A. 
The National Electrical Code 2014 Edition (NEC) shall apply to all electrical installations as though fully written and set forth herein, except as specifically noted otherwise in this Building Ordinance. The ICC Electrical Code shall no longer apply within the Village of Homer Glen.
[Amended 12-13-2017 by Ord. No. 17-068]
B. 
Registration. All electrical contractors engaged in the performance of electrical work shall be registered by the Village. The contractor shall file with the Building Department a copy of the valid registration.[1]
[1]
Editor's Note: See Ch. 83, Art. IV, Contractors.
C. 
Permits.
(1) 
Permits are required for all electrical work. Permits for electrical work shall be issued only when a duly licensed and bonded electrical contractor is listed on the permit application. It shall be unlawful for any person to install, alter, or repair any electrical wire or apparatus by authority of the permit issued to and for the use of some other person.
(2) 
Exception. Qualified homeowners may do work on their own place of residence.
[Amended 12-13-2017 by Ord. No. 17-068]
D. 
It shall be unlawful for any person to alter, disturb or change any electrical wiring or equipment or to permit any electrical wiring or equipment to be altered, disturbed, or changed unless done in conformity with the regulations in this Building Ordinance.
E. 
Where rework or rewiring of any building or structure is 50% or more, all wiring in the entire structure shall be installed as per the currently adopted Electrical Code.
F. 
Electrical metallic tubing (thin wall) shall not be installed underground or in concrete that is in contact with the earth.
G. 
All electrical services shall be rigid metal conduit, or intermediate metal conduit. The underground portion of services can include Schedule 40 PVC with rigid elbow risers with a properly sized ground per Table 250-122 NEC.
H. 
No more then 10 feet of service entrance conductor shall be allowed unless protected with an exterior means of disconnect.
[Amended 12-13-2017 by Ord. No. 17-068]
I. 
If required by the authority having jurisdiction, a diagram showing service and feeder wire sizes, type of conductors, calculated loads, the area in square feet being supplied, and demand factors shall be supplied. In addition, panel schedules shall show connected loads, total connected loads per phase.
J. 
NEC 210-8 shall be amended to apply to all structures.
[Amended 12-13-2017 by Ord. No. 17-068]
(1) 
NEC 210-8(A)(5), Unfinished basements. Add to this section the following subsection:
Ground fault circuit interrupter protection will not be required for ejector pumps, sump pumps and furnaces.
(2) 
NEC 210-8(A)(6), Kitchens. Add to this section the following subsection:
Ground fault circuit interrupter protection will not be required for refrigerators. Refrigerators must be on a separate circuit.
(3) 
NEC 210-12(A), Dwelling Units. Delete the following subsection and add the following:
Arc-Fault Circuit-Interrupter Protection (A) Dwelling Units. All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets of devices installed in dwelling unit bedrooms.
K. 
NEC 210-52(B), Exception No. 2, shall read as follows: "The receptacle outlet for refrigeration equipment shall be supplied from an individual branch circuit rated 15 amperes or greater."
L. 
New Item #3 shall be amended to NEC 210-8(B) as follows: "All Outdoors."
[Amended 12-13-2017 by Ord. No. 17-068]
M. 
Sizing of electrical services for dwellings. (All measurements shall be taken from the outside of the walls of the dwelling unit.)
(1) 
Dwelling units 2,500 square feet to 3,500 square feet shall have a minimum size electrical service of 200 amperes or greater.
(2) 
Dwelling units over 3,500 square feet shall have electrical services rated at least 350 amperes or greater.
(3) 
Exception. Load calculations may be presented to the Building Department for review. The Village determines the proper size of electrical service based on the load calculation submitted. At no time shall the total calculated load exceed 80% of the service size.
N. 
Storage spaces of five square feet or more shall be illuminated.
O. 
All fixtures shall have at least one lamp installed, and all receptacles intended to be used for switched lighting shall be marked for the final inspection.
P. 
All garages attached or unattached with power are required to be on their own twenty-ampere circuit. (The twenty-ampere circuit is a minimum requirement; more circuits may be added or required as needed.) Outlets are required for each vehicle bay of the garage.
[Amended 12-13-2017 by Ord. No. 17-068]
Q. 
All one-half horsepower or larger motors and all appliances rated at 1127 VA or greater shall be on their own dedicated circuit.
R. 
Every panel box must have each circuit labeled. All electrical panels must be located a minimum of three feet away from the sump or ejector pit.
S. 
To NEC 210-5 add a new subsection as follows:
All 3 phase 120/240 volt services shall have phases marked (A) Black (B) Red and (C) Blue
Add new Subsection (D) as follows: "All 3 phase 277/480 volt services shall have phases marked (A) Brown, (B) Orange (C) Yellow, with the neutral being of a gray color. Junction boxes shall be marked 277/480 volts with a permanent marker or approved sticker-type products."
T. 
In commercial and industrial installations, all switches for fire alarms and burglar alarms shall be equipped with mechanical lockouts to prevent an accidental turnoff of the circuits.
U. 
In NEC 800.44, Overhead Conductor Clearances, for swimming pools and hot tubs shall be per NEC 680.0.
[Amended 12-13-2017 by Ord. No. 17-068]
V. 
All commercial/industrial parking facilities having moderate to heavy traffic shall require galvanized steel conduit (IMC) under the paved areas for all power and lighting installations.
W. 
NEC 250-50(a)(1) shall read: "Continuity. Continuity of the grounding path or bonding connection to interior piping shall not rely on water meters, water softeners, water heaters, water filtering devices or other similar equipment."
X. 
NEC Articles 320, 322, 324, 326, 328, 330, 332, 334, 336, 338, 340, 353, 360, 362, 386, 394, 396 and 398 shall be deleted in their entirety, or as approved by the Chief Building Official.
[Amended 12-13-2017 by Ord. No. 17-068]