Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Sands Point, NY
Nassau County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Adopted 3-16-1976 by L.L. No. 2-1976, as published in the Book of Ordinances of the Village of Sands Point and as last supplemented 8-25-1981]
It is the intent of the Village of Sands Point (hereinafter referred to as "Village") that this Part 3 shall apply in situations of potential major health hazard, such as swimming pools, automatic sprinklers, private wells, fish and garden pools and in such additional situations as in the discretion of the Village must be subject to the requirements of this Part 3.
[Amended 8-28-2001 by L.L. No. 6-2001]
A. 
All backflow prevention devices installed shall be tested annually. All new devices shall be tested when initially installed. Testing shall be conducted by a New York State Department of Health certified backflow prevention device tester. The tester shall file the required New York State forms and results within 30 days of conducting the tests. Any device that fails the test shall be repaired and required to pass the test.
B. 
It shall be the responsibility of the owner of the building or premises to have the devices tested annually. Failure to comply shall be punishable by a fine of $500 and/or the shutoff of the water service line.
[Amended 3-22-2022 by L.L. No. 5-2022]
The Superintendent or his designated agent shall have the right of entry to premises or into any building, during reasonable hours, for the purpose of making inspection of the plumbing systems installed in such buildings or premises, provided that, with respect to the inspection of any single-family dwelling, consent to such inspection shall first be obtained from a person of suitable age and discretion therein or in control thereof. Failure to give consent to a reasonable request to inspect shall be considered a violation of this Part 3.
As used in this Part 3, the following terms shall have the meanings indicated:
Air Gap
The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank or plumbing fixture, including but not limited to a swimming pool, wading pool, garden pool, fish tank or other device, and the flood-level rim of the receptacle.
Approved
Accepted by the Village Board of Trustees and by the Nassau County Department of Health, where required, as meeting an applicable specification stated or cited in this Part 3 or as suitable for the proposed use.
Auxiliary Supply
Any water source or system other than the potable water supplied by the Village of Sands Point that may be available in the building or on the premises.
Backflow
The flow of water or other liquids, mixtures or substances into the distributing pipes of a potable supply of water from any source or sources other than its intended source.
Backflow Preventer
A device or means to prevent backflow.
Backsiphonage
Backflow resulting from negative pressures in the distributing pipes of the potable water supply.
Board
The Board of Trustees of the Village of Sands Point.
Check Valve
A self-closing device which is designed to permit the flow of fluids in one direction and to close if there is a reversal of flow.
Contamination
See "pollution."
Cross-Connection
Any physical connection between a potable water supply and any waste pipe, soil pipe, sewer drain or any unapproved source or system. Furthermore, it is any potable water supply outlet which is submerged or can be submerged in wastewater and or any other source of contamination. See "backflow" and "backsiphonage."
Drain
Any pipe that carries wastewater or waterborne wastes within the drainage system of a building.
Fixture, Plumbing
Installed receptacles, devices or appliances supplied with water or that receive or discharge liquids or liquid-borne wastes.
Flood-Level Rim
The edge of the receptacle from which water overflows, which shall include but not be limited to the overflow rim of a swimming pool, wading pool or garden pool.
Hazardous Plumbing
Any arrangement of plumbing, including piping and fixtures, whereby a cross-connection is created.
Health Hazard
Any condition, devices or practices in the water supply system and its operation which create or, in the judgment of the Superintendent, may create a danger to the health and well-being of the water consumer. An example of a health hazard is a structural defect in the water supply system, whether of location, design or construction, that regularly or occasionally may prevent satisfactory purification of the water supply or cause it to be polluted from extraneous sources.
Hydropneumatic Tank
A pressure vessel in which air pressure acts upon the surface of the water contained within the vessel, pressurizing the water distribution piping connected to the vessel.
Inlet
The open end of the water supply pipe through which the water is discharged into the plumbing fixture.
Negative Water Pressure
Water flowing in an opposite direction to the direction intended (backflow).
Plumbing System
Includes the water supply and distribution pipes, plumbing fixtures and traps; soil, waste and vent pipes; building drains and building sewers, including their respective connections, devices and appurtenances within the property lines of the premises; and water-treating or water-using equipment.
Pollution
The presence of any foreign substance (organic, inorganic, radiological or biological) in water that tends to degrade its quality so as to constitute a hazard or impair the usefulness of the water.
