Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Carrollton, MO
Carroll County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Ord. No. 2017-1241 § 1, 8-21-2017[1]]
The Council adopts the 2017 Edition of the National Electrical Code, including Appendix H (Article 80), one (1) copy of which has been on file with the Town Clerk for a period of ninety (90) days prior to the adoption of this Article (as amended), by reference as if fully set forth in its entirety. At least one (1) copy of the 2017 Edition of the National Electrical Code shall remain on file in the office of the Town Clerk and shall be kept available for public use, inspection, and examination.
[1]
Editor's Note: Section 6 of this ordinance provided an effective date of 1-1-2018.
[Ord. No. 2017-1241 § 2, 8-21-2017]
A. 
The code adopted by this Article is hereby amended by substituting the following sections in lieu of those sections with corresponding numbers in the code, or, where there is no corresponding section in the code, the following sections shall be enacted as additions to the code:
1. 
Amendments to Article 80.
a. 
Article 80.2 is amended to read as follows:
Article 80.2 Electric Inspector. An individual authorized to perform electrical inspections for the Town.
b. 
In Article 80.13(13), insert "10."
c. 
In Article 80.15, delete (A) through (F).
d. 
Revise Article 80.15(G) as follows:
(G) Appeal. The applicant for an electrical permit, the holder of an electrical permit, or the owner or agent of a building or structure wherein electrical work is to be installed may appeal a decision of the authority having jurisdiction refusing to grant modification of the provisions of the Electrical Code covering the manner of installation, or materials to be used in the installation, to the Board of Adjustment. Application for appeal shall be filed in accordance with the procedures set out in Section 113 of the Building Code of Carrollton, Missouri.
e. 
In Article 80.19 (F)(3), insert "10."
f. 
Replace Article 80.23 (B)(3) with:
80.23(B)(3) Penalties. Any person who shall violate a provision of this code or shall fail to comply with any of the requirements thereof, shall upon conviction thereof, shall be punished as set forth in the Article adopting this code. Each day that a violation continues shall be deemed a separate offense. The Town is not required to prove criminal intent as a part of its case. It is enough to prove that the defendant either did the act which was prohibited or failed to do an act which the defendant was legally required to do.
g. 
In Article 80.25(C), insert "10."
h. 
Delete Article 80.27 and replace with:
Article 80.27 Licensing.
Article 80.27.1 Certificate of competency. It shall be unlawful for any person to engage in the installation, alteration or repair of electrical wiring, equipment, apparatus or fixtures for light, heat or power purposes; installation or additions to sound, audio visual or communication equipment in or on any building, structure, or premises within the corporate limits of the Town of Carrollton, Missouri, unless issued a certificate of competency by the Town or by a municipality or county in the State of Missouri.
Exception No. 1. This shall not be construed to cover cases where the connected electrical load is not increased or where no new electrical wiring is required.
Exception No. 2. All electrical permits may be issued to the general contractor on behalf of the master electrical contractor for new one- and two-family dwellings and building alteration or building additions for one- and two-family dwellings. All electrical work must be performed by an electrician licensed by the Town of Carrollton, or as allowed by ordinance.
Exception No. 3. Electricians holding a certificate who are regular employees of the firm or corporation for which the work is to be performed may obtain a permit to do electrical work on the premises of the firm or corporation, provided the work is not associated with work requiring a building permit.
Exception No. 4. A permit may be issued to any person to do work in a single-family dwelling used exclusively for living purposes, including the usual accessory buildings and quarters in connection with such building, provided that the person is a bona fide owner of the dwelling, will occupy the dwelling for a period of not less than one (1) year, will personally purchase all materials and perform all labor authorized by the permit, and that the applicant shall file an affidavit certifying that these conditions will be met before the issuance of the permit.
Work performed under any permit shall be subject to all applicable regulatory provisions of this code.
Article 80.27.2 Type of examination required. The type of examination required will be determined by the codes official and will be selected from the standard examination list as prepared and published by Thomson Prometric, 1260 Energy Lane, St. Paul, MN 55108, or the ICC National Standardized Examinations Program, www.iccsafe.org/contractor (1-877-STD-Exam), or any state issued and approved exam.
Article 80.27.3 Reciprocity. The Town will honor licenses issued from other jurisdictional areas, provided the certification of having satisfactorily completed the Thomson Prometric or ICC examination applicable for the type of license requested.
