Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Fox Point, WI
Milwaukee County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
The Wisconsin Uniform Dwelling Code, Chapter SPS 323 of the Wisconsin Administrative Code, and all amendments thereto are hereby made a part of this code by reference and shall apply to all one- and two-family dwellings and alterations and additions thereto.
NOTE: Before proceeding with the construction, installation, erection, alteration or remodeling of any boiler, furnace, incinerator, wood burner, heat-producing apparatus, air-cooled, water-cooled or mechanically cooled air conditioning or refrigeration system, storage tanks or other equipment pertaining to the use of flammable liquids, a permit shall be first obtained from the Building Inspector.
A. 
Temporarily out-of-service. Tanks shall be rendered "temporarily out-of-service" only when it is planned that they will return to active service at the location within 90 days. The following steps shall be carried successively:
(1) 
Removal of a flammable liquid which can be pumped out with a service pump.
(2) 
Cap or plug the fill line, gauge opening and pump suction, using appropriate sealing compound on pipe fittings. If fill line and gauge opening are equipped with caps which can be properly locked, the secure locking of these caps is sufficient.
(3) 
Leave the vent line open.
B. 
Abandoned tanks. Tanks which are no longer in service may be rendered "temporarily out-of-service" pending their removal in accordance with the procedure outlined in Subsection E.
C. 
Leaking tanks. All tanks found to be leaking shall be removed as per Subsection E(5). Such removal shall be completed within the time required by the Village Building Inspector, and no later than 60 days from the date of notice from the Building Inspector.
[Amended 8-13-2013 by Ord. No. 2013-08]
D. 
Change in use. Whenever there is a change in use of a premises which no longer requires the use of existing underground tanks, they shall be removed as per Subsection E(5). This shall apply to all premises where the use has already changed and all future changes in use. Such removal shall be completed within the time required by the Village Building Inspector, and no later than 60 days from the date of notice from the Building Inspector.
[Amended 8-13-2013 by Ord. No. 2013-08]
E. 
Removal of tanks. Tanks shall be removed according to the following successive steps:
(1) 
Remove all flammable liquid from connecting lines and tank.
(2) 
Disconnect and remove, insofar as possible, the suction, inlet, gauge and vent lines.
(3) 
Cap or plug open ends of remaining lines.
(4) 
Close all openings in the tank with pipe plugs before the tank is removed from the ground.
(5) 
Remove the tank from the premises within 72 hours from the time the tank is uncovered. This seventy-two-hour period commences upon the initial digging or excavation to remove the tank, and terminates only when the tank is physically removed from the site.
[Amended 8-13-2013 by Ord. No. 2013-08]
(6) 
Keep the tank tightly sealed with plugs or caps until it is removed from the premises and during transportation upon its removal.
F. 
If removal of the tank from the ground would affect the structural integrity of the building and if the Building Inspector and/or the Fire Inspector determines a condition of hardship to exist, the tank may be abandoned in place and filled with an inert material after emptying and cleaning of the tank. The tank cleaning would be performed by a certified tank cleaner.
[Added 5-28-1991 by Ord. No. 91-574]
A. 
Permit requirements.
(1) 
Permit required. Except as hereinafter provided, before proceeding with the construction, erection or installation of any air-cooled, water-cooled or mechanically cooled air-conditioning or refrigeration system or unit or backup generator installations, in or to serve any building, a permit shall first be obtained from the Building Inspector.
(2) 
Permits shall not be required for the installation of any air-conditioning or refrigeration system or unit that does not use water for cooling and where the source of operating power is obtained by plugging in an electrical cord connection to an electrical outlet. This subsection shall be applicable to portable units.
(3) 
Application for a permit shall be made by the installing contractor upon a form provided by the Building Inspector, shall be filled out completely and shall provide the following information:
(a) 
Name and address of contractor.
(b) 
Location of premises where installation is proposed.
(c) 
Name and address of owner.
(d) 
Location of unit on premises, including distance to lot lines for exterior apparatus.
(e) 
Manufacturer's identification, classification and size of unit.
(f) 
Nature of coolant, if applicable.
