The mobile home park area shall be subject to the rules and regulations, where provided, of the Borough of Lake City fire prevention authority.
Mobile home park areas shall be kept free of litter, rubbish and other flammable materials, and the park owner or operator will be responsible.
Portable fire extinguishers of a type approved by the fire prevention authority shall be kept in public service buildings under park control, and a sufficient number shall be maintained throughout the park in readily accessible and well-marked positions.
A. 
Fire hydrants shall be installed if their water supply, source is capable of serving them in accordance with the following requirements:
(1) 
The water supply source shall permit the operation of a minimum of two one-and-one-half-inch hose streams.
(2) 
Each of two nozzles, held four feet above the ground, shall deliver at least 75 gallons of water per minute at a flowing pressure of at least 30 pounds per square inch at the highest point of the park.
B. 
Fire hydrants, if provided, shall be located within 600 feet of any mobile home, service building or other structure in the park and shall be installed by the park owner in accordance with the Borough of Lake City specifications.