Exciting enhancements are coming soon to eCode360! Learn more 🡪
Jefferson County, MO
 
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Ord. No. 11-0248 §1, 8-9-2011]
This code establishes construction standards for on-site sewage treatment systems. In accordance with the authority granted in Section 701.040, RSMo., this code establishes the standards and criteria for the design, location, installation and repair of individual on-site sewage treatment systems to promote the public health and general welfare and to protect the surface and ground waters of the State.
[Ord. No. 11-0248 §1, 8-9-2011; Ord. No. 18-0499, 12-10-2018]
All on-site wastewater treatment and treatment systems shall be located in accordance with the distances shown in Table 602.1. Distances shall be measured from the point in the treatment system closet to the property line, stream, lake, impoundment or well.
Table 602.1
Minimum Setback Distances
Minimum Distance From3
Tank1
(feet)
Treatment
Area2 (feet)
Lagoons6
(feet)
Private water supply well
50
100
100
Public water supply well
300
300
300
Cistern
25
25
25
Spring
50
100
100
Classified stream, lake or impoundment*
50
50
50
Stream or open ditch4
25
25
25
Property lines5
10
10**
100
Building foundation
15
15
100
Basement
15
25
100
Swimming pool
15
15
50
Water line under pressure
10
10
10
Suction water line
50
100
100
Upslope interceptor drains
-
10
10
Down slope interceptor drains
-
25
25
Top of slope of embankments or cuts of two (2) feet or more vertical height
-
20
20
Edge of surficial sink holes
50
100
500
Other soil absorption system except repair area
-
20
20
*
A classified stream is any stream that maintains permanent flow or permanent pools during drought periods and supports aquatic life.
**
Fifty (50) feet of downslope property line initially, but repair may be allowed to twenty-five (25) feet of downslope property line.
1
Includes sewage tanks, intermittent sand filters and dosing chambers.
2
Includes all systems (sand filter, wetland and the like) except wastewater stabilization ponds.
3
Unplugged abandoned wells or wells with less than eighty (80) feet casing depth shall have one hundred fifty (150) feet minimum distance from all above.
4
Sewage tanks and soil absorption systems shall never be located in the drainage area of a sinkhole.
5
The Code Official may grant minor variances to the property line setbacks when the project involves installation of drip absorption or trickle irrigation systems that are being installed to repair an existing system on an existing lot that is otherwise too small to maintain the regular setbacks. The Code Official must first determine from data supplied by the licensed designer that under normal operating conditions the effluent from the system will remain within the boundaries of the property.
6
The lagoon shall be located a minimum of two hundred (200) feet from the nearest existing adjoining residence.
[Ord. No. 11-0248 §1, 8-9-2011; Ord. No. 13-0459 §2, 12-10-2013]
A. 
Table 603.1(a) or 603.1(b) shall be used to determine the minimum design daily flow of sewage required in calculating the design volume of on-site sewage systems to serve selected types of establishments. The minimum design volume of sewage from any establishment shall be two hundred forty (240) gallons per day. Design of sewage treatment and treatment systems for establishments not identified in this code shall be determined using available flow data, water-using fixtures, occupancy or operation patterns and other measured data.
1. 
Volume determination. In determining the volume of sewage from single-family dwellings, the minimum flow rate shall be one hundred twenty (120) gallons per day per bedroom. The minimum volume of sewage from each single-family dwelling shall be two hundred forty (240) gallons per day. When the occupancy of a single-family dwelling exceeds two (2) persons per bedroom, the volume of sewage shall be determined by the maximum occupancy at a rate of sixty (60) gallons per person per day.
[Ord. No. 18-0499, 12-10-2018]
2. 
Other establishments. For establishments or housing developments other than a single-family residence, either Table 603.1(a) or Table 603.1(b) shall be used to estimate the sewage flow rate or actual measured flow rate for existing systems may be used. Values for estimated sewage flow for establishments having food service operations shall be increased by a factor of one and one-half (1½) to compensate for the high organic strength. Grease traps shall be required at food service facilities, meat markets and other places of business where the accumulation of grease or oils can cause premature failure of a soil absorption system. The following design criteria shall be met:
a. 
The grease trap shall conform to Plumbing and Drainage Institute Standard PDI-G101 or equivalent;
b. 
The grease trap shall be plumbed to receive all wastes associated with food handling and no toilet wastes;
c. 
The grease trap liquid capacity shall be sufficient to provide for at least five (5) gallons of storage per meal served per day, at least two-thirds (⅔) of the required septic tank liquid capacity, or a capacity as determined in accordance with the following formula:
LC = D x GL x ST x HR / 2 x LF
Where:
LC
=
grease trap liquid capacity (gallons)
D
=
number of seats in dining area
GL
=
gallons of wastewater per meal
(1.5 single-service; 2.5 full-service)
ST
=
storage capacity factor = 2.5
HR
=
number of hours open
LF
=
loading factor = (1.25 interstate highway
=
1.0 other highways and recreational areas
=
0.8 secondary roads);
d. 
Two (2) or more chambers must be provided, with total length-to-width ratio at least two (2) to one (1). Chamber opening and outlet sanitary tee must extend down at least fifty percent (50%) of the liquid depth;
e. 
Access manholes, with a minimum diameter of twenty-four (24) inches, shall be provided over each chamber and sanitary tee. The access manholes shall extend at least to finished grade and be designed and maintained to prevent surface water infiltration. The manholes shall also have readily removable covers to facilitate inspection and grease removal; and
f. 
Where it has been demonstrated that specially designed grease interceptors will provide improved performance, the grease trap liquid capacity may be reduced by up to fifty percent (50%).
3. 
Population to be served. Unless satisfactory justification can be given for using lower per-unit occupancies, the figures in Table 603.1(b) shall be used in determining the population for which to design the sewage works.
4. 
Reduction in sewage flow. Reductions in design sewage flow rates may be allowed by the Code Official on a case-by-case basis depending upon water conservation plans. Sewage flow rates may be reduced up to forty percent (40%) for gray water systems where the toilet wastes are discharged to a holding tank and disposed of off site or where waterless toilets are utilized.
Table 603.1(a)
Quantities of Domestic Sewage Flows
[Ord. No. 13-0459 §2, 12-10-2013]
Type of Establishment1
Flow (gallons per day per unit unless otherwise indicated)
Residential Units
Single-Family Dwelling
120/bedroom
Multiple-Family Dwelling (with laundry capabilities)
120/bedroom
Multiple-Family Dwelling (without laundry)
95/bedroom
Capabilities cottages
50/person (in excess of 2 persons/bedroom)
Manufactured Home Parks
300/home 2
Commercial Facilities
Transportation terminals (airports, bus stops, railroad stations, etc.)
5/passenger
Laundromats
580/machine
Beauty Shops (Style Shops)
125/chair
Bowling Lanes
50/lane
Business (other than those listed elsewhere in this table)
25/employee
Factories (exclusive of industrial waste)
25/person/shift
With showers
10/person/shift
Marinas
10/boat slip
With bathhouse
30/boat slip
Motels/Hotels
120/room
With cooking facilities
175/person
Offices (per shift)
25/person
Service Stations
250/water closet or urinal
24-hour Service Stations
325/water closet
Theaters: Movies
5/seat
Drive-in
15/vehicle space
Warehouses
30/employee
Public parks (toilets only)
5/user
Public parks with bathhouse
15 — 25/user
Camps
Construction or Work Camps
60/person
With chemical toilets
40/person
Summer Camps
60/person
Campgrounds/Recreational Vehicle Park (without water and sewer hookups)
100/campsites
Campgrounds/Recreational Vehicle Park (with water and sewer hookups)
120/space
Assembly & Mercantile
Retail
120/1,000 sq. ft. of retail sales area
Stadium, Auditorium, Theater, Drive-in
5/seat or space
Swimming Pools, Spas, and Bathhouses
10/person
Churches (not including a Kitchen, Food Service Facility, Day Care or Camp)
3/seat
Churches (with a Kitchen but not including Food Service Facility, Day Care or Camp)
5/seat
Food or Drink Establishment3
Food Service Facility, Day Care, Camp, or Country Club
20/member
Bar (not serving food)
20/seat
Restaurants
40/seat, or 40/15 sq. ft. of dining area whichever is greater
24-hour Restaurant
75/seat
Convenience Store
  <2,000 sq. ft. floor space
500 gal/day
  With food preparation
750 gal/day
  2,000 — 3,000 sq. ft. floor space
750 gal/day
  With food preparation
1,125 gal/day
  3,000 — 5,000 sq. ft. floor space
1,000 gal/day
  With food preparation
1,500 gal/day
  5,000 — 7,000 sq. ft. floor space
2,000 gal/day
  With food preparation
3,000 gal/day
>7,500 sq. ft. floor space
3,000 gal/day
  With food preparation
Under DNR regulation
Food Stands
  1) Per 100 square feet of food stand floor space
50 gal.
  2) Add per food employee
25 gal.
Other food service facilities
5/meal
Meat Markets
  1) Per 100 square feet of market floor space
50 gal.
  2) Add per market employee
25 gal.
Institutional3
Hospitals
300/bed
Day Care Facilities
15/person
Residential Care Facilities
60/person
Rest Homes and Nursing Homes
  With laundry
120/bed
  Without laundry
60/bed
Day Schools
  With cafeteria, gym, and showers
15/student
  With cafeteria only
12/student
  With neither cafeteria nor showers
10/student
Boarding Schools
60/person
1
Establishments with flows greater than three thousand gallons per day (3,000 gpd) shall be regulated under Chapter 644, RSMo., administered by the Department of Natural Resources.
2
Shall consider flow into the soil absorption system from manufactured homes where taps are allowed to run to prevent freezing.
3
Establishments processing food may be required to provide grease interceptors in an accessible location prior to the sewage treatment system.
Table 603.1(b)
Sewage Works Population/Design
Unit
Persons/Unit
Apartments or Condominiums
(1 bedroom)
(2 bedroom)
(3 bedroom)
2.0
3.0
3.7
Camper trailers with sewer hookup
3.0
Camper trailers without sewer hookup
2.5
Manufactured Homes
3.0 — 3.7
Motels
3.0
Residences
3.7
Note: Gallons per person per unit includes normal infiltration for residential systems.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
All proposed sites for on-site sewage treatment systems shall be evaluated as set forth in Article IV.
B. 
Soil Permeability. Soil permeability is that quality that enables soil to transmit water or air. It can be measured quantitatively in terms of flow of water through a unit cross section of saturated soil in unit time under specified temperature and hydraulic condition.
C. 
Soil Morphology. This evaluation shall be conducted by a licensed on-site soil evaluator unless an engineer or registered geologist has had special training and field experience that meets the requirements of this code.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
Building Sewers. Building sewers used to conduct wastewater from a building to an on-site wastewater treatment and treatment system shall be constructed of material meeting the minimum requirements of American Society for Testing and Materials (ASTM) Standards and listed by that agency for such use. Suitable materials meeting ASTM standards include: Acrylonitrile, butadiene styrene (ABS), cast-iron pipe, concrete pipe, copper or copper-alloy tubing, polyvinyl chloride (PVC) or vitrified clay pipe. Although listed by ASTM, asbestos cement pipe is prohibited. Building sewer specifications are as follows:
1. 
Size. Building sewers shall not be less than four (4) inches in diameter;
2. 
Slope. Building sewers shall be laid on a minimum slope of twelve (12) inches per one hundred (100) feet.
3. 
Cleanouts. A cleanout shall be provided at least every one hundred (100) feet and at every change in direction or slope if the change exceeds forty-five degrees (45°). A cleanout shall be provided between house and tank.
4. 
Connection to sewage tank. The pipe going into and out of the sewage tank shall be schedule 40 PVC or cast iron and shall extend a minimum of five (5) feet beyond the hole of excavation for the sewage tank.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
General. All liquid waste and gray water with the following exceptions shall discharge into the sewage tank. Roof, garage, footing, surface water, drainage, cooling water discharges and hazardous wastes shall be excluded from the sewage tank. Backwash from water softeners and swimming pool filtration systems shall be excluded from the sewage tank. In such event of excluding swimming pool filter backwash, the Department of Natural Resources shall be contacted for applicability of a discharge permit. All sewage tank effluent shall be discharged to a soil absorption system that is designed to retain the effluent upon the property from which it originated. All tanks regardless of material or method of construction shall:
1. 
Be water-tight and designed and constructed to withstand all lateral earth pressures under saturated soil conditions with the tank empty; and
2. 
Be designed and constructed to withstand a minimum of two (2) feet of saturated earth cover above the tank top.
B. 
Septic Tanks. Regardless of material or method of construction, septic tanks shall conform to the following criteria:
1. 
The liquid depth of any septic tank or its compartment shall be not less than thirty-six (36) inches. A liquid depth greater than six and one-half (6½) feet shall not be considered in determining tank capacity.
2. 
No tank or compartment shall have an inside horizontal dimension less than twenty-four (24) inches.
3. 
Inlet and outlet connections of the tank shall be protected by baffles or sanitary tees as defined in Subsection (B)(6).
4. 
The space in the tank between the liquid surface and the top of the inlet and outlet baffles shall not be less than twenty percent (20%) of the total required capacity, except that in horizontal cylindrical tanks, this space shall be not less than fifteen percent (15%) of the total required liquid capacity.
