air gap.
(4)Â
Building drainage, sewer or vent systems.
(5)Â
Any other fixture or similar hazard.
Except where potable water provided for a refrigerator
condenser or cooling jacket is entirely outside the piping or tank
containing a toxic refrigerant and two separate thicknesses of metal
separate from the potable water supply, the inlet connection shall
be provided with an approved check valve. Also adjacent to and at
the outlet side of the check valve, an approved pressure relief valve
shall be provided. Such valve shall be set to relieve at five pounds
per square inch above the maximum water pressure at the point of installation
if the refrigeration units contain more than 20 pounds of refrigerants.
A.Â
Water outlets. A potable water system shall be protected
against backflow and backsiphonage by providing and maintaining at
each outlet:
(1)Â
Air gap. An air gap, as specified in Subsection B, between the potable water outlet and the flood-level rim of the fixture it supplies, including but not limited to swimming pools, wading pools or fish tanks, or between the outlet and any other source of contamination; or
(2)Â
Backflow presenter. A device or means to prevent backflow.
B.Â
Minimum required air gap.
(1)Â
How measured. The minimum required air gap shall be
measured vertically from the lowest end of a potable water outlet
to the flood rim or line of the fixture or receptacle into which it
discharges.
(2)Â
Size. The minimum required air gap shall be twice
the effective opening of a potable water outlet unless the outlet
is a distance less than three times the effective opening away from
a wall or similar vertical surface, in which case the minimum required
air gap shall be three times the effective opening of the outlet.
In no case shall the minimum required air gap be less than as shown
in the table below for plumbing fixtures or less than 12 inches for
swimming pools, wading pools, garden pools and fish tanks.
Minimum Air Gaps for Generally Used Plumbing
Fixtures
| |||
---|---|---|---|
Fixture
|
Minimum Air Gap
(inches)
When Not Affected by Near
Wall1
|
When Affected by Near Wall2
| |
Lavatories and other fix- tures with effective
openings not greater than 1/2 inch in diameter
|
1.0
|
1.50
| |
Sinks, laundry trays, goose- neck bath faucets
and other fixtures with effective openings not greater than 3/4 inch
in diameter
|
1.5
|
2.25
| |
Over-rim bath fillers and other fixtures with
effective openings not greater than 1 inch in diameter Fixture
|
2.0 Minimum Air Gap (inches) When Not Affected
by Near Wall1
|
3.0 When Affected by Near Wall2
| |
Drinking water fountains, single orifice 7/16
(0.437) inch in diameter or multiple orifices having total area of
0.150 square inch (area of circle: 7/16 inch in diameter)
|
1.0
|
1.50
| |
Effective openings greater than 1 inch
|
Note 3
|
Note 4
|
NOTES:
| |
---|---|
1Sidewalls, ribs
or similar obstructions do not affect air gaps when spaced from inside
edge of spout opening a distance greater than three times the diameter
of the effective opening for a single wall, or a distance greater
than four times the diameter of the effective opening for two intersecting
walls.
| |
2Vertical walls,
ribs or similar obstructions extending from the water surface to or
above the horizontal plane of the spout opening require a greater
air gap when spaced closer to the nearest inside edge of spout opening
than specified in Note 1 above. The effect of three or more such vertical
walls or ribs has not been determined. In such cases, the air gap
shall be measured from the top of the wall.
| |
3Two times diameter
of effective opening.
| |
4Three times diameter
of effective opening.
|
C.Â
Approval of devices. Before any device for the prevention
of backflow or backsiphonage is installed, it shall have first been
approved in writing by the Village. In addition, the Department of
Health approval is required in those instances where an air gap or
control device, for which an acceptable list has been established
by the New York State Department of Health, is utilized to protect
the water supply distribution system for protection against backflow,
and such device shall be maintained in good working condition by the
owner of the premises responsible for the maintenance of the system.
If found to be defective or inoperative, it shall be repaired or replaced
promptly.
