Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Carrollton, MO
Carroll County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Ord. No. 687 §801, 11-1-1960]
For the purpose of this Chapter:
DRY CLEANING
Considered the process of removing dirt, grease, paint or other stains from wearing apparel, textiles, fabrics, rug, etc., by the use of nonaqueous liquid solvents. Dry dyeing shall be considered the process of dyeing clothes or other fabrics or textiles in a solution of dye colors and flammable liquids.
[Ord. No. 687 §802, 11-1-1960]
No person, firm or corporation shall engage in the business of dry cleaning or dry dyeing unless he/she shall first obtain from the Building Inspector a permit setting forth the location, class of plant, flash point of solvent and type of equipment to be used. All provisions of this Chapter must be complied with and no change shall be made in class of solvent nor in equipment unless permission for such change shall first have been obtained from the Building Inspector. No solvent shall be used in any equipment other than class of solvent for which it was designed.
[Ord. No. 687 §803, 11-1-1960]
A. 
For the purpose of this Chapter, dry cleaning and dry dyeing plants shall be divided into the following four (4) classes.
1. 
Class I plants shall be those employing as solvent having a flash point below one hundred degrees Fahrenheit (100° F.) (closed cup test).
2. 
Class II plants shall be those employing a solvent having a flash point above one hundred degrees Fahrenheit (100° F.) (closed cup test) but not meeting requirements as further outlined herein for Class III or Class IV plants.
3. 
Class III plants shall be those employing a solvent complying with the following specifications in dry cleaning systems and drying cabinets or tumblers which have been specifically approved by Underwriters' Laboratories, Inc., or a similarly recognized testing laboratory as being suitable for use with such solvents.
a. 
Flash point (closed cup test) is not lower than one hundred thirty-eight and two-tenths degrees Fahrenheit (138.2° F.).
b. 
Initial boiling point is not lower than three hundred fifty-seven and eight-tenths degrees Fahrenheit (357.8° F.).
c. 
Ignition temperature is not lower than four hundred fifty-three and two-tenths degrees Fahrenheit (453.2° F.).
d. 
The lower limit of explosive range is not less than eight-tenths percent, (0.8%), by volume in air at an initial temperature of three hundred two degrees Fahrenheit (302° F.).
e. 
Solvents shall not heat spontaneously.
4. 
Class IV plants shall be those employing a solvent classified by Underwriters' Laboratories, Inc., or a similarly recognized testing laboratory as nonflammable or as nonflammable at ordinary temperatures and only moderately flammable at higher temperatures.
[Ord. No. 687 §804, 11-1-1960]
A. 
New Class I dry cleaning plants or systems shall be prohibited.
B. 
Existing Class I dry cleaning plants or systems may be continued in use, provided the quantity of cleaning solvent having a flash point below one hundred degrees Fahrenheit (100° F.) (closed cup test) that is stored or handled is not increased.
[Ord. No. 687 §805, 11-1-1960]
A. 
Class II plants shall be located only in one story, flat roof buildings having masonry walls and with concrete or equivalent floor, above grade, and without puts, wells, pockets, or basements. If located within the fire limits, the roof shall be of fire resistant construction; if located outside of the fire limits, the roof may be of combustible construction provided that it is protected on the under side with a ceiling of cement or gypsum plaster on metal lath, or equivalent construction. Dry cleaning or drying buildings shall not be closer than ten (10) feet to a property line except that if the roof is of fire resistive construction, standard masonry walls without openings may be located on the property line.
B. 
Dry cleaning and drying operations shall not be carried on in the same building with other occupancies except that incidental operations such as laundering, pressing, ironing, etc. may be in the same building, or a communicating building, if separated from the dry cleaning room or drying room by partitions or walls having a fire resistance rating of not less than two (2) hours, with any communicating openings protected by standard fire doors approved for the protection of openings in such walls. There shall be at least two (2) means of exit provided from the dry cleaning or drying room.
C. 