5. 
Inlet and outlet baffles shall be constructed of acid-resistant concrete, acid-resistant fiberglass or plastic.
6. 
Sanitary tees shall be affixed to the inlet or outlet pipes with a permanent water-proof adhesive. Baffles shall be integrally cast with the tank, affixed with a permanent water-proof adhesive or with stainless steel connectors top and bottom.
7. 
The inlet baffle shall extend at least six (6) inches but no more than twenty percent (20%) of the total liquid depth below the liquid surface and at least one (1) inch above the crown of the inlet sewer.
8. 
The outlet baffle and the baffles between compartments shall extend below the liquid surface a distance equal to forty percent (40%) of the liquid depth, except that the penetration of the indicated baffles or sanitary tees for horizontal cylindrical tanks shall be thirty-five percent (35%) of the total liquid depth. They also shall extend above the liquid surface as required in this code. In no case shall they extend less than six (6) inches above the liquid surface.
9. 
Approved filters shall be provided for outlets for each tank. Approval shall be based on acceptable test data that confirms the filter reduces Total Suspended Solids (TSS) a minimum average of forty percent (40%) over conventional tees or baffles.
10. 
There shall be at least one (1) inch between the underside of the top of the tank and the highest point of the inlet and outlet devices.
11. 
The inlet shall be not less than three (3) inches above the outlet.
12. 
The inlet and outlet shall be located opposite each other along the axis of maximum dimension. The horizontal distance between the nearest points of the inlet and outlet devices shall be at least four (4) feet.
13. 
Sanitary tees shall be at least four (4) inches in diameter. Inlet baffles shall be no less than six (6) inches or no more than twelve (12) inches measured from the end of the inlet pipe to the nearest point on the baffle. Outlet baffles shall be six (6) inches measured from beginning of the outlet pipe to the nearest point on the baffle.
14. 
Access to the septic tank shall be as follows:
a. 
Manholes. Access shall be provided over both the inlet and outlet devices and to each tank compartment by means of either a removable cover or a manhole. Where the top of the tank is located more than eighteen (18) inches below the finished grade, manholes and inspection holes shall extend to approximately six (6) inches above the finished grade. The extension can be made using a riser of approved material and fitted with tight covers of heavy metal or concrete. Proper attention shall be given to the accident hazard involved when manholes are extended close to the ground surface. All manhole openings shall be provided with a substantial, fitted, water-tight cover of concrete, cast iron or other approved materials. The manhole covers shall have either an effective locking device or otherwise be adequately sealed in a manner to prevent accidental access.
b. 
A six (6) inch inspection port shall be provided over the inlet and outlet baffles of each tank and terminate at or above grade. An inspection port shall not be used as a pump out access. A manhole cover may also serve in place of inspection ports.
15. 
Compartmentation of single tanks shall be in accordance with the following:
a. 
Septic tanks, fabricated as a single unit, shall be divided into two (2) or more compartments.
b. 
When a septic tank is divided into two (2) compartments, not less than one-half (½) nor more than two-thirds (⅔) of the total volume shall be in the first (1st) compartment.
c. 
When a septic tank is divided into three (3) or more compartments, one-half (½) of the total volume shall be in the first (1st) compartment and the other half equally divided in the other compartments.
d. 
Connections between compartments shall be baffled so as to obtain effective retention of scum and sludge. The submergence of the inlet and outlet baffles of each compartment shall be as specified in Section 705.350 (B)(7) and (8) of this code.
e. 
Adequate venting shall be provided between compartments by baffles or by an opening of at least fifty (50) square inches near the top of the compartment wall; and
f. 
Adequate access to each compartment shall be provided by one (1) or more manholes, with a minimum opening twenty (20) inches square or in diameter and located within six (6) inches of all walls of the tank.
16. 
The use of multiple tanks shall conform to all of the following:
a. 
Where more than one (1) tank is used to obtain the required liquid volume, the tanks shall be connected in series.
b. 
Each tank shall comply with all other provisions of this Section.
c. 
No more than three (3) tanks in series can be used to obtain the required liquid volume.
d. 
The first (1st) tank shall be no smaller than any subsequent tanks in series.
17. 
Septic tanks serving non-residential flows shall be a minimum of one thousand (1,000) gallons liquid capacity and shall be at least as large as the capacities given in Table 607.2(a). No tank shall be designed to retain less than two (2) days, forty-eight (48) hours flow.
Table 607.2(a)
Non-Residential Septic Tank Capacity
FLOW
(gallons per day)
MINIMUM LIQUID CAPACITY
(gallons)
1 — 249
1,000
250 — 374
1,250
375 — 499
1,500
500 — 649
1,800
650 — 749
2,000
750 — 849
2,200
850 — 999
2,500
1,000 — 1,249
3,000
1,250 — 1,499
3,500
1,500 — 1,749
4,000
1,750 — 1,999
4,500
2,000 — 2,249
5,000
2,250 — 2,499
5,500
2,500 — 2,749
6,000
2,750 — 3,000
6,500
18. 
The liquid capacity of a septic tank serving a dwelling shall be based upon the number of bedrooms contemplated in the dwelling served and shall be at least as large as the capacities given in Table 607.2(b).
Table 607.2(b)
Residential Septic Tank Capacity*
[Ord. 12-10-2013 §2, 12-10-2013]
Number of Bedrooms
Minimum Liquid Capacity
(gallons)
1 — 3
1,000
4
1,250
5
1,500
6
1,750
7
2,000
8
2,250
* These figures provide for use of garbage grinders, automatic clothes washers and other household appliances (water usage not to exceed 120 gallons per day per bedroom).
C. 
Location. Location of the sewage tank shall be as follows:
1. 
The sewage tank shall be placed so that it is accessible for the removal of liquids and accumulated solids;
2. 
The sewage tank shall be placed on firm and settled soil capable of bearing the weight of the tank and its contents; and
3. 
The sewage tank shall be set back as specified in Table 602.1.
D. 
Solids Removal. The owner of any septic tank or his/her agent shall regularly inspect and arrange for the removal and sanitary treatment of seepage from the tank whenever the top of the sludge layer is less than twelve (12) inches below the bottom of the outlet baffle, or whenever the bottom of the scum layer is less than three (3) inches above the bottom of the outlet baffle. Tanks shall be pumped whenever the bottom of the scum layer is within three (3) inches of the bottom of the outlet device or the sludge level is within twelve (12) inches of the bottom of the outlet device.
E. 
Tank Replacement. Septic tanks shall no longer be permitted for tank replacement on existing systems unless a soil morphology test is performed detailing the soil application rate is five tenths (0.5) or better, or a NSF Class 1 aerator must be installed. A septic tank can be used preceding a lagoon and as a trash tank preceding a NSF Class 1 aerator. Existing septic tanks must be inspected by a licensed design engineer or licensed installer to verify the tank is sealed and has sufficient structural integrity. Tank replacement will require a permit, drawings or plans that detail the proposed tank location.
[Ord. No. 18-0499, 12-10-2018]
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
An aeration treatment unit (ATU) utilizes the principle of oxidation in the decomposition of sewage by the introduction of air into the sewage. An ATU may be used as the primary treatment unit instead of a septic tank except where special local conditions may limit their use. All ATU systems shall comply with the general requirements for sewage tanks set forth in Section 705.350(B) of this code and with the following:
1. 
Limitations. Special conditions where Aeration Treatment Units (ATUs) cannot be used may include, but not be limited to, intermittent use (interruptions allowing more than five (5) days without continuous flow) will adversely affect the functioning of the plant.
2. 
General. The ATU shall be located where it is readily accessible for inspection and maintenance. Setback distances for ATUs shall be in accordance with Table 602.1.
3. 
Design. All ATUs shall comply with National Standard Foundation NSF International Standard Number 40 or 245. In addition, all ATUs shall comply with the requirements stipulated in Section 705.260, Tanks. The ATU shall have a minimum treatment capacity of one hundred twenty (120) gallons per bedroom per day or five hundred (500) gallons, whichever is greater.
[Ord. No. 13-0459 §2, 12-10-2013]
4. 
Effluent treatment. Effluent from an ATU shall be discharged into a soil absorption system or other final treatment system in accordance with Section 705.420. No reductions in the area of soil absorption systems or other final treatment systems shall be permitted.
5. 
Operation and maintenance. Where ATUs are used, operation and maintenance are required. ATUs shall be inspected at least two (2) times each year, and pumped in accordance with manufacturer's instructions. Operating permit from Jefferson County is required.
a. 
Maintenance. The Code Commission shall be and is hereby authorized to grant certification to the manufacturers of NSF Class 1 aeration treatment units found to be listed with NSF International.
(1) 
Criteria for approval. Constructions-installation permits may be issued for on-site systems incorporating ATUs for single-family dwellings and commercial facilities if the following criteria are met:
(a) 
The Code Commission has listed the ATU, including brand and model or type where applicable, for use in on-site systems.
(b) 
The ATU meets the performance and model selection criteria specified for the proposed use.
(c) 
The owner of the property served by the on-site system incorporating the ATU has a written service contract as required in Section 705.360(5)(a)(14).
(2) 
Listing and delisting.
(a) 
Any person may submit an application for listing an ATU. The application shall include:
(i) 
Documentation that the ATU meets the performance requirements in Section 705.360(5)(a)(3).
(ii) 
Documentation that the ATU has been certified by NSF International as a Class 1 and is still in good standing.
(iii) 
A guide for inspecting the ATU installation.
(iv) 
A plan for training agents on inspection of the ATU and training and certifying system installers on installation of the ATU.
(v) 
A plan for training and certifying CMP on system maintenance for the ATU.
(vi) 
Documentation that the ATU complies with Section 705.360(5)(a)(5 — 7), (9).
(b) 
The Code Official will approve applications to list ATU that the Code Official determines meet the performance requirements in Subsection (5)(a)(3) under normal operating conditions. ATU will be listed by brand and model or type for the treatment standards they achieve.
(c) 
The Code Official may remove ATUs from the list if it is determined the requirements for approval in Subsection (5)(a)(3) are no longer satisfied or if:
(i) 
Ten percent (10%) or more of installed systems under ten (10) years of age fail;
(ii) 
NSF International Certification of the ATU as a Class 1 residential on-site sewage treatment system is not current; or
(iii) 
The manufacturer goes out of business.
(3) 
Performance testing and standards for listing ATUs.
(a) 
Product testing. ATUs shall be tested according to the product standards and testing protocol established by the NSF International Standard Number 40 and 245 Residential Wastewater Treatment System, July 2009 or another NSF International protocol approved by the Code Official. Testing for the fecal coliform and total nitrogen parameter shall include the collection and analysis of influent and effluent grab samples at a minimum frequency of three (3) days per week and the same duration (twenty-six (26) consecutive weeks) and hydraulic loadings (design and stress loading) as the NSF International sample collection requirements for the BOD5, CBOD5, and TSS parameters. The testing shall be performed by NSF International or a testing facility acceptable to NSF International.
(b) 
Product performance. An ATU shall produce effluent quality equal to or better than Treatment Standard I or II specified in this Section:
(i) 
Treatment Stand I means (NSF Standard 40):
i) 
CBOD5 — The thirty (30) day average of CBOD5 concentrations of effluent samples shall not exceed twenty-five (25) mg/l. The seven (7) day average of CBOD5 concentrations of effluent samples shall not exceed forty (40) mg/l.
ii) 
TSS — The thirty (30) day average of TSS concentrations of effluent shall not exceed thirty (30) mg/l. The seven (7) day average of TSS concentrations of effluent shall not exceed forty-five (45) mg/l.
iii) 
pH — The pH of individual effluent samples shall be between six (6.0) and nine (9.0).
(ii) 
Treatment Standard II means (NSF Standard 245):
i) 
CBOD5 — The average CBOD5 of all effluent samples shall not exceed twenty-five (25) mg/l.
ii) 
TSS — The average TSS of all effluent samples shall not exceed thirty (30) mg/l.
iii) 
Total Nitrogen — The average total nitrogen concentration of all effluent samples shall be less than fifty percent (50%) of the average total nitrogen concentrations of all influent samples.
iv) 
pH — The pH individual effluent samples shall be between six (6.0) and nine (9.0).
(4) 
ATU model type and size selection. The model, type, and size of the ATU proposed for a system shall be consistent with manufacturer recommendations and match the daily design wastewater flow anticipated from the dwelling or facility.
(5) 
Access ports. At a minimum, the ATU shall have ground-level access ports sized and located to facilitate installation, removal, sampling, examination, maintenance, and servicing of components or compartments that require routine maintenance, or inspection. Access ports shall facilitate:
(a) 
Visually inspecting and removing mechanical or electrical components;
(b) 
Removing components that require periodic cleaning or replacement;
(c) 
Visual inspecting and collecting samples; and
(d) 
Removing (manual/or pumping) accumulated residuals.
(e) 
Access ports shall be protected against unauthorized intrusion. Acceptable protective measures include, but are not limited to, padlocks or covers that can be easily removed only with tools, or a cover having a minimum net weight of 65 pounds.
[Ord. No. 13-0459 §2, 12-10-2013]
(6) 
Malfunction, failure sensing, and signaling equipment.
(a) 
The system shall be designed to prevent the passage of untreated waste into the absorption field if the ATU malfunctions.