Article 80.27.4 Insurance requirements. It shall be unlawful for any person holding a certificate to engage in work authorized by such certificate in the corporate limits of the Town without first having filed with the Town a certificate of comprehensive liability insurance with a minimum of one hundred thousand dollars ($100,000.00) per claim bodily injury, one hundred thousand dollars ($100,000.00) per claim property damage, with three hundred thousand dollars ($300,000.00) aggregate per occurrence. Such insurance shall insure the proper construction, erection, and maintenance of the electrical work in accordance with the provisions of this code and shall insure the Town from any and all claims or demands for damages by reason of any negligence of the electrical contractor or contractor's agents, or by reason of defects in the construction, or damages resulting from any part thereof. The Town requires a thirty-day cancellation notice from the insurance company.
Article 80.27.5 Work allowed under license. No person who has obtained an electrical contractor's certificate shall allow his/her name to be used by another person for the purpose of obtaining permits, or for doing business or work under such license. Every person licensed shall notify the code official of the address of the licensee's place of business, if any, and the name under which such business is carried on, and shall give immediate notice to the codes official of any change in either.
Article 80.27.6 License fees. Electrical contractors and electricians shall pay annual business license fees to the Town in an amount to be determined under the provisions of the ordinances of the Town.
i. 
In Article 80.29, insert "Town," and add:
Liability. Any officer or employee charged with the enforcement of this code, while acting on behalf of the Town, shall not thereby render such individual liable personally, and is hereby relieved from all personal liability for any damage accruing to persons or property as a result of any act performed in the discharge of official duties. Any suit instituted against any officer or employee because of an act performed by that officer or employee in the lawful discharge of duties and under the provisions of this code shall be defended by the legal representative of the jurisdiction until the final termination of the proceedings. The officer or employee shall not be liable for costs in any action, suit or proceeding that is instituted pursuant to the provisions of this code; and any officer or employee acting within the scope of employment and in good faith and without malice shall be free from liability for acts performed under any of its provisions or by reason of any act or omission in the performance of official duties in connection therewith. Nothing contained herein shall be deemed a waiver of the immunities and protection afforded to the Town or officers and employees pursuant to State and Federal law.
2. 
Amendments to NEC.
a. 
Amend Article 100 as follows:
Equipment - delete word "machinery."
Kitchens - Add "A fixed or portable single microwave does not constitute a permanent cooking facility."
b. 
In Article 110.2, add "The local electrical inspector shall enforce all rules and specifications in this Article as necessary to determine conformity of electrical materials, devices, or appliances with approved methods of construction in order to protect life and property. The label of a nationally recognized electrical testing laboratory, inspection agency, or other organization concerned with product evaluation that maintains periodic inspection during production of equipment or materials, whose label indicates compliance with nationally recognized standards or tests to determine suitable usage in a specified manner, is prima facie evidence that the electrical materials, devices, or appliances are conforming and listed for installation under the provisions of this Article. Only those materials, devices, or appliances which are approved for the purpose intended may be installed to use electricity for light, heat, or power. This includes all materials used to install the materials, devices, or appliances. The manufacturer's name, trademark, or other identification symbol must be placed on or provided with the materials, devices, or appliances, together with rated voltage, current, wattage, or other applicable ratings necessary to determine the purpose and use for which they are intended in accordance with Article 670. It is not the local electrical inspector's responsibility to enforce nationally recognized testing laboratory listings on equipment."
c. 
In Article 110.3, add "The local electrical inspector may grant special approval of materials, devices, or appliances if no standard has been prepared or adopted to which they should conform. Special approval applies only to the particular sample approved and not to the line as manufactured, stored, sold, installed, or attached and may be granted only for those materials, devices, or appliances which, in the opinion of the local electrical inspector, are safe for the use intended. The details of decisions made by the electrical inspector shall be recorded and entered into the files of the electrical inspection division. Any decisions made by the local electrical inspector may be reviewed for consideration by the Board of Adjustment. The Town does not assume any liability for damage or injury to persons or property because of the use of those materials, devices, or appliances."
d. 
Article 110.26 is amended to read as follows:
Article 110.26(D) Electric fences. Electric fencing is not allowed to be installed in the Town except as approved by the municipal utilities and the codes official.
e. 
Article 201.52 is amended to read as follows:
Article 201.52(J) Sump pit. In one- and two-family dwellings, a receptacle outlet shall be installed within three (3) feet of the sump pit on an individual circuit.
f. 
Article 210.8 is amended to read as follows:
Article 210.8 Ground-fault circuit-interrupter protection for personnel. (A) Dwelling units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(A)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel.