[Amended 8-28-2001 by L.L. No. 6-2001]
D.Â
Design criteria for physical connection control devices
shall be as follows:
Control Devices
| |||||||
---|---|---|---|---|---|---|---|
Condition
|
Air Gap
|
Reduced Pressure Device
|
Double Check Valve Assembly
|
Atmospheric Breaker
|
Pressure Vacuum Breaker
| ||
Any physical connection which may be subject
to back pressure involving:
| |||||||
Hazardous substances1
|
X
|
X
| |||||
Nonhazardous substances2
|
X
|
X
|
X
| ||||
Any physical connection not subject to back
pressure involving:
| |||||||
Hazardous substances1
|
X
|
X
|
X
|
X
| |||
Nonhazardous substances2
|
X
|
X
|
X
|
X
|
X
|
NOTES:
| |
---|---|
1A hazardous substance
includes sewage, lethal chemicals or other substances which, if introduced
into the public water supply system, would or may endanger the health
of the consumer.
| |
2A nonhazardous substance
would not endanger the health of the consumer but would be a nuisance
if introduced into the public water supply system.
|
E.Â
Installation of devices.
(1)Â
Vacuum breakers. Vacuum breakers shall be installed
with the critical level at least six inches above the flood-level
rim of the fixture they serve and on the discharge side of the last
control valve to the fixture. No shutoff valve or faucet shall be
installed beyond the vacuum breaker. For closed equipment or vessels
such as pressure sterilizers, the top of the vessel shall be treated
as the flood-level rim but a check valve shall be installed on the
discharge side of the vacuum breaker.
(2)Â
Reduced pressure backflow preventer. A reduced-pressure-type
backflow preventer may be installed subject to full static pressure.
(3)Â
Devices of all types. Backflow and backsiphonage preventing
devices shall be accessibly located, preferably in the same room with
the fixture they serve. Installation in utility or service spaces
is also permitted, provided that they are readily accessible.
F.Â
Protective devices required. Approved devices to protect
against backflow and backsiphonage shall be installed at all fixtures
and equipment where backflow and/or backsiphonage may occur and where
a minimum air gap cannot be provided between the water outlet to the
fixture or equipment and its flood-level rim.
(1)Â
Connections not subject to back pressure. Where a
water connection is not subject to back pressure, a vacuum breaker
shall be installed on the discharge side of the last valve on the
line serving the fixture or equipment. A list of some conditions requiring
protective devices of this kind is given in the table below, entitled
"Cross-Connections Where Protective Devices Are Required and Critical
Level (C-L) Settings for Vacuum Breakers." NOTE: "Critical level"
(C-L) is defined as the level to which the vacuum breaker may be submerged
before backflow will occur. Where the C-L is not shown on the preventer,
the bottom of the device shall be taken as the C-L.
Cross-Connections Where Protective Devices
Are Required and Critical Level (C-L) Settings for Vacuum Breakers
| |||
---|---|---|---|
Fixture or Equipment
|
Method of Installation
| ||
Aspirators and ejectors
|
C-L at least 6 inches above flood level of receptacle
served
| ||
Dental units
|
C-L at least 6 inches above flood level of machine.
Install on both hot- and cold-water supply line.
| ||
Models without built-in breakers
|
C-L at least 6 inches above flood-level rim
of bowl
| ||
Dishwashing machines
|
C-L at least 6 inches above flood level of machine.
Install on both hot- and cold-water supply line.
| ||
Flushometers (closet and urinal)
|
C-L at least 6 inches above top of fixture supplied
| ||
Garbage can cleaning machine
|
C-L at least 6 inches above flood level of machine.
Install on both hot- and cold-water supply line.
| ||
Hose outlets Cross-Connections
|
C-L at least 6 inches above highest point on
hose line
| ||
Laundry machines
|
C-L at least 6 inches above flood level of machine.