(b) 
The ATU shall possess a mechanism or process capable of detecting:
(i) 
Failure of electrical and mechanical components that are critical to the treatment process; and
(ii) 
High liquid level conditions above the normal operating specifications.
(c) 
The ATU shall possess a mechanism or process capable of notifying the system owner of failures. The mechanism shall have circuits separated from pump circuits and deliver a visible and audible signal.
(i) 
The visual alarm signal shall be conspicuous at a distance of fifty (50) feet from the system and its appurtenances.
(ii) 
The audible alarm signal strength shall be between seventy (70) and ninety (90) dbA at five (5) feet and sixty (60) dbA at a distance of eighteen (18) feet from the system and its appurtenances.
(iii) 
The visual and auditory signals shall continue to function in the event of electrical, mechanical equipment, or hydraulic malfunction of the system. The audible signal may be disabled for service while cause for the alarm is identified and alleviated.
(d) 
A clearly visible label or plate with instructions for obtaining service shall be permanently located near the failure signal.
(7) 
Data plate. The ATU shall have permanent and legible data plates as follows:
(a) 
Located on the front of the electrical control, if the ATU has an electrical control box or panel; and the tank, aeration equipment assembly, or riser at a location accessed during maintenance cycles and inspections.
(b) 
Each data plate shall include:
(i) 
Manufacturer's name and address;
(ii) 
Model number;
(iii) 
Serial number (required on one (1) data plate only);
(iv) 
The performance expectation as determined by performance testing and evaluation.
(8) 
Siting and absorption area construction criteria.
[Ord. No. 13-0459 §2, 12-10-2013]
(a) 
ATU approved for Treatment Standard 40 may be sited and sized as follows:
(i) 
In areas with temporary water table, in accordance with specification for sand filters in areas with temporary ground water.
(ii) 
In areas with permanent ground water, where four (4) feet of separation can be maintained between the bottom of the trench and ground water and the other criteria in this code can be met.
(iii) 
On sites meeting criteria for standard on-site systems or for pressurized systems in this code.
(b) 
ATU used in conjunction with approved disinfection and approved nitrogen reduction processes and approved for Treatment Standard 245 may be sited and sized as follows:
(i) 
On sites meeting the criteria for Treatment Standard 40 in Subsection (5)(a)(8)(a) of this Section.
(ii) 
On sites where minimum setback to permanent water table, lakes, streams, or wells cannot be met due to lot size or configuration.
(9) 
Limited warranty. The ATU manufacturer shall:
(a) 
Warrant all components of the ATU to be free from defects in material and workmanship for a minimum of two (2) years from the date of installation; and
(b) 
Fulfill the terms of the warranty by repairing or exchanging any components that the manufacturer determines may be defective.
(10) 
Installation. ATUs shall be installed in accordance with the manufacturer's instructions and this code. The installer shall be certified by the ATU manufacturer to install the system and provide written certification to the Code Official that the ATU components were installed in accordance with the manufacturer's instructions and this code.
(11) 
(Reserved)
(12) 
Operation and maintenance standards. The owner of an ATU system must ensure the ATU and all components of the on-site system are properly operated and timely maintained or decommissioned and the effluent standards in Subsection (5)(a)(3) of this Section are met.
(13) 
Owner's manual. The designer of each on-site system using an ATU must provide a comprehensive owner's manual prepared by the manufacturer or designer to the system owner, manufacturer's representative, installer, and if requested, the Code Official before or at the time of installation. The manual may be a collection of individual system component manuals and shall include information on system specifications, system installation, operating and maintenance, and troubleshooting and repair.
(14) 
Service contracts.
(a) 
The owner of an ATU system must maintain a contract with a maintenance provider certified by the manufacturer to serve and maintain the on-site system. A service contract must be entered before the system is installed and must be maintained until the system is decommissioned. A single service contract and maintenance provider for both the ATU and other components is preferable to multiple contracts for maintenance providers.
(b) 
The service contract must provide the following:
(i) 
Provide for a minimum of four (4) inspections and service visits by a maintenance provider scheduled every one hundred eighty (180) days over the two (2) year period to inspect, adjust, and service the ATU;
(ii) 
Provide for an ATU effluent quality inspection by a maintenance provider consisting of, but not limited to, a visual assessment for color, turbidity, and scum overflow; and olfactory assessment for odors; and any other performance assessment or operational diagnosis, which may include sampling of treated effluent (post-disinfection if disinfection is used) necessary to determine or ensure proper operation of the system;
(iii) 
Include a clause stating that the dealer, authorized representative, or maintenance provider must notify the system owner in writing about any improper system function that cannot be remedied during the time of inspection and include an estimated date of correction;
(iv) 
Include other information and conditions of the agreement such as:
i) 
Owner's name and address,
ii) 
Property address,
iii) 
Permit requirements,
iv) 
Contract information for the owner, dealer, authorized representative, or maintenance provider and agent.
(v) 
Details of service to be provided, including the service required in this Section;
(vi) 
Schedule of maintenance provider duties;
(vii) 
Cost and length of service contract and time period covered;
(viii) 
Details of any warranty; and
(ix) 
Owner's responsibilities under the contract for routine operation of the on-site system.
(15) 
Maintenance providers. Dealers or authorized representative under a contract required in this Section must comply with the following requirements.
(a) 
A maintenance provider must observe and record conditions found and report those observations to the system owner. System owner must report evidence of any system failures to the Code Official and take appropriate action approved by the Code Official to correct the problem. Any repair or alteration must comply with this code.
(b) 
Maintenance providers must maintain accurate records of their service contracts, customers, performance data, and time line for renewing the contracts. These records must be available for inspection upon request by the Code Official.
(c) 
Within thirty (30) days of their termination or expiration, providers must notify the Code Official of service contract that are terminated or not renewed.
(d) 
All maintenance providers must make emergency service available within forty-eight (48) hours of a service request.
(e) 
The maintenance provider must submit six (6) month service reports to the Code Official for each system under contract to be serviced by the maintenance provider.
(f) 
Anyone doing service on ATU must be certified by the manufacturer and listed with NSF International.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
When required as a design feature of an on-site sewage treatment system, effluent pumps, associated equipment and connections shall comply with the following:
1. 
The pump must be rated for effluent service by the manufacturer and meet electrical safety standards of Underwriters Laboratories or equivalent.
2. 
The pump must be submersible and kept submersed at all times when in use and the pump intake be kept a minimum of two (2) inches off the tank bottom.
3. 
The pump manufacturer shall provide a two (2) year limited warranty.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
Each septic tank system shall have an effluent filter approved by the Code Official.
1. 
The person who installs the septic tank system shall install the effluent filter as a part of the septic tank system in accordance with the specifications provided by the manufacturer of the effluent filter. An effluent filter shall:
a. 
Be made of materials that are capable of withstanding the corrosives to which septic tank systems are normally subject.
b. 
Reduce TSS of forty percent (40%) over the conventional tees or baffles.
c. 
Be designed and constructed to allow for routine maintenance.
2. 
The access device shall provide access to each compartment of a septic tank for inspection and maintenance either by means of an opening in the top of the septic tank or by a riser assembly and shall include an appropriate cover. The access device shall:
a. 
Be of sufficient size to facilitate inspection and service.
b. 
Be designed and constructed to equal or exceed the minimum loading specifications applicable to the septic tank.
c. 
Prevent water entry.
d. 
Shall terminate a minimum of four (4) inches above grade.
[Ord. No. 11-0248 §1, 8-9-2011; Ord. No. 13-0459 §2, 12-10-2013]
Electrical circuits to the ATU and PHT shall be provided with manual circuit disconnects within a water-tight, corrosion-resistant, outside enclosure (NEMA 4 X or equivalent) adjacent to the ATU and PHT securely mounted at least twelve (12) inches above the finished grade or inside of access port. Control panels provided by the manufacturer shall be installed in a water-tight, corrosion-resistant enclosure (NEMA 4 X or equivalent) adjacent to the unit or on the side of the system readily visible from the unit and accessible by maintenance personnel. Conductors shall be conveyed to the disconnect enclosure and control panel through water-proof, gas-proof and corrosion-resistant conduits. Splices and wire junctions, if needed, shall be made outside the ATU and PHT in a water-tight, corrosion-resistant enclosure (NEMA 4 X or equivalent) securely mounted adjacent to the unit at least twelve (12) inches above the finished grade. Wire grips, duct seal, or other suitable material shall be used to seal around wire and wire conduit openings inside the ATU and PHT and disconnect enclosure. The ATU and PHT shall have an alarm device or devices to warn the user or operator of a unit malfunction or a high water condition. The alarm shall be audible and visible by system users and securely mounted adjacent to the ATU and PHT, on the side of the system in clear view of the unit, or inside the finished occupied space of the system. If mounted outside, the alarm shall meet NEMA 4 X standards or equivalent. The alarm circuit or circuits shall be supplied ahead of any ATU and PHT electrical control circuit overload and short circuit protective devices.
[Ord. No. 11-0248 §1, 8-9-2011]
The common design of absorption systems is the use of absorption trenches, each separate from the other and each containing a distribution pipe. This type system shall be used whenever practical. Other types of absorption systems may be used as alternatives where the site conditions meet the specific design requirements of the alternative systems. Installation shall not be made while the soil is wet or moist. This is to prevent smearing and destroying the structure of the soil. All absorption systems shall have curtain drains, terraces or use of other flow diversion methods to minimize surface or ground water from loading the absorption field.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
The absorption trench gives additional treatment to the sewage from the treatment tank. Regardless of its appearance of clarity or transparency, the outflow or effluent from a sewage tank is a dangerous source of contamination. The satisfactory operation of the sewage treatment system is largely dependent upon the proper site selection, design and construction of the absorption trench.
1. 
Gravity conventional absorption trenches shall not be constructed in soils having a loading rate slower than three-tenths (0.3) gpd/square foot and in no case shall gravity absorption trenches be constructed in soil with loading rate faster than one and two-tenths (1.2) gpd/square foot that may result in contamination of water bearing formations of surface water.
2. 
The absorption trench shall be located on the property to maximize the vertical separation distance from the bottom of the absorption trench to the seasonal high ground water level, as determined by the presence of mottling, bedrock or other limiting layer. The vertical separation between the bottom of the absorption trench and limiting layer or seasonal high water table shall be no less than two (2) feet for standard systems. Greater vertical separation may be required where water-bearing formations are in danger of contamination.
3. 
Absorption trenches shall not be constructed in unstabilized fill or ground, which has become severely compacted due to construction equipment.
4. 
The loading rates in any absorption trench system shall be in accordance with Table 613.15(a). Absorption trenches in highly permeable soils shall have a minimum vertical separation of four (4) feet between the absorption trench bottom and seasonal high ground water table or bedrock. Cherty clays may have a loading rate of three-tenths (0.3) gpd per square foot to eight-tenths (0.8) gpd per square foot. Cherty clay soils located in areas of severe geological limitations shall have less than fifty percent (50%) rock fragments and a vertical separation distance of four (4) feet or more between the absorption trench bottom and bedrock. Unlined absorption trenches shall not be installed in cherty clays when the field evaluation indicated the presence of large voids. Regardless of the loading rate, absorption trenches installed in areas of severe geological limitations with cherty clays shall be designed for a maximum loading rate of four-tenths (0.40) gallons per square foot or a minimum three hundred seventy-five (375) square feet per bedroom. The design loading rate shall be based on the most hydraulically limiting naturally occurring soil horizon to a depth of two (2) feet below trench bottom.
[Ord. No. 13-0459 §2, 12-10-2013]
Table 613.15(a)
Application Rate by Soil Groups for Conventional Systems
[Ord. No. 13-0459 §2, 12-10-2013]
Soil Group
Soil Texture Classes
(USDA Classification)
Application Rate*
(gpd./sq. ft.)
Type
Texture
Structure/Color
I
Sands (with S or PS structure and clay mineralogy)
Sand, Loamy sand
Any striation/Brown (no gray)
1.2 — 0.8
II
Coarse Loams
(with S or PS structure and clay mineralogy)
Sandy loam, Loam
Granular, fine and medium subangular blocky
0.9 — 0.7
Sandy loam, Loam
Prismatic; coarse, subangular, and angular blocky
0.7 — 0.5
III
Fine Loams
(with S or PS structure and clay mineralogy)
Silt loam, Clay Loam, Sandy clay loam, Silty clay loam
Granular, fine, and medium subangular blocky
0.6 — 0.4
Silt loam, Clay loam, Sandy clay loam, Silty clay loam
Prismatic, coarse subangular and angular blocky
0.4 — 0.3
IV(a)
Clays
(with S or PS structure and clay mineralogy)
Sandy clay, Silty clay, Clay (low to moderate shrink/swell)
Granular, fine, and medium subangular blocky
0.4 — 0.2
Sandy clay, Clay, Silty clay, (low to moderate shrink/swell)
Prismatic; coarse subangular or angular blocky
0.3 — 0.1
*
Gallons of sewage tank effluent per day per square foot of trench bottom (gpd/sq.ft.).
Note:
I.
When loading rate is less than 0.4 gpd per square foot, backfill above infiltration barrier shall be sand, loamy sand or sandy loam, when available. Two (2) to four (4) inches of loamy soil shall be used to cap the sandy backfill. This is to keep rainwater from entering the system.
II.
The design loading rate shall be based on the most hydraulically limiting naturally occurring soil horizon to a depth of two (2) feet below trench bottom.
