Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Plattsburgh, NY
Clinton County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
As used in this chapter, the following terms shall have the meanings indicated:
AUTOMATIC
Self-acting, operating by an internal mechanism when actuated by some impersonal influence, as for example, a change in current strength, pressure, temperature or mechanical configuration.
AUTOMATIC SETBACK THERMOSTAT
An automatic control device actuated by temperature, and designed to be responsive to temperature, capable of automatically reducing its setpoint temperature during a predesignated period.
BASEMENT
A space of full-story height below the first floor of a building which is not designed or used primarily for living accommodations.
BASEMENT, UNHEATED
A basement in a dwelling which is not provided with a heat source sufficient to maintain a minimum temperature of 50° F.
Btuh
British thermal units per hour.
BUILDING
A combination of any materials; whether portable or fixed, forming a structure in which energy usage takes place in the normal course, affording shelter for persons or property.
BUILDING INSPECTOR
The Building Inspector of the City of Plattsburgh, New York.
CITY
The City of Plattsburgh, New York.
COEFFICIENT OF HEAT TRANSMISSION
The amount of heat transfer through a material or arrangement of material expressed in Btuh per square foot per degree Fahrenheit of temperature difference. For outside surfaces, the wind velocity is 15 miles per hour. The coefficient of heat transmission is represented by the symbol "U." For wood frame construction, the effect of normal framing members may be neglected in the determination of U values.
COMBINED THERMAL TRANSMITTANCE
An overall coefficient of heat gain expressed in units of Btuh per square foot as calculated using Equation 1.[1]
COMMERCIAL BUILDING
Any building that cannot be classified as a dwelling or mobile home.
CRAWL SPACE
Any unfinished, accessible space below the first floor which is less than full-story height.
CRAWL SPACE, UNHEATED
A crawl space in a one- or two-family dwelling or multifamily dwelling which is not provided with a heat source sufficient to maintain a minimum temperature of 50° F.
DWELLING
A building, other than a mobile home, designed or used as a living unit for one or more families.
ENERGY AUDIT
An engineering analysis which shall consider all possible energy conservation measures and shall identify the estimated costs and energy cost savings likely to be realized from their implementation.
HEAT TRANSMISSION
The amount of heat, measured in Btuh, transferred from one location to another as a result of the temperature difference in the two locations.
HEATED SPACE
Any space within the building which is provided with a heat source sufficient to meet the design dry bulb temperature, but which is neither a heated basement nor heated crawl space as determined by application of the definitions in this section.
HYDRONIC HEATING SYSTEM
A heating system using primarily liquid or gaseous water to distribute heating energy throughout the building.
INSULATION
Any material which has a relatively high resistance to heat flow, and which is used principally to retard the flow of heat.
LIVING UNIT
A dwelling or portion thereof, providing complete living facilities for one family, including permanent provision for living, sleeping, eating, cooking and sanitation.
MOBILE HOME
A structure, transportable in one or more sections, which is eight body feet or more in width and is 32 body feet or more in length and which is built on a permanent chassis and designed to be used as a dwelling, with or without permanent foundation, when connected to the required utilities and includes the plumbing, heating, air-conditioning and electrical systems contained therein.
MUNICIPAL LIGHTING DEPARTMENT
The Municipal Lighting Department of the City of Plattsburgh, New York.
POWER AUTHORITY
The Power Authority of the State of New York.
SETBACK CONTROLLER
An automatic control device capable of reducing the setpoint temperature of several thermostats during a predesignated period.
SYSTEM
A combination of central or terminal equipment or components and/or controls, accessories, interconnecting means and terminal devices by which energy is transformed so as to perform a specific function, such as heating, ventilation, air conditioning, service water heating or illumination.
THERMOSTATIC CONTROL VALVE
An automatic control valve designed to be responsive to room air temperature.
UTILITY
A municipal electric system which receives its full power requirement from the Power Authority.