Reduced-Pressure Backflow Preventer
An assembly of differential valves and check valves, including an automatically opened spillage port to the atmosphere, designed to prevent backflow.
Static Line Pressure
That pressure measured in any waterline without flow.
Superintendent
The Superintendent of the Village of Sands Point Water Department.
Surge Tank
The receiving nonpressure vessel forming part of the air gap separation between a potable and an auxiliary supply.
Vacuum
Any pressure less than that exerted by the atmosphere.
Vacuum Breaker, Nonpressure Type
A vacuum breaker designed so as not to be subjected to static line pressure.
Vacuum Breaker, Pressure Type
A vacuum breaker designed to operate under conditions of static line pressure.
Village
The Incorporated Village of Sands Point.
Water, Nonpotable
Water that is not safe for human consumption or which is of questionable potability.
Water, Potable
Any water which complies with the provisions of Part 72, Drinking Water Standards, of the Administrative Rules and Regulations of the New York State Commissioner of Health.
A. 
General. A potable water supply system shall be designed, installed and maintained in such manner as to prevent contamination from nonpotable water, liquids, solids or gases from being introduced into the potable water supply through cross-connections or any other piping connecting to the system.
B. 
Cross-connections prohibited. Cross-connections between potable water systems and other systems or equipment containing water or other substances of unknown or questionable safety are prohibited except where and when, as approved by the authority having jurisdiction, suitable protective devices such as the reduced-pressure backflow presenter or equal are installed, tested and maintained to ensure proper operation on a continuing basis.
C. 
Interconnections. Interconnection between two or more public water supplies shall be permitted only with the written approval of the Village and the Nassau County Department of Health.
D. 
Individual water supplies. Cross-connections between an individual water supply and a potable public supply shall not be made unless specifically approved in writing by the Village and the Nassau County Department of Health.
E. 
Connections to boilers. Potable water connections to boiler-fed water systems where chemical treatment is applied shall be made through an air gap or provided with an approved backflow preventer.
F. 
Prohibited connections to fixtures and equipment. Connection to the potable water supply system for the following is prohibited unless protected against backflow in accordance with § 168-76 or as set forth as follows:
(1) 
Bidets.
(2) 
Operating or dissection tables or similar equipment. In such installation, the hose used for water supply shall terminate at least 12 inches away from every point of the table or attachments.
(3) 
Pumps for nonpotable water, chemicals or other substances. Priming connections may be made only through an air gap.
(4) 
Building drainage, sewer or vent systems.
(5) 
Any other fixture or similar hazard.
Except where potable water provided for a refrigerator condenser or cooling jacket is entirely outside the piping or tank containing a toxic refrigerant and two separate thicknesses of metal separate from the potable water supply, the inlet connection shall be provided with an approved check valve. Also adjacent to and at the outlet side of the check valve, an approved pressure relief valve shall be provided. Such valve shall be set to relieve at five pounds per square inch above the maximum water pressure at the point of installation if the refrigeration units contain more than 20 pounds of refrigerants.
A. 
Water outlets. A potable water system shall be protected against backflow and backsiphonage by providing and maintaining at each outlet:
(1) 
Air gap. An air gap, as specified in Subsection B, between the potable water outlet and the flood-level rim of the fixture it supplies, including but not limited to swimming pools, wading pools or fish tanks, or between the outlet and any other source of contamination; or
(2) 
Backflow presenter. A device or means to prevent backflow.
B. 
Minimum required air gap.
(1) 
How measured. The minimum required air gap shall be measured vertically from the lowest end of a potable water outlet to the flood rim or line of the fixture or receptacle into which it discharges.
(2) 
Size. The minimum required air gap shall be twice the effective opening of a potable water outlet unless the outlet is a distance less than three times the effective opening away from a wall or similar vertical surface, in which case the minimum required air gap shall be three times the effective opening of the outlet. In no case shall the minimum required air gap be less than as shown in the table below for plumbing fixtures or less than 12 inches for swimming pools, wading pools, garden pools and fish tanks.
Minimum Air Gaps for Generally Used Plumbing Fixtures
Fixture
Minimum Air Gap
(inches)
When Not Affected by Near Wall1
When Affected by Near Wall2
Lavatories and other fix- tures with effective openings not greater than 1/2 inch in diameter
1.0
1.50
Sinks, laundry trays, goose- neck bath faucets and other fixtures with effective openings not greater than 3/4 inch in diameter
1.5
2.25
Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter Fixture
2.0 Minimum Air Gap (inches) When Not Affected by Near Wall1
3.0 When Affected by Near Wall2
Drinking water fountains, single orifice 7/16 (0.437) inch in diameter or multiple orifices having total area of 0.150 square inch (area of circle: 7/16 inch in diameter)
1.0
1.50
Effective openings greater than 1 inch
Note 3
Note 4
NOTES:
1Sidewalls, ribs or similar obstructions do not affect air gaps when spaced from inside edge of spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.