III.
Soil Groups I and II with loading rate 1.2 to 0.8 gpd per square foot shall be required to have an aeration treatment unit (ATU) NSF STD 40 or STD 245 for effluent discharge into an absorption system.
5. 
Each absorption trench system shall have a minimum of three (3) trenches with no one (1) trench longer than one hundred (100) feet unless approved by the Code Official on a case-by-case basis. The absorption trenches shall be located not less than three (3) times the trench width on centers with a minimum spacing of five (5) feet on centers.
6. 
Absorption trenches shall be at least eighteen (18) inches wide and no more than thirty-six (36) inches wide. Thirty-six (36) inch wide trenches shall not be utilized in soils with loading rates less than four-tenths (0.40) gallons per square foot. The bottom of standard absorption trenches shall be at least eighteen (18) inches and no more than thirty (30) inches below the finished grade except as approved by the Code Official.
7. 
The pipe used between the sewage tank and the absorption system shall be a minimum of four (4) inch inside diameter equivalent to the pipe used for the building sewer as set forth in Section 705.340 of this code. The pipe shall have a minimum fall of not less than one-eighth (⅛) inch per foot. All joints shall be of water-tight construction.
8. 
Gravity-fed absorption field distribution lines shall be at least four (4) inches in diameter. Perforated distribution line shall have holes at least one-half (½) inch and no more than three-fourths (¾) inch in diameter.
a. 
Pipe used for distribution lines shall meet the appropriate ASTM standard or those of an equivalent testing laboratory. Fittings used in the absorption field shall be compatible with the materials used in the distribution lines.
b. 
When four (4) inch or six (6) inch diameter corrugated plastic tubing is used for distribution lines, it shall be certified as complying with applicable ASTM standards. The corrugated tubing shall have either two (2) or three (3) rows of holes, each hole between one-half (½) inch and three-fourths (¾) inch in diameter and spaced longitudinally approximately four (4) inches on centers. Coiled tubing shall not be used.
9. 
The absorption trenches shall be constructed as level as possible, but in no case shall the fall in a single trench bottom exceed one-fourth (1/4) inch in ten (10) feet. The ends of distribution lines shall be capped or plugged, or when they are at equal elevations, they shall be connected.
10. 
Rock used in soil absorption systems shall be clean gravel, and graded or sized between one and one-half (1½) and three (3) inches with no more than ten percent (10%) material to pass through a one-half (½) inch screen. The rock shall be placed a minimum of eighteen (18) inches deep with at least twelve (12) inches below the pipe and two (2) inches over the pipe and distributed uniformly across the trench bottom and over the pipe. Limestone and dolomite shall be prohibited. Before placing soil backfill over the trenches, the gravel shall be covered with one (1) of the following:
a. 
Unfaced, rolled, three and one-half (3½) inch thick fiberglass insulation;
b. 
Synthetic drainage fabric; or
c. 
Other material approved by the Code Official laid as to separate the gravel from the backfill.
11. 
Complex slope patterns and slopes dissected by gullies shall not be considered for installation of absorption trenches. Uniform slopes under fifteen percent (15%) shall be considered suitable slope for installation of absorption trenches. When slopes are less than two percent (2%), provisions shall be made to insure adequate surface drainage. When slopes are greater than four percent (4%), the absorption trenches shall follow the contour of the ground. Uniform slopes between fifteen percent (15%) and thirty percent (30%) shall not be used for installation of absorption trenches unless the soils are three (3) feet or more below the trench bottom. Slopes within this range may require installation of interceptor drains upslope from the soil absorption system to remove all excess water that might be moving laterally through the soil during wet periods. Usable areas larger than minimum are ordinarily required in this slope range. Slopes greater than thirty percent (30%) shall not be utilized for installation of absorption trenches unless the following requirements can be met and approval is obtained from the Code Official:
a. 
The slope can be terraced or otherwise graded or the absorption trenches can be located in naturally occurring soil, so as to maintain a minimum ten (10) foot horizontal distance from the absorption trench and the top edge of the fill embankment; and
b. 
The soil is permeable and no restrictive layers or water tables occur at a depth within two (2) feet of the trench bottom; and
c. 
Surface water runoff is diverted around the absorption trench field so that there will be no scouring or erosion of the soil over the field or to allow surface runoff onto the field; and
d. 
If necessary, ground water flow from heavy rainfall is intercepted and diverted to prevent that water from running into or saturating the soil absorption system; and
e. 
There is sufficient ground area available to install the absorption trench system with these modifications.
f. 
Grading design to be required on sewer site plan.
12. 
Effluent distribution devices, including distribution boxes, flow dividers and flow diversion devices, shall be of sound construction, accessible without excavation, water-tight, not subject to excessive corrosion and of adequate design as approved by the Code Official. Effluent distribution devices shall be separated from the sewage tank by a minimum of two (2) feet of undisturbed or compacted soil and shall be placed level on a solid foundation of soil, gravel or concrete to prevent differential settlement of the device. Distribution boxes provided with flow equalizers are required.
a. 
Each distribution line shall connect individually to the distribution box and shall be water-tight.
b. 
The pipe connecting the distribution box to the distribution line shall be of a water-tight construction laid on undisturbed earth.
c. 
No more than four (4) distribution lines shall be connected to a distribution box receiving gravity flow unless the ground surface elevation of the lowest trench is above the flow line elevation of the distribution box.
13. 
Step-downs or drop boxes may be used where topography prohibits the placement of absorption trenches on level grade. Serial distribution systems shall be limited to a separation of at least three (3) feet between the bottom of the absorption trenches and the limiting condition such as slow permeability or zone of seasonal saturation as evidenced by mottling. Whenever the design sewage flow rate requires more than seven hundred fifty (750) lineal feet of distribution line in a step-down or drop-box type system, the absorption field shall be divided into two (2) or more equal portions. Step-downs shall be constructed of two (2) feet of undisturbed soil, constructed to a height level with the top of the upper distribution line. The inlet to a trench shall be placed either in the center or as far as practical from the outlet (overflow) from the same trench. Drop boxes shall be constructed so that the inlet supply pipe is one (1) inch above the invert of the outlet supply pipe which is connected to the next lower drop box. The top of the trench outlet laterals, which allow effluent to move to the distribution lines, shall be two (2) inches below the invert of the outlet supply line. It is required that drop boxes be designed to close off the trench outlets to provide for periods of resting when the absorption trench becomes saturated.
14. 
Dosing or even distribution shall be provided on all systems when the design sewage flow requires more than five hundred (500) lineal feet of distribution line. When the design sewage flow requires more than one thousand (1,000) lineal feet of distribution line, the absorption field shall be divided into two (2) equal portions and each half dosed alternatively, not more than four (4) times per day. Each side of the system shall be dosed not more than four (4) times per day. The volume of each dose shall be the greater of the daily sewage volume divided by the daily dosing frequency, or an amount equal to approximately three-fourths (¾) of the internal volume of the distribution lines being dosed (approximately one-half (½) gallon per lineal foot of four (4) inch pipe). Whenever dosed distribution box systems are utilized, the separation distance between the absorption trench bottom and limiting condition shall be at least two (2) feet.
15. 
Gravelless subsurface absorption systems may be used as an alternative to conventional four (4) inch pipe placed in gravel filled trenches; however, they cannot be used in areas where conventional systems would not be allowed due to poor permeability, high ground water or insufficient depth to bedrock. Design approval for these systems is required from the Code Official prior to installation and all manufacturing specifications and installation procedures shall be closely adhered to. Gravelless trench systems using fabric wrapped tubing shall not be used, where wastes contain high amounts of grease and oil, such as in restaurants.
a. 
Large diameter pipe. Pipe shall consist of eight (8) inches, ten (10) inches corrugated polyethylene tubing encased in a nylon, polyester, or nylon/polyester blend filter wrap installed in a trench twenty-four (24) inches wide and backfilled with soil classified as Soil Group I or II. The loading rate shall not exceed eight-tenths (0.8) gallons per day per square foot.
(1) 
The eight (8) inch to ten (10) inch corrugated polyethylene tubing used in gravelless systems shall meet the requirements of ASTM F667, Standard Specification for Large Diameter Corrugated Polyethylene Tubing. For purpose of calculation, the eight (8) inch pipe may be considered equal to eighteen (18) inches in width of a standard absorption trench. The ten (10) inch pipe may be considered equal to twenty-five (25) inches in width of a standard absorption trench.
(2) 
Two (2) rows of perforations shall be provided located one hundred twenty degrees (120°) apart along the bottom half of the tubing, each sixty degrees (60°) away from each row of holes. Perforations shall be cleanly cut and uniformly spaced along the length of the tubing and shall be staggered so that there is only one (1) hole in each corrugation. The tubing shall be marked with a visible top location indicator. All gravelless drainfield pipe shall be encased at the point of manufacture with a filter wrap of spun bonded nylon, spun laced nylon, polyester, or nylon/polyester blend nylon filter wrap or other substantially equivalent material approved by the Code Official. Corrugated tubing shall be covered with black polyethylene sleeve, which shall encase the large diameter pipe and wrap until just prior to installation in the trench.
(3) 
Rigid corrugated tubing shall be covered with filter wrap at the factory and each joint shall be immediately encased in a protective wrap that will prevent ultraviolet light penetration which shall continue to encase the large diameter pipe and wrap until just prior to installation in the trench. Filter wrap encasing the tubing shall not be exposed to sunlight (ultraviolet radiation) for extended periods. Rocks and large soil clumps shall be removed from backfill material prior to being used. Clayey soils (Soil Group IV) shall not be used for backfill. The near end of the large diameter pipe shall have an offset adapter (small end opening at top) suitable for receiving the pipe from the treatment unit or distribution device and making a mechanical joint in the trench.
(4) 
The trench for the gravelless system shall be dug with a level bottom. On sloping ground, the trench shall follow the contour of the ground to maintain a level trench bottom and to ensure a minimum backfill of six (6) inches. It is recommended that the minimum trench width for the gravelless system be eighteen (18) inches in friable soils to ensure proper backfill around the bottom half of the pipe. In cohesive soils, the minimum width of excavation shall be twenty-four (24) inches. In clay soils, it is recommended that the trench be backfilled with sandy material, sandy loam, loam, clay loam, silt loam or silty clay loam. The gravelless system may be installed at a trench bottom depth of eighteen (18) inches minimum to thirty (30) inches maximum, but a more shallow trench bottom depth of eighteen (18) to twenty-four (24) inches is recommended. To promote equal effluent and suspended solids distribution, the slope of the drain-pipe shall be from zero (0) to one-half (½) inches per one hundred (100) feet.
b. 
A gravelless chamber. May be installed based on bottom absorption area utilizing a reduction of up to forty percent (40%) for a fifteen (15) inch chamber and twenty-five percent (25%) for a twenty-two (22) inch and thirty-four (34) inch chamber based upon a soil morphology evaluation. However, as described in Table 613(a), the maximum loading rate provided for any particular soil group must not be exceeded. For this purpose, the fifteen (15) inch chamber may be considered equal to twenty-one (21) inches in width of a standard absorption trench. The twenty-two (22) inch chamber may be considered equal to twenty-eight (28) inches in width of a standard absorption trench. The thirty-four (34) inch chamber may be considered equal to forty-two (42) inches in width of a standard absorption trench. Installation of the chamber system shall be in accordance with this code except:
(1) 
The installation shall be made in accordance with the manufacturer's specifications;
(2) 
The side walls of trenches placed in Group IV(a) soils shall be raked to open pores which were damaged or sealed during excavation; and
(3) 
Chambers utilizing maximum sidewall absorption features shall be installed per the manufacturer's recommendations to maximize the use of upper soil horizons.
Table 613.15(b)
Loading Rate for Chamber Systems
Soil Group
Range for Chambers
(gpd/sq.ft.)
I
1.0 — 1.2
II
0.7 — 0.8
III
0.5 — 0.6
IV (a)
0.3 — 0.4
IV (b)
Unsuitable
V
0.4 — 0.6
Note:
1.
Application rate is the effective area per lineal feet of the chamber based on the actual dimensional width of the chamber at the trench or bed bottom.
2.
The loading rate shall be based on the most hydraulically limiting naturally occurring soil horizon within three (3) feet of the ground surface or to a depth of two (2) foot below trench bottom, whichever is greater.
c. 
A gravelless expanded polystyrene (EPS) aggregate system may be installed in lieu of gravel systems at the sizing as shown below. For purpose of calculation, the twelve (12) inch minimum diameter EPS aggregate cylinder, with four (4) inch perforated distribution pipe, may be considered equal to twenty-four (24) inches in width of a standard absorption trench or at two (2) square feet. The twelve (12) inch EPS aggregate shall be installed in an eighteen (18) to twenty-four (24) inch wide trench. Installation of the gravelless EPS aggregate system shall be in accordance with this code except:
(1) 
The installation shall be made in accordance with the manufacturer's specifications and sizing in this part;
(2) 
The side walls of trenches placed in Group IV(a) soils shall be raked to open pores which were damaged or sealed during excavation.
16. 
Dosing/alternating systems are encouraged, especially in slowly permeable soil conditions.
17. 