ZONE
A space or group of spaces within a building with heating and/or cooling requirements sufficiently similar so that comfort conditions can be maintained throughout by a single controlling device.
[1]
Editor's Note: Equation 1 is included as an attachment to this chapter.
Existing dwellings converting to electric heat shall meet the following requirements:
A. 
Minimum insulation standards.
(1) 
The maximum coefficient of heat transmission (U value) through roof and ceiling assemblies adjacent to heated space shall be 0.03.
(2) 
The maximum coefficient of heat transmission of floors over an unheated basement shall be 0.08.
(3) 
The dwelling shall have storm windows or thermal windows with multiple glazing with a maximum U value of 0.69.
(4) 
The entrances to the dwelling shall have storm doors or thermal doors with a maximum U value of 0.40.
(5) 
Vapor barriers, weatherstripping and window caulking shall be used where applicable and practical.
B. 
Minimum heating system standards.
(1) 
For systems using baseboard radiation, one of the following control methods is required.
(a) 
A separate automatic setback thermostat shall be installed in each room, provided that no more than one such thermostat need be installed in any two-room living unit.
(b) 
A central setback controller connected to individual room thermostats shall be installed.
(2) 
For the conversion from a fossil-fuel hydronic heating system to electric heat:
(a) 
Conversion of an existing fossil-fuel boiler to an electric resistance boiler is prohibited.
(b) 
An electric boiler specifically designed for use as a heating boiler with the appropriate American Society of Mechanical Engineers (ASME) approvals shall be installed.
(c) 
One of the following control methods is required:
[1] 
A separate zone with an automatic setback thermostat for each floor, or for each living unit, if there is more than one living unit on a floor.
[2] 
Thermostatic control valves be installed on each radiator and an automatic setback thermostat be installed for the boiler.
(3) 
For the installation of an electric resistance warm-air system or conversion of a fossil-fueled warm-air heating system to electric resistance heat, the following is required:
(a) 
A separate duct heater or furnace is provided for each floor, or for each living unit, if there is more than one living unit on a floor.
(b) 
For each duct heater or furnace, a separate automatic setback thermostat shall be required.
(4) 
For heat pump systems, an automatic setback thermostat shall be required.
(5) 
For all electric heating system conversions, existing fireplaces shall be equipped with a tight-fitting shutoff damper and, where applicable, a source of combustion air-ducted from the outdoors of sufficient quantity to support combustion shall be installed. This source shall be equipped with a damper capable of being fully closed.
C. 
In unusual circumstances, when the application of these provisions appears impracticable or inequitable, the City will refer the matter to the Power Authority for special ruling or for the approval of special conditions which may be mutually agreed upon. The applicant will submit, along with the request for special ruling or for the approval of special conditions, a copy of an energy audit performed on the building by a registered architect or professional engineer.
Existing commercial buildings converting to electric heat shall meet the following:
A. 
Minimum insulation standards.
(1) 
The maximum combined thermal transmittance value for exterior wall systems, Uo as calculated using Equation 1[1] shall be 0.28.
[1]
Editor's Note: Equation 1 is included as an attachment to this chapter.
(2) 
The maximum coefficient of heat transmission (U value) for roof and ceiling assemblies adjacent to heated space shall be 0.06.
(3) 
The maximum coefficient of heat transmission of floors over an unheated basement shall be 0.08.
(4) 
Vapor barriers, weatherstripping and window caulking shall be used where applicable and practical.
B. 
Minimum heating system standards.
(1) 
The system shall have at least one independent zone per floor.
(2) 
One of the following control methods is required:
(a) 
A separate automatic setback thermostat shall be installed for each zone.
(b) 
A central setback controller connected to individual zone thermostats shall be installed.
(3) 
For the conversion from a fossil-fueled hydronic heating system to electric heat:
(a) 
Conversion of an existing fossil-fuel boiler to an electric resistance boiler is prohibited.