2Vertical walls, ribs or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening require a greater air gap when spaced closer to the nearest inside edge of spout opening than specified in Note 1 above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the air gap shall be measured from the top of the wall.
3Two times diameter of effective opening.
4Three times diameter of effective opening.
C. 
Approval of devices. Before any device for the prevention of backflow or backsiphonage is installed, it shall have first been approved in writing by the Village. In addition, the Department of Health approval is required in those instances where an air gap or control device, for which an acceptable list has been established by the New York State Department of Health, is utilized to protect the water supply distribution system for protection against backflow, and such device shall be maintained in good working condition by the owner of the premises responsible for the maintenance of the system. If found to be defective or inoperative, it shall be repaired or replaced promptly.
[Amended 8-28-2001 by L.L. No. 6-2001]
D. 
Design criteria for physical connection control devices shall be as follows:
Control Devices
Condition
Air Gap
Reduced Pressure Device
Double Check Valve Assembly
Atmospheric Breaker
Pressure Vacuum Breaker
Any physical connection which may be subject to back pressure involving:
Hazardous substances1
X
X
Nonhazardous substances2
X
X
X
Any physical connection not subject to back pressure involving:
Hazardous substances1
X
X
X
X
Nonhazardous substances2
X
X
X
X
X
NOTES:
1A hazardous substance includes sewage, lethal chemicals or other substances which, if introduced into the public water supply system, would or may endanger the health of the consumer.
2A nonhazardous substance would not endanger the health of the consumer but would be a nuisance if introduced into the public water supply system.
E. 
Installation of devices.
(1) 
Vacuum breakers. Vacuum breakers shall be installed with the critical level at least six inches above the flood-level rim of the fixture they serve and on the discharge side of the last control valve to the fixture. No shutoff valve or faucet shall be installed beyond the vacuum breaker. For closed equipment or vessels such as pressure sterilizers, the top of the vessel shall be treated as the flood-level rim but a check valve shall be installed on the discharge side of the vacuum breaker.
(2) 
Reduced pressure backflow preventer. A reduced-pressure-type backflow preventer may be installed subject to full static pressure.
(3) 
Devices of all types. Backflow and backsiphonage preventing devices shall be accessibly located, preferably in the same room with the fixture they serve. Installation in utility or service spaces is also permitted, provided that they are readily accessible.
F. 
Protective devices required. Approved devices to protect against backflow and backsiphonage shall be installed at all fixtures and equipment where backflow and/or backsiphonage may occur and where a minimum air gap cannot be provided between the water outlet to the fixture or equipment and its flood-level rim.
(1) 
Connections not subject to back pressure. Where a water connection is not subject to back pressure, a vacuum breaker shall be installed on the discharge side of the last valve on the line serving the fixture or equipment. A list of some conditions requiring protective devices of this kind is given in the table below, entitled "Cross-Connections Where Protective Devices Are Required and Critical Level (C-L) Settings for Vacuum Breakers." NOTE: "Critical level" (C-L) is defined as the level to which the vacuum breaker may be submerged before backflow will occur. Where the C-L is not shown on the preventer, the bottom of the device shall be taken as the C-L.
Cross-Connections Where Protective Devices Are Required and Critical Level (C-L) Settings for Vacuum Breakers
Fixture or Equipment
Method of Installation
Aspirators and ejectors
C-L at least 6 inches above flood level of receptacle served
Dental units
C-L at least 6 inches above flood level of machine. Install on both hot- and cold-water supply line.
Models without built-in breakers
C-L at least 6 inches above flood-level rim of bowl
Dishwashing machines
C-L at least 6 inches above flood level of machine. Install on both hot- and cold-water supply line.
Flushometers (closet and urinal)
C-L at least 6 inches above top of fixture supplied
Garbage can cleaning machine
C-L at least 6 inches above flood level of machine. Install on both hot- and cold-water supply line.
Hose outlets Cross-Connections
C-L at least 6 inches above highest point on hose line
Laundry machines
C-L at least 6 inches above flood level of machine. Install on both hot- and cold-water supply lines.