The Code Official may permit the use of a bed system on sites where the minimum soil permeability is a loading rate of forty-five hundredths (0.45) or faster and essentially meeting the other requirements of this Section, and only on lots which are limited by topography, space or other site planning considerations. In such cases the number of square feet of bottom area needed shall be increased by fifty percent (50%) over what would be required for a trench system. Distribution lines shall be at least eighteen (18) inches from the side of the bed and shall have lines on three (3) foot centers and care must be taken to divert surface water away from the bed. When the design volume of sewage exceeds six hundred (600) gallons per day, adequate space shall be provided to accommodate a trench system for the absorption field. There shall be no less than a two (2) foot separation between the bed bottom and the limiting layer or seasonal high water table.
a. 
Possible modifications to standard absorption systems, which may be utilized to overcome selected soil and site limitations and must be approved by the Code Official, and include the following:
(1) 
Shallow placement of absorption trenches shall be utilized where insufficient depth to seasonally high or perched water table or where insufficient soil thickness prevents the placement of conventional distribution lines in accordance with this Section. Shallow trenches shall be designed and constructed to provide a minimum of two (2) feet of natural soil separation between the trench bottom and the uppermost elevation of the seasonally high or perched water table and rock. Shallow trenches may be constructed by placing the top of the gravel at original ground level and covering the absorption field with loamy soil (sandy loam, loam, clay loam, silt loam or silty clay loam) to a depth of eight (8) to twelve (12) inches at the center. The cover over the absorption field shall extend at least five (5) feet beyond the edge of any trench and have a turf grass cover established immediately after construction. If an area is to be filled and the trenches constructed in the fill with the bottom of the trenches in at least six (6) inches of natural soil, the following procedures must be followed:
(a) 
The fill material shall be of a sandy texture with maximum clay content of twenty percent (20%). The fill material shall not be hauled or worked wet. The area to be filled must be protected from traffic and small brush and trees removed prior to placement;
(b) 
The soil surface must be loosened with a cultivator or garden plow. This work must be done when the soil is dry;
(c) 
The fill is moved onto the site without driving on the loosened soil. The fill material is then tilled into the natural soil to create a gradual transition between the two. The remaining fill is then added in layers until the desired height is obtained with each layer being tilled into the preceding layer; and
(d) 
The site is then shaped to shed water and fill all low spots before the absorption system is installed. After installation of the absorption system, the site must have a turf grass cover established as soon as possible;
(2) 
Alternating dual field absorption systems may be utilized where soils are limited by high clogging potentials, with loading rates of two-tenths (0.2) gpd/square feet or in high shrink/swell potential soils. Alternating dual field absorption systems shall be designed with two (2) complete absorption fields, each sized a minimum of seventy-five percent (75%) of the total area required for a single field and separated by an effluent flow diversion valve. The diversion valve shall be constructed to resist five hundred (500) pounds crushing strength, structurally sound and shall be resistant to corrosion. A valve placed below ground level shall be constructed so that it may be operated from the ground surface; and
(3) 
Sand-lined trenches may be used in areas where the soil has greater than fifty percent (50%) rock fragments and there are severe geological limitations. For a maximum loading rate of four-tenths (0.4) gallons per day per square foot or a minimum of three hundred (300) square feet per bedroom, the sand is not required to meet the requirements for intermittent sand filters. The material shall be natural or manufactured sand and have no more than fifteen percent (15%) clay content. Manufactured sand shall be chat, fines manufactured from igneous rocks or chert gravel or manufactured from crushed glass. Crushed limestone is not acceptable. For higher loading rates, the sand must meet the requirements for an intermittent sand filter.
(a) 
In standard four (4) inch pipe and gravel trenches, the depth of liner material must be twelve (12) inches below the gravel and at least six (6) inches on the sides of the gravel up to the top of the gravel. To place sand on the sides of the trenches, the trench walls must be excavated on a slope instead of vertically. The side slopes shall be two (2) horizontal to one (1) vertical and in no case steeper than one (1) horizontal to one (1) vertical.
(b) 
In gravelless pipe systems, the minimum thickness of liner material is six (6) inches around the pipe.
(c) 
The effluent to sand-lined systems in areas of potential ground water contamination shall be equally distributed as much as practically possible. Serial and drop box systems shall not be used. As a minimum, a distribution box shall be used to evenly distribute the effluent to the trenches.
(d) 
The sand-lined trenches may be used, with the approval of the Code Official, where the percentage of rock fragments is less than seventy percent (70%) for at least four (4) feet below the trench bottom. For sand-lined trenches to function properly, the permeability of the natural material shall be similar to the permeability of the liner material and lined trenches must not be used over fragipans or other restrictive layers which have potential to perch water tables and could cause saturation of the liner material.
[Ord. No. 11-0248 §1, 8-9-2011]
A. 
General. The intent of this Section is to provide minimum standards for the design, location, installation, use and maintenance of alternative sewage treatment systems in areas of limiting soil characteristics, where a standard system cannot be installed or a standard system is not the most suitable treatment. These systems shall be designed and stamped by a registered licensed designer. All absorption systems shall have curtain drains, terraces or use of other flow diversion methods to minimize surface or ground water from loading the absorption field. Alternate systems shall have a Class 1 NSF International aeration treatment unit.
B. 
Low Pressure Pipe (LPP) System. A low pressure, two (2) to four (4) foot pressure head, pipe system may be utilized where soil and site conditions prohibit the installation of a conventional or modified septic tank system due to the presence of shallow soil conditions, seasonally high water table conditions and slow soil permeability. The Code Official may permit the use of a LPP system where there are cherty clay soils, severe geological limitations or both. The separation distance in cherty clay soils, severe geological limitations or both for ground water between the trench bottoms and bedrock shall be at least two (2) feet. The amount of rock fragments shall be less than fifty percent (50%) and in no case more than seventy percent (70%), unless the trenches are lined with sand. If the soils have severely diminished, soil qualities shall be sand lined.
1. 
The LPP shall consist of the following basic components:
a. 
A network of one (1) to two (2) inch diameter perforated PVC, one hundred sixty (160) pounds per square inch pipe or equivalent placed in natural soil no more than eighteen (18) inches in depth, and not less than twenty-four (24) inches in width and spaced not less than five (5) feet on center. Trenches shall include at least five (5) inches of pea gravel below the pipe and two (2) inches above the pipe; and four (4) inches of soil cover. The holes in the perforated pipe shall be spaced from two (2) feet to no more than eight (8) feet. The minimum hole size is five thirty-two seconds (5/32) inch;
b. 
An approved Class 1 aeration unit or other approved pretreatment system and a pumping or dosing tank. The pumping or dosing tank shall be sized at a minimum of one thousand (1,000) gallons or one (1) day’s storage above the pump, whichever is greater;
[Ord. No. 18-0499, 12-10-2018]
c. 
A submersible sewage effluent pump (not a sump pump) with appropriate on/off controls for controlled dosing and a high water alarm or other approved pressure dosing and distribution system; and
d. 
A water-tight supply manifold pipe for conveying effluent from the pump to the low pressure network.
2. 
The soil and site criteria for low-pressure pipe systems shall meet the following minimum requirements:
a. 
LPP absorption fields may be installed on slopes greater than ten percent (10%), with special design procedures to assure proper distribution of effluent over the absorption field.
b. 
There shall be at least twenty-four (24) inches of separation between the naturally occurring soil surface and bedrock, water-impeding formation, seasonally high water table or evidence of chroma 2 mottles. This twenty-four (24) inch depth shall consist of permeable soils with loading rate in accordance with Table 614(a). The loading rate shall be based on the most hydraulically limiting natural occurring soil horizon within three (3) feet of the ground surface or to a depth of one (1) foot below trench bottom, whichever is deeper. The bottom of the proposed trenches must be located a minimum of two (2) feet above rock, water-impeding formation, seasonally high water table or where there is evidence of chroma 2 mottles. In areas where there are severe geological limitations and the soils have a high chert content, the bottom of the proposed trenches shall be at least four (4) feet above bedrock unless an evaluation by a registered geologist determines that the separation distance may be reduced.
3. 
The following application rates shall be used in determining the maximum application rate for low pipe systems:
a. 
In calculating the number of square feet for the absorption field (not square footage of trench bottom), the design sewage flow shall be divided by the application rate from Table 614(a). The lateral lines shall have a minimum spacing of five (5) feet on centers within the areas calculated for the absorption field area; and of total area.
b. 
The systems shall be designed so that the discharge from any one (1) lateral line does not vary more than ten percent (10%) from the other laterals. All laterals shall have an envelope of trench rock surrounding the pipe. The trench rock shall be placed to a minimum depth of four (4) inches below the pipe and two (2) inches above the pipe.
4. 
Design of the LPP shall comply with accepted practices and be specifically approved by the Code Official. The system shall be designed and bear the seal of a registered licensed designer.
Table 614(a)
Application Rates by Soil Group for Low Pressure Pipe (LPP) Systems
Soil Group
Soil Texture Classes
(USDA Classification)
Application Rate
*(gpd./sq. ft.)
Type
Texture
Classes
I**
Sands (with S or PS structure and clay mineralogy)
Sand, Loamy sand
No structure (Brown colors)
0.4
II
Coarse Loams (with S or PS structure and clay mineralogy)
Sandy loam, Loam
Granular; fine and medium subangular blocky
0.35
Sandy loam, Loam
Prismatic; coarse subangular and angular blocky
0.2
III
Fine Loams (with S or PS structure and clay mineralogy)
Silt loam, Clay loam, Sandy clay loam, Silty clay loam
Granular; fine and medium subangular blocky
0.2
Silt loam, Clay loam, Sandy clay loam, Silty clay loam
Prismatic; coarse subangular and angular blocky
0.15
IV(a)
Clays (with S or PS structure and clay mineralogy)
Sandy clay, Silty clay, Clay (low to moderate shrink/swell)
Granular; fine and medium subangular blocky
0.1
Sandy clay, Clay, Silty clay
Prismatic; coarse subangular or angular blocky
0.05
IV(b)
Sandy clay, Clay, Silty clay loam, Clay loam, Silty clay (high shrink/swell potential)
Subangular, Angular blocky, or Prismatic
Not suitable
V
Skeletal (less than 50% coarse fragments), Silt loam, Silty clay loam, Clay, Silty clay
Anything but platy or massive
0.15
*
Gallons of sewage tank effluent per day per square foot of total area.
**
In areas where there are severe geological limitations and the soils consist of greater than thirty-five percent (35%) gravel by volume, the loading rate of two-tenths (0.2) gallons per day per square foot (0.2 gpd/sq.ft.) shall be used.
The design loading rate of the LPP Systems shall be based on the most hydraulically limiting naturally occurring soil horizon within three (3) feet of the ground surface or to a depth of two (2) foot below trench bottom, whichever is greater.
[Ord. No. 13-0459 §2, 12-10-2013]
Table 614(b)
Application Rates by Soil Group for Drip Systems
[Ord. No. 13-0459 §2, 12-10-2013]
Soil Group
Soil Texture Classes
(USDA Classification)
Application Rate
*(gpd./sq. ft.)
Type
Texture
Classes
I**
Sands (with S or PS structure and clay mineralogy)
Sand, Loamy sand
No structure (Brown colors)
0.5 — 0.4
II
Coarse Loams (with S or PS structure and clay mineralogy)
Sandy loam, Loam
Granular; fine and medium subangular blocky
0.4 — 0.35
Sandy loam, Loam
Prismatic; coarse subangular and angular blocky
0.3 — 0.2
III
Fine Loams (with S or PS structure and clay mineralogy)
Silt loam, Clay loam, Sandy clay loam, Silty clay loam
Granular; fine and medium subangular blocky
0.3 — 0.2
Silt loam, Clay loam, Sandy clay loam, Silty clay loam
Prismatic; coarse subangular and angular blocky
0.20 — 0.15
IV(a)
Clays (with S or PS structure and clay mineralogy)
Sandy clay, Silty clay, Clay (low to moderate shrink/swell)
Granular; fine and medium subangular blocky
0.2 — 0.1
Sandy clay, Clay, Silty clay
Prismatic; coarse subangular or angular blocky
0.1 — 0.05
IV(b) 1
Silty clay loam, Sandy clay: 35% to 40% clay (high shrink/swell potential)
Fine, medium, and coarse subangular or angular blocky. Weak, medium or strong grade. Prismatic structure: 0.05
0.1-0.075
IV(b) 2
Sandy clay, Silty clay, Clay: 40% to 60% clay (high shrink/swell potential)
Fine, medium, and coarse angular or subangular blocky. Weak, medium or strong grade. Prismatic structure: 0.05
0.075-0.05
IV(b) 3
Clay: greater than 60% (high shrink/swell potential)
Any size, grade or type of structure.
0.05
V
Skeletal (less than 50% coarse fragments), loam, silty clay loam, clay, silty clay
Anything but platy or massive
0.3 — 0.15
*
Gallons of sewage tank effluent per day per square foot of total area.
**
In areas where there are severe geological limitations and the soils consist of greater than thirty-five percent (35%) gravel by volume, the loading rate of two-tenths (0.2) gallons per day per square foot (0.2 gpd/sq. ft.) shall be used.
***
Drip soil absorption system loading rate for soil classified as being in Group IV(b), the maximum application rate shall be 0.10 gpd/sq. ft.