(b) 
An electric boiler specifically designed for use as heating boiler with the appropriate American Society of Mechanical Engineers (ASME) approvals shall be installed.
(4) 
Where electric heating is to be used for zone temperature control in heating, ventilating and air-conditioning (HVAC) systems, the following control methods are required:
(a) 
Reheat systems. Systems employing reheat and serving multiple zones (other than those employing variable air volume for temperature control) shall be provided with control that will automatically reset the system's cold air supply to the highest temperature level that will satisfy the zone requiring the coolest air. Single-zone reheat systems shall be controlled to sequence reheat and cooling.
(b) 
Dual duct and multizone systems. These systems shall be provided with controls to reset the cold-deck air supply to the highest temperature that will satisfy the zone requiring the coldest air and to reset the hot-deck air supply to the lowest temperature that will satisfy the zone requiring the warmest air.
C. 
In unusual circumstances, when the application of these standards appears impractical or inequitable, the City will refer the matter to the Power Authority for special ruling or for the approval of special conditions which may be mutually agreed upon. The applicant will submit, along with the request for special ruling or for the approval of special conditions, a copy of an energy audit performed on the building by a registered architect or professional engineer.
A. 
Existing mobile homes converting to electric heat [built prior to the effective date of the Department of Housing and Urban Development (HUD) Mobile Home Construction and Safety Standards] shall meet the following requirements:
(1) 
Glazing: The U value shall equal 0.69.
(2) 
Entrance doors: The U value shall equal 0.40.
B. 
Unusual circumstances. In unusual circumstances, when the application of these standards appears impractical or inequitable, the City will refer the matter to the Power Authority for special ruling or for the approval of special conditions which may be mutually agreed upon. The applicant will submit, along with the request for special ruling or for the approval of special conditions, a copy of an energy audit performed on the building by a registered architect or professional engineer.
The standards specified herein shall be effective on and after September 1, 1981, as a precondition for the expansion of existing electric service for the purpose of providing electric heat to all existing buildings and to existing mobile homes not subject to HUD Mobile Home Construction and Safety Standards.
A. 
The requirements imposed by these standards represent the minimum standards of the Power Authority for existing buildings and mobile homes for which utilities may provide electric service. These standards are not intended to supersede more stringent municipal requirements or standards nor are they intended in any way to contravene the State Energy Conservation Construction Code Act (SECCA).
B. 
The thermal protection for mobile homes is controlled by the Department of Housing and Urban Development Mobile Home Construction and Safety Standards. In accordance with the Housing and Community Development Act of 1974, Title VI (cited as the National Mobile Home Construction and Safety Standards Act of 1974), the federal standards take precedence over all state or local standards.
To ensure compliance with the minimum insulation and heating system standards, the following procedures will be observed:
A. 
Building permit applications for conversion of existing buildings or mobile homes to electric heat shall include the following data:
(1) 
Heat load calculations for the building or mobile home.
(2) 
For commercial buildings, combined thermal heat transmission calculations utilizing Equation 1 (included as an attachment to this chapter).
(3) 
Plans and/or specifications for the building or mobile home showing that the scope of work is in compliance with the requirements of this chapter. Plans and/or specifications must show sufficient detail such as location of thermostats to document full compliance with the requirements of this chapter.
B. 
Inspections of the building or mobile home will be made by an authorized representative of the City at appropriate times during the work period to inspect the work in progress. The owner of the building or mobile home shall notify the Building Inspector when the building or mobile home is ready for inspection. At least 24 hours' advance notice shall be given when requesting inspection.
C. 
Prior to connection of electrical service for heating, the Municipal Lighting Department will require a certificate of compliance stating that the required minimum insulation and heating standards prescribed herein have been met. The certificate of compliance shall be signed by the contractor, owner and Building Inspector. The certificate of compliance for expansion of existing electrical service for the purpose of conversion to electric heat is included at the end of this chapter.