Lawn sprinklers
C-L at least 12 inches above highest sprinkler or discharge outlet
Steam tables
C-L at least 6 inches above flood level
Tank and vats
C-L at least 6 inches above flood-level rim or line
Trough urinals
C-L at least 30 inches above perforated flush pipe
Flush tanks
Equip with approved ball cock. Where ball cocks touch tank water, equip with vacuum breaker at least 1 inch above overflow outlets. Where ball cock does not touch tank water, install ball cock outlet at least 1 inch above overflow outlet or provide vacuum breaker as specified above.
Hose bibbs (where aspirators or ejectors could be connected)
C-L at least 6 inches above flood level of receptacle served
(2) 
Connections subject to back pressure. Where a potable water connection is made to a line, fixture, tank, vat, pump or other equipment with a hazard of backflow or backsiphonage where the water connection is subject to back pressure and an air gap cannot be installed, the Superintendent may require the use of an approved reduced-pressure backflow preventer. A partial list of such cross-connections which may be subject to back pressure is as follows:
[Amended 8-28-2001 by L.L. No. 6-2001]
(a) 
Chemical lines.
(b) 
Dock water outlets.
(c) 
Individual water supplies.
(d) 
Industrial process water lines.
(e) 
Pressure tanks.
(f) 
Pumps.
(g) 
Steam lines.
(h) 
Swimming pools.
(i) 
Tank and vats, bottom inlets.
(j) 
Hose bibbs.
G. 
Double check-double gate valves. The Superintendent may authorize installation of approved double check double valve assemblies with test cocks as protective devices against backflow in connections between a potable water system and other fluid systems which present no significant health hazard in the judgment of the Superintendent.
H. 
Low-pressure cutoff required on booster pumps. When a booster pump is used on a water pressure booster system and the possibility exists that a positive pressure of 10 pounds per square inch or less may occur on the suction side of the pump, there shall be installed a low-pressure cutoff on the booster pump to prevent the creation of a vacuum or negative pressure on the suction side of the pump, thus cutting off water to other outlets.
I. 
Maintenance requirements.
(1) 
General requirements. It shall be the responsibility of building and premises owners to maintain all backflow presenters and vacuum breakers within the building or on the premises in good working order and to make no piping or other arrangements for the purpose of bypassing backflow devices.
(2) 
Reduced-pressure backflow preventers. Periodic testing and inspection schedules shall be established by the Village for all reduced-pressure backflow preventers, and the interval between such testing and inspections and maintenance service of each device shall be established in accordance with the age and condition of the device. Inspection intervals should not exceed one year, and maintenance service should not exceed five years. These devices shall be inspected frequently after the initial installation to assure that they have been installed properly and that debris resulting from the installation has not interfered with the functioning of the device. The testing procedures shall be in accordance with the manufacturer's instructions when approved by the Village. Testing shall be conducted by a state-certified inspector, and the devices shall bear an inspection certification tag indicating the date of inspection and the name and address of the plumber who conducted such inspection.
[Amended 8-28-2001 by L.L. No. 6-2001]
The Village shall give notice of violation in writing to the owner or authorized agent of the owner of the building or premises in which a violation of this Part 3 is found. The Village shall set a reasonable time, not exceeding 120 days, for the owner to have the violation removed or corrected. Upon failure of the owner to have the defect corrected by the end of the specified time interval, the Village may, if in its judgment an imminent health hazard exists, cause the water service to the building or premises to be terminated and/or recommend such additional fines or penalties to be invoked as herein may be provided.
[Amended 12-17-1991 by L.L. No. 8-1991; 8-28-2001 by L.L. No. 6-2001]
Any owner or authorized agent of the owner responsible for the maintenance of the plumbing systems in the building who violates any provision hereof or knowingly permits a violation to remain uncorrected after the expiration of time set by the Village shall, upon conviction thereof, be required to pay a fine of $250 for each violation. Each day of failure to comply with the requirements of this Part 3 after the specified time provided under § 168-77 shall constitute a separate violation.
[Added 8-28-2001 by L.L. No. 6-2001]
Should any section or provision of this chapter be adjudged as invalid by any court of competent jurisdiction, such judgment shall not affect, impair or invalidate any other part of this chapter or the remainder thereof but shall be confined in its operation to only that section or part thereof directly or necessarily involved in the controversy in which such judgment shall have been rendered.