The design loading rate for drip systems shall be based on the most hydraulically limiting naturally occurring soil horizon within twenty (20) inches of the ground surface or to a depth of one (1) foot below trench bottom, whichever is greater. Class IV(b) soils shall not be considered a hydraulically limiting naturally occurring soil horizon.
C. 
Wastewater Stabilization Pond (Lagoon). A lagoon can provide satisfactory sewage treatment in rural areas where soils are not suited for absorption systems. No more than one (1) single-family residence will be allowed on one (1) lagoon.
1. 
The following minimum separation distances are outlined in Table 602.1.
2. 
Lagoons may be utilized when there are no significant limitations related to ground water from their use and the soils have been demonstrated to be very slowly permeable such as percolation rates slower than one hundred twenty (120) minutes per inch. There shall be either a minimum separation distance between the lagoon bottom and creviced bedrock of three (3) feet or installation of a clay liner with a minimum thickness of one (1) foot or a synthetic liner, either of which must be acceptable to the Code Official. Percolation losses from the lagoon shall not exceed one-eighth (⅛) inch per day to prevent ground water contamination or nuisance conditions. Site modifications may be accomplished to provide these soil requirements. In areas of severe geological limitations, restrictive layers such as fragipans shall be a minimum of twelve (12) inches thick and shall not be breached during construction.
3. 
Slopes greater than fifteen percent (15%) shall be avoided.
4. 
Timber shall be removed for a distance of fifty (50) feet from the water's edge to enhance wind action and prevent shading.
5. 
The Code Official shall require that a minimum one thousand (1,000) gallon septic tank or ATU precede the lagoon. If irrigation of the effluent is required to maintain the wastewater on the property from which it originated, a septic tank or ATU shall precede the lagoon. The use of a septic tank or ATU shall not be used as a basis for reduction of the setback distances as set forth in Table 602.1.
6. 
The lagoon shall be designed on the basis of five hundred (500) square feet of water surface area per bedroom at the three (3) foot operating level. The minimum water surface area at the three (3) foot level shall be nine hundred (900) square feet.
7. 
A single cell is generally acceptable for single residence lagoon systems. If multiple cells are used for further polishing or storing of the effluent, the secondary cell shall be at least one-half (½) the size of the primary cell.
8. 
The minimum embankment top width shall be least four (4) foot. The embankment slopes shall not be steeper than three to one (3:1) on the inner and outer slopes. Inner embankment slopes shall not be flatter than four to one (4:1). Outer embankment slopes shall be sufficient to prevent the entrance of surface water into the lagoon. Freeboard shall be at least twenty-four (24) inches.
9. 
To minimize erosion and facilitate weed control, embankment shall be seeded with a locally hardy grass from the outside toe to one (1) foot above the water line. Alfalfa or similar long-rooted crops, which might interfere with the structure of the embankment, shall not be used.
10. 
The influent line shall be of a sound, durable material of water-tight construction of SDR 35 or greater. The line shall have a minimum diameter of four (4) inches and be laid on a firm foundation at a minimum grade of one-eighth (⅛) inch per foot from the point of entry into the lagoon. A cleanout or manhole shall be provided in the influent line near the lagoon embankment. From this point the line shall either be laid to the inner toe of the embankment and then on the bottom of the lagoon to the terminus point or the line shall be supported and secured every five (5) feet. A concrete splash pad three (3) feet square shall be placed under the terminus of the pipe.
The elevation of the cleanout or manhole bottom shall be a minimum of six (6) inches above the high water level in the lagoon.
11. 
The lagoon shall be shaped so there are no narrow or elongated portions. Rectangular cells shall have a length not exceeding three (3) times the width. No islands, peninsulas or coves shall be permitted. Embankments shall be rounded at corners to minimize accumulation of floating materials.
12. 
The floor of the lagoon shall be stripped of vegetation and leveled to the proper elevation. Organic material removed from the lagoon area shall not be used in embankment construction. The lagoon shall be sealed to prevent excessive exfiltration. Seals consisting of soils must be adequately compacted by the construction equipment.
13. 
Embankments shall be constructed of impervious materials and compacted sufficiently to form a stable structure with very little settlement.
14. 
The lagoon area shall be enclosed with a fence conforming to the following conditions:
a. 
The fence is at least five (5) feet in height;
b. 
Fence post shall be galvanized and/or painted steel. The fence shall be chain link or welded type material with no smaller than fourteen (14) gauge wire. The holes in the wire shall not be larger than two (2) horizontal by four (4) vertical. Metal post and metal top rail shall be used;
c. 
Fence posts shall be driven, tamped or set in concrete. Line posts shall be at least eighteen (18) inches deep and shall be spaced no more than ten (10) feet apart. Corner posts shall be at least twenty-four (24) inches deep and shall be properly braced;
d. 
The fence shall be of sound construction with no gaps or openings along the bottom;
e. 
The fence shall be no closer than the center of the berm to the waters edge at the three (3) feet deep operating level. Fence setbacks shall not exceed thirty (30) feet from the water's edge;
f. 
A properly hinged four (4) foot high gate or comparable materials to be installed and provided with an effective latching device. The gate shall be minimum forty-eight (48) inches in width to accommodate maintenance and mowing equipment; and
g. 
The fence shall be completed prior to occupancy of the dwelling.
h. 
The lagoon must be posted "KEEP OUT" on four (4) sides each opposite of another.
15. 
There shall be no permanent connection of any roof drain, footing drain or any source of rainwater to the lagoon.
16. 
Odor problems caused by spring turnover of water, temporary overloading, ice cover, atmospheric conditions or anaerobic conditions may be controlled by broadcasting sodium or ammonium nitrate over the surface of the pond. In general, the amount of sodium or ammonium nitrate shall not exceed two (2) pounds per day until the odor dissipates.
17. 
Lagoons shall be designed with a four-inch diameter outfall pipe drawing effluent from eight (8) inches below the operating surface. All outfall discharge shall be kept on the subject property.
[Ord. No. 18-0499, 12-10-2018]
D. 
Elevated Sand Mounds. Elevated sand mounds may be considered whenever site conditions preclude the use of absorption trenches. The construction of a mound shall be initiated only after a site evaluation has been made and landscaping, dwelling placement, effect on surface drainage and general topography has been considered.
1. 
Elevated sand mounds shall not be utilized on soils where the high ground water level as evidenced by mottling, bedrock or other strata having a percolation rate slower than one hundred twenty (120) minutes per inch occurs within twenty-four (24) inches of natural grade. In areas where there is a significant potential for ground water contamination, a registered licensed designer shall determine the amount of soil needed. Mounds shall be constructed only upon undisturbed naturally occurring soils.
2. 
Elevated sand mounds are subject to the setback distances required in Table 602.1.
3. 
The fill material from the natural soil plowed surface to the top of the rock-filled bed shall be sand, loamy sand or sandy loam. Loading rates on the sand fill shall not exceed the values in Table 614.5(a).
Table 614.5(a)
Loading Rates for Soil Textures
Suited to Use as Fill in a Mound System
Texture
Loading Rate
(gal./sq. ft./day)
Medium to coarse sand
1.2
Fine sand
1.0
Loamy sand
0.8
Sandy loam
0.6
Note: Rock fragments larger than one-sixteenth (1/16) inch shall not exceed fifteen percent (15%) by volume of the material used for sandy fill.
4. 
There shall be a minimum of two (2) feet of fill material and six (6) inches of naturally occurring soils between the bottom of the trench rock and the highest elevation of the limiting conditions as defined in Subsection (D)(1). If the area to be filled has less than six (6) inches of existing soil between bedrock and the fill material, a minimum of six (6) inches of Group I soil shall be filled above the bedrock before placing Group II soil. The area to be filled shall extend twenty (20) feet minimum beyond the edge of the drainfield trenches in all directions.
5. 
Whenever possible, mounds shall be located on flat areas or crests of slopes. Mounds shall not be located on natural slopes of more than six percent (6%) if the percolation rate is slower than sixty (60) minutes per inch to a depth of at least twenty-four (24) inches below the sand layer. Mounds may be located on slopes up to a maximum of twelve percent (12%) if the soil percolation rate is faster than sixty (60) minutes per inch to a depth of twenty-four (24) inches below the sand layer.
6. 
The width of the trench rock in a single bed shall not exceed ten (10) feet.
7. 
The required bottom area of the trenches or bed and the effective basal area of the mound shall be based on one hundred twenty (120) gallons per bedroom per day. The basal area of the mound shall have the minimum area as shown in Table 614.5(b).
[Ord. No. 13-0459 §2, 12-10-2013]
Table 614.5(b)
Loading Rate for Mound Systems
Percolation Rate
(min./in.)
of Basal Area
(gpd/sq. ft.)
1 — 30
1.2
31 — 45
0.75
46 — 60
0.5
61 — 120
0.25
8. 
The area of sand fill shall extend beyond the basal area and the sides shaped to a three to one (3:1) or four to one (4:1) slope. The sand fill shall be covered with six (6) inches of fine textured soil and a final cap of six (6) inches of good topsoil applied. Also the mound shall be seeded with a grass to establish a turf grass cover as soon as possible. No shrubs shall be planted on the top of the mound.
9. 
The land area fifty (50) feet down slope of the elevated sand mound is the effluent dispersal area and the soil in this area shall not be removed or disturbed.
10. 
Dosing shall be required for all elevated sand mounds. The mound shall be dosed not more than two (2) times per day. The size of the dosing pump shall be selected to maintain a minimum pressure of one (1) pound per square inch (1 psi), two and three-tenths (2.3) feet of head, at the end of each distribution line.
a. 
Perforation holes and hole spacing shall be determined to insure equal distribution of the effluent throughout the bed or trenches.
b. 
The perforated pipe laterals shall be connected to a two (2) inch diameter manifold pipe with the ends capped. The laterals shall be spaced no farther than forty (40) inches on center and no farther than twenty (20) inches from the edge of the trench rock. The perforated pipe laterals shall be installed level, with the perforations facing downward. There shall be a minimum of nine (9) inches of trench rock below the laterals and two (2) inches above the laterals. The material used to cover the trench rock shall be untreated building paper, six (6) inches of compacted straw or three and one-half (3.5) inch unbacked fiberglass insulation or a geotextile.
c. 
The manifold pipe shall be connected to the supply pipe from the pump. The manifold shall be sloped toward the supply pipe from the pump. Backflow valves are prohibited in the pump discharge line. The pump discharge line shall be graded to permit gravity flow to the absorption area or back to the dosing tank. Proper air relief and anti-siphon devices shall be installed in the piping to prevent siphoning of effluent from the dosing tank or from the mound.
11. 
Prior to preparing the area selected for the mound, above ground vegetation must be closely cut and removed from the ground surface. Prior to plowing, the dosing pump discharge line shall be installed from the pump chamber to the point of connection with the distribution manifold. The area shall then be plowed to a depth of seven (7) to eight (8) inches parallel to the land contour with the plow throwing the soil upslope to provide a proper interface between the fill and natural soils. In no case shall a rubber-tired tractor be used after the surface preparation is completed. Tree stumps shall be cut flush with the surface and the roots shall not be pulled. The soil shall be plowed only when the moisture content of a fragment eight (8) inches below the surface is below the plastic limit.
12. 
Mound construction shall proceed immediately after surface preparation is completed.
a. 
A minimum of twelve (12) inches of sand fill shall be placed where the trench rock is to be located. A crawler tractor with a blade shall be used to move the sand into place. At least six (6) inches of sand shall be kept beneath equipment to minimize compaction of the plowed layer. The sand layer upon which the trench rock is to be placed shall be level.
b. 
After hand leveling of the trench rock, the distribution system shall be placed and the pipes covered with two (2) inches of rock. After installation of the distribution system, the entire mound is to be covered with topsoil native to the area. The entire mound shall be crowned by providing twelve (12) inches of topsoil on the side slopes with a minimum of eighteen (18) inches over the center of the mound. The entire mound shall then have a turf grass cover established to assure stability of the installation.
c. 
The area surrounding the elevated sand mound shall be graded to provide diversion of surface runoff waters.
E. 
Holding Tank Sewage System.
1. 
A holding tank is an alternative to an on-site sewage treatment system with very special system and limited applications, such as:
a. 
Controlled commercial usage with design flows of less than fifty (50) gallons per day on situations, such as vehicle parks, dump stations, campgrounds, marinas, etc.
b. 
Repair of failing on-site sewage systems.
c. 
Emergency situations where an approved repair or replacement system installation is delayed due to weather induced soil or site conditions.
d. 
Where Missouri DNR has issued a sewer construction permit for a system using a temporary holding facility pending completion of an approved central wastewater and collection treatment system.
2. 
A holding tank shall only be approved by the Code Official if the following options are not feasible:
a. 
On-site system.
b. 
On-site system with off-site drainfield.
c. 
Connection to sewer system.
3. 
Operation and maintenance.
a. 
The Code Official shall require an operating permit renewal every two (2) years.
b. 
Pumping, hauling and disposal must be by a sewage-pumping contractor.
c. 
Disposal of sewage from a holding tank system must be at a site approved by the Missouri Department of Natural Resources.
d. 
Operation records must be maintained by the owner and pumper which include information about pumping frequency, sewage volume, disposal site, proof of acceptance by the disposal site operator, alarms, and system serving and repairs.
e. 
Copies of operation records must be maintained according to the permit requirements and made available to the Code Official upon request.
f. 