Install on both hot- and cold-water supply lines.
| ||
Lawn sprinklers
|
C-L at least 12 inches above highest sprinkler
or discharge outlet
| ||
Steam tables
|
C-L at least 6 inches above flood level
| ||
Tank and vats
|
C-L at least 6 inches above flood-level rim
or line
| ||
Trough urinals
|
C-L at least 30 inches above perforated flush
pipe
| ||
Flush tanks
|
Equip with approved ball cock. Where ball cocks
touch tank water, equip with vacuum breaker at least 1 inch above
overflow outlets. Where ball cock does not touch tank water, install
ball cock outlet at least 1 inch above overflow outlet or provide
vacuum breaker as specified above.
| ||
Hose bibbs (where aspirators or ejectors could
be connected)
|
C-L at least 6 inches above flood level of receptacle
served
|
(2)Â
Connections subject to back pressure. Where a potable
water connection is made to a line, fixture, tank, vat, pump or other
equipment with a hazard of backflow or backsiphonage where the water
connection is subject to back pressure and an air gap cannot be installed,
the Superintendent may require the use of an approved reduced-pressure
backflow preventer. A partial list of such cross-connections which
may be subject to back pressure is as follows:
[Amended 8-28-2001 by L.L. No. 6-2001]
G.Â
Double check-double gate valves. The Superintendent
may authorize installation of approved double check double valve assemblies
with test cocks as protective devices against backflow in connections
between a potable water system and other fluid systems which present
no significant health hazard in the judgment of the Superintendent.
H.Â
Low-pressure cutoff required on booster pumps. When
a booster pump is used on a water pressure booster system and the
possibility exists that a positive pressure of 10 pounds per square
inch or less may occur on the suction side of the pump, there shall
be installed a low-pressure cutoff on the booster pump to prevent
the creation of a vacuum or negative pressure on the suction side
of the pump, thus cutting off water to other outlets.
I.Â
Maintenance requirements.
(1)Â
General requirements. It shall be the responsibility
of building and premises owners to maintain all backflow presenters
and vacuum breakers within the building or on the premises in good
working order and to make no piping or other arrangements for the
purpose of bypassing backflow devices.
(2)Â
Reduced-pressure backflow preventers. Periodic testing
and inspection schedules shall be established by the Village for all
reduced-pressure backflow preventers, and the interval between such
testing and inspections and maintenance service of each device shall
be established in accordance with the age and condition of the device.
Inspection intervals should not exceed one year, and maintenance service
should not exceed five years. These devices shall be inspected frequently
after the initial installation to assure that they have been installed
properly and that debris resulting from the installation has not interfered
with the functioning of the device. The testing procedures shall be
in accordance with the manufacturer's instructions when approved by
the Village. Testing shall be conducted by a state-certified inspector,
and the devices shall bear an inspection certification tag indicating
the date of inspection and the name and address of the plumber who
conducted such inspection.
[Amended 8-28-2001 by L.L. No. 6-2001]
The Village shall give notice of violation in
writing to the owner or authorized agent of the owner of the building
or premises in which a violation of this Part 3 is found. The Village
shall set a reasonable time, not exceeding 120 days, for the owner
to have the violation removed or corrected. Upon failure of the owner
to have the defect corrected by the end of the specified time interval,
the Village may, if in its judgment an imminent health hazard exists,
cause the water service to the building or premises to be terminated
and/or recommend such additional fines or penalties to be invoked
as herein may be provided.
[Amended 12-17-1991 by L.L. No. 8-1991; 8-28-2001 by L.L. No. 6-2001]
Any owner or authorized agent of the owner responsible for the maintenance of the plumbing systems in the building who violates any provision hereof or knowingly permits a violation to remain uncorrected after the expiration of time set by the Village shall, upon conviction thereof, be required to pay a fine of $250 for each violation. Each day of failure to comply with the requirements of this Part 3 after the specified time provided under § 168-77 shall constitute a separate violation.
[Added 8-28-2001 by L.L. No. 6-2001]
Should any section or provision of this chapter
be adjudged as invalid by any court of competent jurisdiction, such
judgment shall not affect, impair or invalidate any other part of
this chapter or the remainder thereof but shall be confined in its
operation to only that section or part thereof directly or necessarily
involved in the controversy in which such judgment shall have been
rendered.