A mechanical system of ventilation shall be installed in dry cleaning areas and drying rooms. Such system shall have sufficient capacity to insure complete and continuous change of air once every six (6) minutes, shall be provided with means for remote control, and shall operate automatically when any dry cleaning equipment is in use.
[Ord. No. 687 §806, 11-1-1960]
Class III plants may be located in buildings of any class of construction. If in the same building with other tenants, the dry cleaning or drying section shall be cut off from the remainder of the building vertically and horizontally in an approved manner including approved automatic or self closing fire doors. Vertical cutoffs shall be not less than floor assemblies of double seven-eighths-inch wood flooring protected underneath by cement or gypsum plaster ceiling on metal late; horizontal cutoffs shall be not less than cement or gypsum plaster on metal lath on both sides of wood studs. In no case shall Class III plants be located in a basement nor in a building also used as a place of public assembly.
[Ord. No. 687 §807, 11-1-1960]
Class IV plants shall not be restricted as to type of building[1]
[1]
Editor's Note: So in original.
[Ord. No. 687 §808, 11-1-1960]
Heat for Class II plants shall be by steam or hot water only. For Class III plants, heating shall be by any approved means which does not involve any open flame or ignition source in the dry cleaning area. Steam and hot water pipes and radiators shall be at least one (1) inch from all woodwork and shall be protected by substantial metal screens so as to prevent combustible goods or materials from coming in contact with pipes or radiators.
[Ord. No. 687 §809, 11-1-1960]
Boilers for Class I and Class II plants shall not be located in a dry cleaning or drying building. If located in a building adjoining a dry cleaning or drying room, the boiler room shall be separated from such room by a standard masonry fire wall without openings. Boilers may be located in the same building with Class III plants, but if adjoining dry cleaning areas they shall be cut off by a partition of noncombustible material, without openings, having a fire resistance rating of not less than two (2) hours.
[Ord. No. 687 §810, 11-1-1960]
Aboveground containers comprising purifiers, clarifiers, filter, etc. in Class I and Class II plants shall not exceed three hundred fifty (350) gallons individual capacity. Solvent storage tanks for Class I plants shall be underground, covered with not less than two (2) feet of earth. Solvent storage tanks for Class II plants may be aboveground if individual capacity of tanks does not exceed two hundred seventy-five (275) gallons and the aggregate capacity of storage tanks does not exceed five hundred fifty (550) gallons. Quantities of solvent for Class II and Class III plants in excess of the above shall be in buried tanks.
[Ord. No. 687 §811, 11-1-1960]
Adequate first aid fire appliances suitable for fighting fires in flammable liquids, shall be provided in all Class I, Class II and Class III plants; at least one (1) extinguishing unit shall be provided at each entrance of every room or area where flammable liquids are used. It is desirable that dry cleaning rooms and drying rooms of Class I plants be protected by an automatic sprinkler system or a steam smothering system or a carbon dioxide flooding system; also, that washers and drying tumblers in Class I and Class II plants be protected by a steam smothering system or a carbon dioxide flooding system; also, that drying cabinets in Class III plants be protected by a steam smothering system or a carbon dioxide flooding system.
[Ord. No. 687 §812, 11-1-1960]
The handling of solvents from storage tanks through the various machines and back to the settling and clear solvent tanks shall be through a closed circuit of piping.
[Ord. No. 687 §813, 11-1-1960]
The cylinders and shells of all washing machines, drying tumblers, walls of drying cabinets, outside shall of extractors and all aboveground containers shall be permanently and effectively grounded.
[Ord. No. 687 §814, 11-1-1960]
Electrical equipment in Class I plants shall conform with Article 500 of the National Electrical Code for Class I Division I hazardous locations containing flammable vapors. For Class II plants all electrical equipment within eight (8) feet of the floor in dry cleaning rooms or other sections subject to flammable vapors shall comply with Article 500 of the National Electrical Code for Class I, Division I, hazardous locations.