Pumping service contracts. Before a permit is issued for installation of a holding tank sewage system, the owner of the system must submit to the Code Official complete documentation in a manner prescribed by the Code Official, and address these items to the satisfaction of the Code Official:
(1) 
Service contract with a sewage system-pumping contractor.
(2) 
Frequency of pumping, by schedule or call-for-service.
(3) 
Financial guarantee for operation, such as a cash deposit or an assignment of funds, in the amount specified by the Code Official. The financial guarantee shall be in an amount at least equal to the cost of three (3) months' service.
[Ord. No. 13-0459 §2, 12-10-2013]
4. 
A holding tank shall be constructed of the same materials and by the same procedures as those specified for water-tight sewage tanks. A manhole of at least twenty (20) inches in diameter shall extend from inside the tank to a point that is at least six (6) inches above finish grade. The manhole lid shall be locked down and water-tight.
5. 
The tank shall be protected against flotation under high water table conditions. This shall be achieved by weight of the tank, earth anchors or shallow bury depths.
6. 
Capacity.
[Ord. No. 13-0459 §2, 12-10-2013]
a. 
For a residence, the tank size shall be one thousand (1,000) gallons or six hundred (600) gallons times the number of bedrooms, whichever is greater.
b. 
For permanent structures, other than residences, the capacity shall be based on measured flow rates or estimated flow rates. The tank capacity shall be at least seven (7) times the daily flow rate. Reserve storage volume three (3) times the daily flow rate.
7. 
Holding tanks shall be located as follows:
a. 
In an area readily accessible to the pump truck under all weather conditions; and
b. 
As specified for septic tanks in Table 602.1; and
c. 
Where accidental spillage during pumpage will not create a nuisance.
8. 
Holding tanks shall be monitored to minimize the chance of accidental sewage overflows. Techniques such as visual observation, warning lights or bells, or regularly scheduled pumping shall be used. For commercial establishments, a positive warning system shall be installed, which allows twenty-five percent (25%) reserve capacity after actuation.
F. 
Sand Filters. ATUs and sand filters may be used along with soil absorption systems in soils with a loading rate of two-tenths (0.20) gpd/sq.ft. Soil absorption systems may be reduced by up to one-third (⅓) of that required for a conventional soil absorption system.
1. 
The ATU must be in accordance with Section 705.360 of this code. Setback distances as shown in Table 602.1 shall apply except that the minimum distance to the down-slope property line shall be fifty (50) feet.
2. 
The following shall apply to gravity flow sand filter systems:
a. 
All piping in a sand filter shall be four (4) inch polyvinyl chloride (PVC). Perforated pipe shall be used for distribution and collection lines;
b. 
All sand filters shall be dosed so as to provide uniform distribution of wastewater throughout the filter cross-section and allow time for re-aeration of the pore spaces to occur. Dosing shall be accomplished by either pumps or siphons;
c. 
Effluent from filter under-drains shall be collected and disposed of properly and effluent shall not discharge;
d. 
Buried sand filters shall be in conformance with Table 614.7. One (1) collector line shall be provided for every six (6) feet of bed width, with a minimum of two (2) collector lines per bed. The collector lines shall have a minimum grade of one percent (1%); and
(1) 
Distribution lines shall be level and spaced a maximum of three (3) feet apart. Each distribution line shall be vented (downstream end) or connected to a common vent. Vents shall extend at least twelve (12) inches above the ground surface with the outlet screened or capped (perforated).
(2) 
ATU effluent shall be applied to the filter through a distribution box. Buried filters shall be dosed with a pump or siphon. The dosing volume shall be sufficient to fill the pore spaces in the gravel to a depth of four (4) inches. For single bed filters receiving septic tank effluent, the hydraulic loading rate shall not exceed one (1) gallon per day per square foot with a maximum organic loading of one and three-fourths (1.75) pounds of biological oxygen demand (BOD) per day per one thousand (1,000) square feet of surface area. Total surface area shall not be less than two hundred (200) square feet.
e. 
Open sand filters are similar to buried filters with the exception that no soil backfill is used on the top of the sand filter. Open sand filters shall be in conformance with Table 614.7.
(1) 
Distribution of wastewater shall be applied by pipes directly over the sand surface at the center of the bed or at the four (4) corners. Splash plates beneath points of discharge shall be used to prevent erosion of the sand. Curbs around the splash plates or large stones placed around the periphery of the plate will help prevent scouring. All exposed pipes shall slope to drain.
(2) 
Filter walls shall be concrete, masonry, compacted clay, high density polyethylene plastic with a minimum thickness of thirty (30) mil, or other material acceptable to the Code Commission; and extend six (6) inches above the sand and six (6) inches above the adjacent ground level.
(3) 
Dosing shall flood the bed to a depth of two (2) inches with a hydraulic loading of two (2) to five (5) gallons per day per square foot (septic tank effluent). Maximum organic loading is five and thirteen-hundredths (5.13) pounds of BOD per day per one thousand (1,000) square feet of surface area.
(4) 
The filter shall be covered to provide protection against severe weather, prevent growth of weeds and to keep children and animals out of the filter. Such cover may include six (6) inches of clean one (1) to two (2) inch gravel, if so designed by an engineer as part of the system. In such event, a vent for the system would not be required if so determined by the registered licensed designer.
Table 614.7
Design Guidelines for Intermittent Sand Filters
Parameter
Buried Filters
Open Filters
Pretreatment
Class 1
Class 1
Setback Distance
Residences
50 ft.
200 ft.
Water Supplies
100 ft.
100 ft.
Backfill Depths
12-inch minimum
Distribution
Gravel
6" (¾" — 2½")
None
Pipe
4" PVC Perforated
PVC or equivalent
Venting
Downstream end
Dosing Frequency
>2 per day
>2 per day
Hydraulic Loading
1.0 gpd/sq. ft.
2 — 5 gpd/sq. ft.
Barrier Material
3½ fiberglass; untreated building paper (4,060 lb.); synthetic fabric; 8" straw
None
Sand
Effective size
0.3 — 1.22 mm
0.3-1.22 mm
Uniformity coefficient
<3.5
<3.5
Fines (<0.13 mm)
<1% (by wt.)
<1% (by wt.)
Depth
24 — 36"
24 — 36"
Collector Lines
Minimum Number
2/bed; 1 line per 6' width
2/bed; 1 line per 6" width
Slope
1% minimum
1% minimum
Gravel
4" overpipe (¾ — 2½")
4" overpipe (¾ — 2½")
Pea Gravel
3" (⅛ — ⅜")
3" (⅛ — ⅜")
Pipe
4" PVC Perforated
4" PVC Perforated
3. 
The following shall apply to pressure dosed sand filter systems:
a. 
Conventional pressure dosed sand filters use an intermittent filter with two (2) feet or more of medium sand designed to filter and biologically treat sewage tank effluent from a pressure distribution system at an application rate not to exceed one and twenty-five hundredths (1.25) gallons per square foot sand surface area per day, applied at a dose not to exceed one-half (½) gallon per orifice per dose. These sand filters may be buried or open.
b. 
Recirculating pressure dosed sand filters use a recirculating filter with two (2) feet or more of medium filter media designed to filter and biologically treat sewage tank effluent from a pressure distribution system at an application rate not to exceed five (5) gallons per square foot filter surface per day, applied at a dose not to exceed two (2) gallons per orifice per dose. These sand filters shall be uncovered and open to the surface.
c. 
Minimum filter area for these filters shall be as follows:
(1) 
Conventional pressure dosed sand filters for single-family residences shall be a minimum of three hundred sixty (360) square feet in surface area with a design sewage flow not to exceed six hundred (600) gallons. If sand filter design flows exceed an average of four hundred fifty (450) gallons per day, the minimum sand surface will be based on one and twenty-five hundredths (1.25) gallons per day per square foot; and
(2) 
Pressure dosed sand filters for commercial facilities shall be sized on the basis of projected daily sewage flow. If the waste strength is proposed to be greater than residential strength waste, pretreatment shall be required which will reduce the biological oxygen demand to levels not to exceed three hundred (300) BOD, TSS to levels not to exceed one hundred fifty (150), and oil and grease to levels not to exceed twenty-five (25). The minimum sand surface will be based on two (2) to five (5) gallons per day per square foot.
d. 
Design criteria shall include the following:
(1) 
Sewage tanks shall be in accordance with Section 705.260. Setback distances as shown in Table 602.1 shall apply. Tanks shall be water-tight and tested in the field. The test shall be performed by filling the tank two (2) inches above the riser inlet. At the end of the first twenty-four (24) hour period, the tank water level shall be refilled. After another twenty-four (24) hour period, no more than one (1) inch of water shall have dropped from the original reading. Risers shall have a water-proof epoxy seal between the tank and riser;
(2) 
Pumping systems for a pressure dosed sand filter system shall provide pumping apparatus that is capable of filtering gross solids larger than one-eighth (⅛) inch and draw from the clear zone near the outlet side of the sewage tank. This zone is described as the layer of effluent between the sludge and scum layers of the sewage tank. Pumps shall be able to deliver adequate head pressure to control orifice plugging. Pumps shall be made of a corrosive-resistant material such as Type 316 stainless steel, suitable plastic, or 85-5-5-5 bronze. Screens shall have at least ten (10) square feet of surface area, with one-eighth (⅛) inch openings;
(3) 
Operation controls shall be on a timer dose that distributes the average daily flow over an eighteen (18) hour period. Recirculating filters will be set to recirculate five (5) times the average daily flow over a twenty-four (24) hour period. Systems shall be designed with a high water alarm and light signal. Control panels shall be located on an exterior location. Control operations shall be located in an area available for maintenance;
(4) 
Intermittent filter media shall be a mixture of sand or durable inert particles with one hundred percent (100%) passing the three-eighths (⅜) inch sieve; ninety percent (90%) to one hundred percent (100%) passing the Number 4 sieve; sixty-two percent (62%) to one hundred percent (100%) passing the Number 10 sieve; forty-five percent (45%) to eighty-two percent (82%) passing the Number 16 sieve; twenty-five percent (25%) to fifty-five percent (55%) passing the Number 30 sieve; ten percent (10%) or less passing the Number 60 sieve; four percent (4%) or less passing the Number 100 sieve; or sand meeting the ASTM-C 33 concrete sand specification minus four percent (4%) or less passing the Number 100 sieve. All drainage rock shall be river washed, hardened and weathered rock. The treatment media will be two (2) inches deep and of a coarse media with an effective size of one and one-half (1½) to three (3) millimeters and a uniformity coefficient of less than two (2). Limestone or dolomite is not acceptable for drainage rock;
(5) 
Recirculating filter media shall be a mixture of sand or durable inert particles with one hundred percent (100%) passing the three-eighths (⅜) inch sieve; seventy-nine percent (79%) to one hundred percent (100%) passing the Number 4 sieve; eight percent (8%) to ninety-two percent (92%) passing the Number 8 sieve; zero percent (0%) to fifteen percent (15%) passing the Number 30 sieve; zero percent (0%) to one percent (1%) passing the Number 50 sieve. All drainage rock shall be river washed, hardened and weathered rock. The treatment media will be two (2) inches deep and of a coarse media with an effective size of one and one-half (1.5) to three (3) millimeters and a uniformity coefficient of less than two (2). Limestone or dolomite is not acceptable for drainage rock; and
(6) 
Container designs may be concrete containers consisting of water-tight walls and floors to prevent ground water from infiltrating or effluent from exfiltrating from the filter. All penetrations through the walls shall be water-tight. Containers may also consist of a thirty (30) mil polyvinyl chloride liner covering the sand filter bottom and side wall areas. Polyvinyl chloride liners should be supplied with repair kits and boots for passage through the liner wall. The bottom area of the liner shall be bedded in two (2) inches of leveling sand. The liner shall be constructed to form a water-proof membrane between the trench bottom and trench walls. The polyvinyl liner shall incorporate all seams to be a chemically or heat bonded water-proof seam.
e. 
