Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Wolcott, NY
Wayne County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Whenever the Plumbing Inspector determines that it is not practical to protect drinking water systems on premises against entry of water from a source or piping system or equipment that cannot be approved as safe or potable for human use, an entirely separate drinking water system shall be installed to supply water at points convenient for consumers.
Water systems, for fighting fire, derived from a supply that cannot be approved as safe or potable for human use or to which chemicals are added shall, wherever practicable, be kept wholly separate from drinking water pipelines and equipment. In cases where the domestic water system is used for both drinking and fire-fighting purposes, approved backflow prevention devices shall be installed to protect such individual drinking water lines as are not used for fire-fighting purposes.
Potable water pipelines connected to equipment for industrial processes or operations shall be protected by a suitable backflow prevention device located beyond the last point from which drinking water may be taken, which device shall be provided on the feed line to process piping or equipment. In the event that the particular process liquid is especially corrosive or apt to prevent reliable action of the backflow prevention device, air-gap separation shall be provided. These devices shall be tested by the water user at least once a year or more often in those instances where successive inspections indicate repeated failure. The devices shall be repaired, overhauled or replaced whenever they are found to be defective. These tests must be performed by a qualified backflow prevention device tester, and records of tests, repairs and replacement shall be kept and made available to the water purveyor and the Health Department upon request.
Sewage pumps shall not have priming connections directly off any drinking water systems. No connections shall exist between the drinking water system and any other piping, equipment or tank in any sewage treatment plant or sewage pumping station.
A. 
Where the circumstances are such that there is special danger to health by the backflow of sewage, as from sewers, toilets, hospital bedpans and the like, into a drinking water system, a dependable device or devices shall be installed to prevent such backflow.
B. 
The purpose of this chapter is not to transcend local plumbing regulations, but only to deal with those extraordinary situations where sewage may be forced or drawn into the drinking water piping. This chapter do not attempt to eliminate at this time the hazards of back-siphonage through flushometer valves on all toilets, but to deal with those situations where the likelihood of vacuum conditions in the drinking water system is definite and there is special danger to health. Devices suited to the purpose of avoiding back-siphonage from plumbing fixtures are roof tanks, barometric loops or separate pressure systems separately piped to supply such fixtures, recognized approved vacuum or siphon breaker and other backflow protective devices which have been proved by appropriate tests to be dependable for destroying the vacuum.
C. 
Inasmuch as many of the serious hazards of this kind are due to water supply piping which is too small, thereby causing vacuum conditions when fixtures are flushed or water is drawn from the system in other ways, it is required that water supply piping that is too small be enlarged whenever possible.
Backflow protection by a suitable backflow prevention device shall be provided on each drinking water pierhead outlet used for supplying vessels at piers or waterfronts. These assemblies must be located where they will prevent the return of any water from the vessel into the drinking water pipeline or into another adjacent vessel. This will prevent such practices as connecting the ship fire-pumping or sanitary-pumping system with a dock hydrant and thereby pumping contaminated water into the drinking water system and thence to adjacent vessels or back into the public mains.
Where the premises contain dual or multiple water systems and piping, the exposed portions of pipelines shall be painted, banded or marked at sufficient intervals to distinguish clearly which water is safe and which is not safe. All outlets from secondary or other potentially contaminated systems shall be posted as being contaminated and unsafe for drinking purposes. All outlets intended for drinking purposes shall be plainly marked to indicate that fact.