(g) 
If water cooled, source of water and method of discharging wastewater. (Refer to Department of Building Inspection.)[1]
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions, Art. II).
(h) 
Where water conservation devices are required, manufacturer's name, identification, classification and size of equipment.
(i) 
Such additional information as shall be required by the Building Inspector.
B. 
Exterior structures. Where any unit of an air-conditioning or refrigeration system or backup generator installation is located outside of the structure, said unit shall comply with setback requirements for accessory structures as set forth in the Chapter 745, Zoning, and said location shall be subject to approval of the Building Inspector. Said location shall not, by noise or sight, be detrimental to adjoining property. As an exception to the requirements of this subsection, however, the Village Manager may authorize a temporary backup generator installation to be located anywhere on a lot if the Village Manager finds that the generator serves a public purpose and will be removed no later than 12 months from the date of the approval, subject to the temporary structure approval procedure described in § 745-7D of this Code.
[Amended 2-12-2010 by Ord. No. 2010-02]
A. 
Domestic type incinerators shall meet the requirements of the State of Wisconsin, Department of Natural Resources as contained in Chapter NR 154, Wis. Adm. Code. Said Department shall have approving authority for the equipment involved. Installation shall conform to the following requirements, unless superseded by the manufacturer's requirements.
B. 
Gas burner connections. Where a gas burner is used, a lever handle shutoff cock shall be provided before the union at an accessible location in the gas line at the rear of the burner. Incinerators furnished with means for automatic ignition of the gas at the main burner shall be equipped with a device which will automatically shut off the main gas supply in the event the means of ignition becomes inoperative or the means of keeping the valve of the device open becomes inoperative or both.
C. 
Mounting.
(1) 
Domestic-type incinerators, except as hereinafter provided, shall be mounted on floors of fire-resistive construction with noncombustible flooring or surface finish and with no combustible material against the underside thereof. Such construction shall extend not less than 12 inches beyond the incinerator base on all sides, except that at the front or side where ashes are removed, it shall extend not less than 18 inches beyond the incinerator.
(2) 
Domestic-type incinerators that are specifically approved for installation on a combustible floor may be mounted in accordance with the conditions of such approval.
D. 
Masonry chimneys for incinerators. Masonry chimneys for domestic type incinerators shall be constructed in accordance with the requirements for masonry chimneys. All flues shall terminate in a substantially constructed spark arrester with openings not greater than 1/2 inch or be provided with other suitable means for avoiding discharge of fly particles. Such screen shall be kept in repair at all times.
(1) 
Domestic-type incinerators shall be connected to a chimney suitable for solid-fuel-burning appliances.
E. 
Clearances.
(1) 
Domestic-type incinerators, except as provided herewith, shall be installed to provide clearances between the unit and woodwork or other combustible material of not less than 36 inches at the sides and top and not less than 48 inches at the front, and in no case shall the clearance above the charging door be less than 48 inches.
(2) 
Domestic-type incinerators that are specifically approved for installation with clearance less than specified above may be installed in accordance with the conditions of such approval, provided that in any case, the clearances shall be sufficient to afford ready accessibility for firing, clean out and any necessary servicing and with a minimum clearance of three inches between the sides and combustible material.
(3) 
Domestic-type incinerators may be installed in rooms, but not in confined spaces such as alcoves, with reduced clearance to woodwork or other combustible material, provided that the combustible material is protected with an approved protective material, but in no case shall this clearance be less than three inches to the protection.
F. 
Smoke pipes for incinerators.
(1) 
Domestic-type incinerator smoke pipes, except as herein provided, shall be installed to provide clearance of not less than 18 inches to woodwork or other combustible material.
(2) 
Domestic-type incinerator smoke pipes may be installed in rooms, but not in confined spaces such as alcoves, with reduced clearances to woodwork or other combustible material provided the combustible material is protected with an approved protective material.
(3) 
Domestic type incinerator smoke pipes shall not pass through any combustible wall or partition unless protected at the point of passage.[1]
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions, Art. II).
G. 
Refuse chutes. Refuse chutes shall not feed directly into incinerators.