[Adopted at time of adoption of Code (see Ch. 1, General Provisions, Art. II)]
A. 
Chapter ATCP 94, Wis. Adm. Code, is adopted by reference and made a part of this article with the same force and effect as though set out in full. Failure to comply therewith shall constitute a violation of this article, punishable according to the penalties provided herein. A copy of such code shall be on file in the office of the Fire Chief or his designee.
B. 
The authorized agent for approval, inspection and plan review under this article shall be the State Department of Agriculture, Trade and Consumer Protection.
A. 
Chapter SPS 340, Wis. Adm. Code, titled "Gas Systems," is adopted by reference to the extent that it is not in conflict with this article and is made a part hereof as though set out in full. A copy of Ch. SPS 340 shall be kept on file in the offices of the Village Clerk-Treasurer and the Fire Chief or his designee. Whenever a conflict exists between the provisions of this article and those of Ch. SPS 340, the provisions of this article shall govern.
B. 
No person shall store liquefied petroleum gas in underground containers unless the storage facility is approved by the Fire Chief or his designee on the basis of safety standards promulgated by the State Department of Safety and Professional Services.
C. 
Cylinders, except those in actual use or attached ready to use on industrial tractors and lift trucks, shall be stored according to regulations provided by the Fire Chief for the exterior storage of containers, adequate housing, painting, ventilation and protection against loss or tampering.
D. 
Liquefied petroleum gas-equipped industrial tractors and lift trucks shall be stored away from combustible materials and in locations where they are not subject to excessive rise in temperature, physical damage or tampering by unauthorized persons.
E. 
Cylinder changing shall be made outside of buildings or in open door areas if such areas are approved by the Fire Chief or his designee.
F. 
No person shall store additional containers inside a building for uses permitted under Ch. SPS 340, Wis. Adm. Code, nor shall additional containers for use on industrial tractors or mobile lift trucks be so stored.
G. 
No vehicle equipped with a liquefied petroleum gas mobile fuel tank shall be stored, parked, or maintained in any building used for institutional occupancy or public assemblies.
H. 
Transport trucks for liquefied petroleum gas shall not be stored closer than 50 feet to any building, trailer camp, property line or public sidewalk. This restriction shall not apply to storage within approved buildings or on approved sites.
I. 
Storage in any building of passenger automobiles equipped with liquefied petroleum gas fuel tanks shall be limited to two automobiles, except in fire-resistive buildings approved for such storage.
Any person, firm, or corporation who or which shall violate and any person, firm, or corporation who or which shall allow, permit, or authorize a violation of any provision of this article or any rule, regulation or order made hereunder shall be subject to a penalty as provided in § 1-3 of this Code.