Exception No. 1 to (2) Garages and accessory buildings. Receptacles in locations that are not readily accessible, (e.g., on the ceiling of a garage).
Exception No. 2 to (2) Garages and (5) Unfinished basements. A single receptacle or a duplex receptacle for two (2) appliances located within dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug connected in accordance with 400.7(A)(6), (7), or (8).
Add the following Exception to (3) Outdoors. GFCI receptacles located in exterior soffits and used for seasonal decorative lighting are not required to be readily accessible.
Exception to (7) Sinks. Where the receptacles are installed within one and eight tenths (1.8 m) (six (6) feet) of the outside edge of the sink.
(a)
Receptacles installed for specific appliances such as clothes washers, refrigerators, garbage disposals, dishwashers, and microwave ovens shall not be required to be GFCI protected where located within six (6) feet of laundry, utility, kitchen or wet bar sink in a dwelling.
(b)
A duplex receptacle may be used for a single appliance, provided the duplex receptacle is located behind the appliance which, in normal use, is not easily moved and the receptacle is not readily accessible for the use of power tools. This receptacle must be marked "not GFCI protected." Receptacles installed under the exceptions to 210.8(A)(2) and (3) shall not be considered as meeting the requirements of 210.52(G).
g. 
Article 210.52 is amended as follows:
Article 210.52 Dwelling unit receptacle outlets (C) Countertops (5) Receptacle outlet location. Exception to (5): Delete the second sentence to the first paragraph that reads; "Receptacles mounted below a countertop in accordance with this exception shall not be located where the countertop extends more than one hundred fifty (150) mm (six (6) inches) beyond its support base." The rest of the section remains as stated. This deletion is to allow the placement of the receptacle no more than twelve (12) inches below the countertop, and anywhere the countertop extends beyond its support base.
Article 210.52 Dwelling unit receptacle outlets. (E) Outdoor outlets. (3) Balconies, decks, and porches. Add the following: A receptacle is not required at an existing structure.
Article 210.52(G)(1) Receptacles in garages. Delete first sentence, as follows: "In each attached garage, and in each detached garage with electric power, the branch circuit supplying receptacles shall not supply outlets outside the garage." Retain second sentence: "At least one (1) duplex receptacle shall be installed for each car space."
h. 
Article 210.63 is amended as follows:
Article 210.63 Heating, air-conditioning, and refrigeration equipment outlet. Existing exception to be shown as Exception No. 1 and add:
Exception No. 2: Rooftop and exterior equipment on one- and two-family dwellings.
i. 
Article 210.64 is amended as follows:
Article 210.64 Electrical service areas. In other than one- and two-family dwellings, a 120-volt, 15- or 20-amp receptacles shall be required within fifty (50) feet of the electrical service equipment. Add second sentence, as follows: "The receptacle shall be readily accessible and located within sight of the service equipment."
j. 
Article 220.14 is amended as follows:
Article 220.14. Branch circuit load calculations. (J) Dwelling occupancies: Delete "one-family, two-family" and add the following requirements for one- and two-family dwellings:
(1)
In one- and two-family dwellings, a 15-amp-rated general purpose circuit shall be limited to a maximum of eight (8) receptacle outlets or openings, or eight lighting outlets or openings, or any combination of receptacle outlets and lighting outlets totaling not more than eight.
(2)
In one- and two-family dwellings, a 20-amp-rated general purpose circuit shall be limited to a maximum of ten (10) receptacle outlets or openings, or ten (10) lighting outlets or openings, or any combination of receptacle outlets and lighting outlets totaling not more than ten (10).
(3)
In one- and two-family dwellings, the small appliance circuits serving the kitchen countertop and similar areas shall be limited to not more than two (2) receptacle outlets or openings for the first two (2) such circuits; the third and succeeding small appliance circuits shall be limited to not more than three (3) receptacle outlets or openings per circuit.
(4)
In one- and two-family dwellings, the microwave receptacle outlet shall be a dedicated 20-amp-rated circuit, and shall share with no other outlets.
k. 
Article 230.46 is amended to read as follows:
230.46 Spliced conductors. Service entrance conductors shall be permitted to be spliced or tapped by clamped or bolted connections. Splices shall be made in enclosures or, if directly buried, with a listed ground splice kit. Splices of conductors shall be made in accordance with 110.14, 300.5(E), 300.13, and Article 300.15.