The filter design criteria shall include the following:
(1) 
The interior base of the filter container shall be level or constructed at a grade of one percent (1%) or less to the under-drain pipe elevation;
(2) 
The under-drain piping shall consist of a pipe with one-fourth (¼) inch grooves cut every four (4) inches along the pipe length to a depth of one-half (½) of the pipe diameter. The bottom of the filter container shall be covered with a minimum of six (6) inches of drain media. The under-drain pipe shall be enveloped in an amount and depth of drainage rock to prevent migration of the under-drain media into the pipe perforations;
(3) 
A minimum of twenty-four (24) inches of approved filter media shall be installed over the under-drain media. The media shall be damp at the time of installation to insure compaction of the media. The top surface of the media shall be level;
(4) 
There shall be a minimum of three (3) inches of clean drain media below the distribution laterals and sufficient media above the laterals equal to or covering the orifice shields and/or pipe;
(5) 
Distribution laterals shall be evenly spaced on minimum, thirty (30) inches on centers. Orifices shall be placed such that there is one (1) orifice or more on average per six (6) square feet of sand surface. Orifice holes shall be one-eighth (⅛) inch in diameter. The diameter of the piping manifold and lateral shall be no less than one-half (½) inch. The ends of the distribution laterals shall be constructed with a means to perform flushing of the piping, collectively or individually, through the operation of a flushing valve;
(6) 
The top of the intermittent media in which the pressure distribution system is installed shall be covered with a breathable nylon or polypropylene spun filter fabric rated at eighty-five hundredths (0.85) ounce per square yard to eliminate soil intrusion into the filter media. Recirculating filters shall be open-topped;
(7) 
The top of the intermittent sand filter area shall be backfilled with a soil cover, free of rocks, vegetation, wood waste, etc. The soil cover shall have a textural class of loamy sand. The soil cover shall have a minimum depth of six (6) inches and a maximum depth of twelve (12) inches. Intermittent sand filters designs may delete soil cover and incorporate three (3) to six (6) inches of a quality cypress or cedar mulch over the entire filter area;
(8) 
Where the effluent from a sand filter is to be discharged via a pump, the pump and related apparatus shall be housed in a vandal-resistant vault designed to withstand the stresses placed upon it and not allow the migration of drain media, sand or under-drain media to its interior. The vault shall have a durable, affixed floor. The vault shall provide water-tight access to the finished grade with a diameter equal to that of a gravity discharge sand filter. The depth of the under-drain and the operational level of the pump cycle and alarm shall not allow effluent to come within two (2) inches of the bottom of the sand filter media. The pump off level shall be no lower than the invert of the perforations of the under-drain piping. The internal sand filter pump shall be electrically linked to the sand filter dosing apparatus in such a manner as to prevent effluent from entering the sand filter in event the internal sand filter pump fails; and
(9) 
Other sand filters which vary in design from those described in this code may be approved on experimental basis by the Code Commission, if it can be demonstrated to produce a comparable effluent quality.
G. 
Drip Soil Absorption. Drip soil absorption, also known as trickle irrigation, may be approved by the Code Official in accordance with Section 705.420. The installation shall be made in accordance with the manufacturer's specifications.
[Ord. No. 13-0459 §2, 12-10-2013]
1. 
Drip lines shall be placed two (2) feet apart in a parallel arrangement. Emitters shall be placed in the drip lines every two (2) feet so there will be a two-foot-by-two-foot grid pattern. Other configurations and spacing of the drip line and emitters may be used in accordance with the manufacturer's recommendations.
2. 
The application rate shall not exceed the values as shown in Table 614(b).
3. 
Drip soil absorption systems may be allowed at sites where the soil is classified as being in Group IV(b). A minimum separation distance of twelve (12) inches shall be maintained between the drip lines and emitters and a high ground water table or other limiting condition. The maximum application rate for IV(b) soils shall be one-tenth (1/10) gallons per day per square foot of absorption field.
H. 
Wetlands. Constructed wetlands provide secondary levels of treatment, which means that some form of pretreatment (ATU, lagoon, etc.) must be used prior to the wetland, as wetlands cannot withstand large influxes of suspended solids. The pretreatment used must be capable of removing a large portion of these solids. Effluent from wetlands must be contained on the owner's property with the same setback distances as required for lagoons in Table 602.1.
1. 
Free water surface wetlands are shallow beds or channels with a depth less than twenty-four (24) inches and filled with emergent aquatic plants. This type of wetland shall not be allowed.
2. 
Submerged flow wetlands are similar to free water surface wetlands except that the channels are filled with shallow depths of rock, gravel or sand. The depth of the porous media is usually less than eighteen (18) inches. The porous media supports the root systems of the emergent aquatic vegetation. The water level is to be maintained below the top of the porous media so that there is no open water surface.
3. 
The surface area of wetlands shall be determined by using the following equation:
As
=
[Q(lnCo - lnCe)) / kT x f x d)
Where:
As
=
wetland surface area, sq. ft.
Q
=
daily bow rate to wetland, cu. ft./day
([gallons/day] + 7.5);
Co
=
influent BOD5 concentration, mg/l;
Ce
=
effluent BOD5 concentration, mg/l;
kT
=
temperature dependent rate constant, per day;
d
=
water depth in wetland, ft.; and
f
=
void fraction of rock media, decimal.
4. 
After a surface area has been determined, a cross sectional area shall be calculated against hydraulic loading by using the following equation:
Ah
=
Q/(Kh x S)
Where:
Ah
=
cross sectional area (hydraulic loading), sq. ft.;
Kh
=
hydraulic conductivity of rock media, ft./day*; and
S
=
slope of wetland bottom, decimal**
*
A value of eight hundred (800) feet per day may be used for the hydraulic conductivity for rock of one (1) inch diameter.
**
Values for slope shall range between one-quarter percent (0.25%) to one percent (1%).
5. 
After the hydraulic loading has been determined, an organic loading shall be calculated using the following equation:
Ao
=
OGL/0.05
Where:
Ao
=
cross sectional area (organic loading), sq. ft.; and
OGL
=
organic loading, lbs. BOD5/day
6. 
The larger of the two (2) calculations, the hydraulic loading or the organic loading, shall be used to determine the wetland dimensions.
7. 
The width of the wetland shall be calculated by dividing the larger cross-sectional area by the water depth. The calculated width shall not be less than one-third (⅓) of the length (a length-width ratio of three to one (3:1)). Should it be necessary to construct a wetland with a ratio greater than three to one (3:1), step-loading along the length of the wetland shall be considered.
8. 
The configuration of a wetland for an individual home can be a one (1) cell or two (2) cells in series, depending upon the soil properties at the site. Larger systems may consist of multiple cells in parallel or series in order to provide more management options.
a. 
Single cells may be used where there will be no percolation of water through the bottom of the wetland. Water movement properties of the soil at the wetland construction site must be determined by use of a properly performed soil profile analysis performed by a qualified person meeting the criteria of 19 CSR 20.3.080.
b. 
For soils with loading rates of two-tenths (0.2) gal./sq. ft. or less and where geological limitations are not severe, a two (2) cell wetland may be used. The first (1st) cell shall be lined, allowing no percolation. The second (2nd) cell may be unlined and filled with sand (not rock) to promote some percolation from the bottom of the wetland. The second (2nd) cell shall not be larger than the first (1st) cell.
9. 
Crushed limestone or other rock with sharp edges shall not be used for a porous media as this type of rock will compact with time. Rock with rounded edges, such as creek gravel, shall be used. Rock must be thoroughly washed to remove fines, which may cause plugging. Rock substrate size shall be one (1) inch diameter, while rock to be used around inlet and outlet pipes may be two (2) to four (4) inches in diameter to reduce potential clogging. A three (3) to four (4) inch layer of washed pea gravel may be used on top of the one (1) inch substrate for decorative purposes.
10. 
All piping shall be Standard Dimension Ration (SDR) 35 sewer pipe, Schedule 40 polyvinyl chloride (PVC) drain, waste, and vent (DWV) pipe, or material of equivalent or stronger construction. Piping shall be a four (4) inch diameter.
11. 
Influent shall be distributed and effluent collected by header pipes running the width of the wetland. Perforated sewer pipe can be used for the headers. For unperforated pipe, a one and one-half (1.5) inch hole shall be drilled every twelve (12) inches along the header. Headers shall be placed at the bottom of the wetland on a bed of rock and covered with two (2) to four (4) inch rock. A cleanout shall be placed before the influent header.
a. 
If effluent from the septic tank flows to the wetland by gravity and there are parallel cells in the wetland, a distribution box shall be placed ahead of the wetland so that flow can be controlled to individual cells.
b. 
If effluent is pumped, the pumping rate shall not exceed twenty-five (25) gallons per minute and no more than one-third (⅓) of the daily design flow shall be pumped at one (1) time.
12. 
Water level in a wetland shall be controllable. The range of control shall be from two (2) inches above the surface of the rock to complete draining of the wetland. Maximum water level in the wetland shall be a minimum of twelve (12) inches below the outlet of the septic tank so that water does not back up into the septic tank.
a. 
To conveniently check the water level relative to the gravel surface, a four (4) inch diameter perforated pipe shall be placed in the bottom of the wetland, through the channel embankment, and then elbowed up to the elevation of the top of the channel.
b. 
Water level control shall be obtained by use of swivel standpipes or collapsible tubing.
13. 
Surface water shall be kept out of the wetland. This may be accomplished by diverting runoff away from the wetland or constructing an earthen berm around the wetland. Berms shall be a minimum of six (6) inches above the surface of the porous media.
14. 
Emergent plants shall be selected by the ability of the plants to: root and grow in the wastewater rock environment, treat wastewater to acceptable levels, produce biomass in amounts that can be controlled and aesthetics. Reference may be made to Tables 614.9(a),(b) in selecting desired plants.
Table 614.9(a)
Plant Growth Data After One Growing Season
Plant Species
Wet Weight
(lbs./sq.ft.)
Dry Weight
(lbs./sq.ft.)
Top Dry
Root Dry
Top/Root
Root Depth
(inches)
Softstem Bulrush
(Scirpus validus)
9.74
4.20
3.20
1.00
3.20
7.00
Horsetail
(Equisetum hyemale)
1.90
0.55
0.20
0.25
0.57
11.0
Water Iris
(Iris pseudacorus)
3.28
0.66
0.31
0.35
0.90
8.00
Pickerel Rush
(Pontederia cordata)
6.24
1.30
0.50
0.80
0.63
15.0
Arrowhead (Sagittaria latifolia)
2.25
0.35
0.17
0.18
0.94
10.0
Cattails (Typha latifolia)
7.89
3.00
1.90
1.10
1.73
8.00
Soft Rush (Juncus effusus)
3.00
1.05
0.65
0.40
1.62
18.0
Flowering Rush (Butomus umbellatus)
0.30
0.07
0.01
0.06
0.18
12.0
Table 614.9(b) Characteristics of Emergent Aquatic Plants
Plant Species
Bloom Date
Type of Bloom
Bloom Color
Plant Height
(Inches)
Growth Pattern
Initial Spacing
(Ft)
Softstem Bulrush
(Scirpus validus)
June — July
Oblong
Spikelets
Gray
40 — 60
Spreading
3
Horsetail
(Equisetum hyemale)
June — July
Oblong Spikelets
Brown
31 — 40
Spreading
3
Water Iris
(Iris pseudacorus)
May — Aug
Flower
White — Lt Blue
10 — 18
Bunches
2 — 3
Pickerel Rush
(Sagittaria latifolia)
July — Sept
Flower
Purple
10 — 18
Bunches
2
Arrowhead (Sagittaria latifolia)
June — July
Hanging Bulbs
Green — White
6 — 10
Spreading
3
Cattails
(Typha latifolia)
May — June
Oblong Spike
Spike Brown
48 — 72
Spreading
3
Soft Rush
(Juncus effusus)
June — July
Flower
Brown
18 — 30
Bunches
2
I. 
Privy. A privy will be allowed only under limited conditions and will not be recognized as a method of sewage treatment for a continuously occupied dwelling, business or other structure. A privy will only be considered for remote sites not served by a piped water source. Plans and construction of a privy will need to meet the approval of the Code Official.
1. 
The privy shall be used to receive only human excreta and toilet paper. The privy shall not be used as a depository for other wastes.
2. 
A pit shall be provided for the privy. The sides of the pit shall be curbed to prevent cave-in. If the pit has an earth bottom, the bottom shall be at least three (3) feet above saturated soil conditions. If this separation distance cannot be achieved in the location of the privy, then the pit shall be liquid-tight.
3. 
The pit shall be pumped out periodically by a licensed waste hauler. At no time shall the pit contents be allowed to accumulate to within one (1) foot of the pit top. The pit contents shall then be transported and disposed into a community sewer system that is in compliance with Chapter 644, RSMo.
4. 
Both the pit and the privy shall be vented. Insect-proof openings shall be placed in the walls, below the seat. A vent shall extend from the underside of the seat board through the roof or up to a horizontal vent open to the sides of the toilet. This vent must be flush with the underside of the seat board and shall not extend down into the pit. All vent openings to the outside shall be properly screened to keep out insects. The top of the privy shall have a screened opening on each side. It is preferable the opening be all the way around the top of the privy in order to allow air to pass through and to carry away any odors which may seep into the upper part of the structure. If a crescent-shaped opening is cut into the door or wall of the privy, it shall also be screened.
5. 
The inside of the privy shall be of durable, smooth, non-absorbent material. If wood is used, the inside of the structure shall be coated with a polyurethane-type coating to minimize the penetration of liquids and odors into the wood.
6. 
A tight-fitting door, preferably with a self-closing feature, such as a door spring, shall be used.
7. 
A privy shall be set back from surface waters, buildings, property lines and water supply wells the same distance as required for soil treatment areas. This information may be found in Table 602.1.
8. 
The privy shall be of sufficient capacity for the facility it serves, but shall have at least fifty (50) cubic feet of capacity.
9. 
Abandoned pits shall have the contents removed, transported and disposed into a community sewer system that is in compliance with Chapter 644, RSMo. This activity shall be performed by a waste hauler. The pit shall then be filled with clean earth and slightly mounded to allow for settling.
J. 
Other Systems. Where unusual conditions exist, special systems of treatment, other than those specifically mentioned in this code, may be employed provided:
1. 
Reasonable assurance of performance of the system is presented to the Code Commission;
2. 
The engineering design of the system is first approved by the Code Commission;
3. 
Adequate substantiating data indicate that the effluent will not contaminate any drinking water supply, ground water used for drinking water or any surface water;
4. 
Treatment and treatment of the wastes will not deteriorate the public health and general welfare;
5. 
These systems comply with all applicable requirements of this code.