Where service entrance conductors are tapped to supply two (2) to six (6) disconnection means grouped at a common location, taps shall be made with fixed lugs only.
l. 
Article 230.50 is amended as follows:
Article 230.50 Protection against physical damage. (B) (1) Service entrance cables. (3) Schedule 40 rigid nonmetallic conduit or equivalent.
m. 
Delete Article 250.53. Grounding electrode system installation. (A)(2) Supplemental electrode required.
n. 
Article 300.5 is amended as follows:
Article 300.5 Underground installations. (D) Protection from damage:
(3) Service conductors: Warning tape shall be installed a minimum of six (6) inches below grade and not less than twelve (12) inches above the electrical cables or conduit in all underground installations of fifty (50) volts or more.
(4) Enclosure and raceway damage: Where the enclosure or raceway is subject to physical damage, the conductors shall be installed in rigid metal conduit, intermediate metal conduit, Schedule 40 rigid nonmetallic conduit, or equivalent.
Add "(5) Underground conductors to comply with installation requirements. All underground conductor installations, in addition to complying with the requirements of the National Electrical Code, and laws of the State of Missouri, shall comply with the requirement that direct burial underground service conductors or feeders shall be installed in a raceway from the building to a point beyond any concrete or asphalt slabs, stoops, footings, or driveways, which may interfere with future conductor replacement."
o. 
Article 300.11 is amended as follows:
Article 300.11 Securing and supporting. (A)(2) Non-fire-rated assemblies: Add exception: One three-quarter-inch raceway or smaller, with maximum conductor fill (for example, twelve #12 AWG), shall be permitted to be supported by the ceiling support wires.
p. 
Article 314.23 is amended as follows:
Article 314.23 (B)(1) Nails and screws: Add last sentence to paragraph: "Screws may be installed through the interior sides of a non-metallic box to mount or fasten the box in place regardless of its listing and labeling, provided the heads of the screws are covered or coated with a non-metallic material."
q. 
Article 314.25 is amended as follows:
Article 314.25 Covers and canopies. Add the following: "The requirement for machine-threaded screws shall not apply to plastic outlet boxes."
r. 
Article 334.12 is amended as follows:
Article 334.12 Uses not permitted. (A) Types NM, NMC, and NMS. Types NM, NMC, and NMS cables shall not be permitted as follows: Delete the following in its entirety: (2). "Exposed in dropped or suspended ceilings in other than one- and two-family and multifamily dwellings."
Article 334.12(B) Types NM and NMS. Types NM and NMS cables shall not be used under the following conditions or in the following locations. Exception: Type NMS cable shall be permitted in wet or damp locations.
s. 
Article 334.15 is amended as follows:
Article 334.15 Exposed Work. (B) Protection from physical damage: Where schedule 80 PVC is stated in paragraph, replace with scheduled 40 PVC or better. Cable shall be protected from physical damage where necessary by rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 40 PVC conduit, or other approved means. Where passing through a floor, the cable shall be enclosed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 40 PVC conduit, or other approved means extending at least one hundred fifty (150) mm (six (6) inches) above the floor.
t. 
In Article 334.30, insert words "non-conductive insulated" before word "staples."
u. 
Article 334.80 is amended as follows:
Article 334.80 Ampacity. The ampacity of Types NM, NMC and NMS cable shall be determined in accordance with 310.15. The ampacity shall be in accordance with the sixty degrees Celsius (60° C.) (one hundred forty degrees Fahrenheit (140° F.)) conductor temperature rating. The ninety degrees Celsius (90° C.) (one hundrd ninety-four degrees Fahrenheit (194° F.)) rating shall be permitted to be used for ampacity derating purposes, provided the final derated ampacity does not exceed that for a sixty degrees Celsius (60° C.) (one hundred fory degrees Fahrenheit (140° F.)) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable try shall be determined in accordance with 392.11.
Where more than two NM cables containing two (2) or more current-carrying conductors are installed, without maintaining spacing between the cables, through the same opening in wood framing that is to be fire- or draft-stopped using thermal insulation, caulk, or sealing foam, the allowable ampacity of each conductor shall be adjusted in accordance with Table 310.15(B)(2)(a). The rest of 334.80 is deleted in its entirety.
v. 
Article 338.10 is amended to read as follows:
Article 338.10 Uses permitted. (B)(4)(a) Interior installations. In addition to the provisions of this Article, Type SE service-entrance cable used for interior wiring shall comply with the installation requirements of Part II of Article 334, excluding 334.80.
w. 
Article 404.9 is amended as follows:
Article 404.9 Provisions for General-use shop switches. (B) Grounding: Add exception 4: In one- and two-family dwellings, switches mounted to non-metallic boxes with non-metallic face plates shall not be required to be effectively grounded.
x. 
Article 404.10 is amended as follows: Article 404.10 Mounting of snap switches. (B) Box mounted. Add last sentence to paragraph, as follows: "The requirement for machine-threaded screws shall not apply to plastic outlet boxes."
y. 
Article 406.4 is amended as follows: Article 406.4 General installation requirements. (D) Replacements. Delete the following sentence: "Arc-fault circuit-interrupter type and ground-fault circuit-interrupter type receptacles shall be installed in a readily accessible location."
z. 
Article 406.5 is amended as follows: Article 406.5 Receptacle mounting. Add last sentence to first paragraph: "The requirement for machine-threaded screws shall not apply to plastic outlet boxes."
aa. 
Article 406.9 is amended as follows:
Article 406.9 Receptacles in damp or wet locations.
(A) Damp locations. A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is covered (attachment plug cap not inserted and receptacle covers closed).
An installation suitable for wet locations shall also be considered suitable for damp locations. A receptacle shall be considered to be in a location protected from weather where located under roofed open porches, canopies, marquees, and the like, and will not be subjected to a beating rain or water runoff. The rest of 406.9(A) is deleted in its entirety.
(B) Wet locations.
(1) Receptacles of fifteen (15) and twenty (20) amperes in a wet location. Receptacles of 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. Weatherproof in-use or bubble covers not required.
The rest of 406.9(8) is deleted in its entirety.
bb. 
In Article 406.12 Tamper-resistant receptacles, delete areas listed in (1), (5), (6) and (7).
cc. 
Article 410.24 is amended as follows: Article 410.24 Connection of electric-discharge and LED luminaires. (B) Access to boxes. Delete in its entirety.
dd. 
In Article 408.36, add the following:
Installation of 120-volt plug-in circuit breakers in three-phase, four-wire panelboard on a delta system is prohibited.
Exception No. 1: Individual protection shall not be required for a panelboard used as service equipment with multiple disconnecting means in accordance with 230.71. In panelboards protected by three (3) or more main circuit breakers or sets of fuses, the circuit breakers or sets of fuses shall not supply a second bus structure within the same panelboard assembly.
Exception No. 2: Individual protection shall not be required for a panelboard protected on its supply side by two (2) main circuit breakers or two (2) sets of fuses having a combined rating not greater than that of the panelboard. A panelboard constructed or wired under this exception shall not contain more than forty-two (42) overcurrent devices. For the purposes of determining the maximum of forty-two (42) overcurrent devices, a two-pole or a three-pole circuit breaker shall be considered as two (2) or three (3) overcurrent devices, respectively.
Exception No. 3: For existing panelboards, individual protection shall not be required for a panelboard used as service equipment for an individual residential occupancy.
ee. 
Article 422.12 is amended to read as follows:
422.12 Central heating equipment. Central heating equipment other than fixed electric space-heating equipment shall be supplied by an individual branch circuit, and a disconnect shall be provided in sight and within six (6) feet of the unit.
Exception No. 1: Auxiliary equipment, such as a pump, valve, humidifier, or electrostatic air cleaner directly associated with the heating equipment shall be permitted to be connected to the same branch circuit.
Exception No. 2: Permanently connected air-conditioning equipment shall be permitted to be connected to the same branch circuit.
ff. 
In Article 422.16 Flexible cords. (B) Specific appliances, add: (5) Storage-type water heaters. Storage-type water heaters shall be permitted to be cord-and-plug connected with a flexible cord rated at thirty (30) amperes. Cord will not be required to be listed for this use.
gg. 
In Article 440.14 Location, add: Exception No 3: Cord-and-plug-connected appliances.
hh. 
In Article 547.5 Wiring methods. (F) Separate equipment grounding conductor, add new last sentence: "Aluminum equipment grounding conductors shall not be permitted underground in agricultural buildings or areas."
ii. 
Article 550.15 is amended as follows: Article 550.15. Wiring methods and materials. (H) Under-chassis wiring (exposed to weather). (2): Change Schedule 80 PVC to Schedule 40 PVC.
jj. 
In Article 600.1, add the following: Permanently installed electric signs, outline lighting, and field-assembled skeletal neon systems shall be listed and labeled by a nationally recognized testing laboratory. Branch circuit wiring and primary electrical connection of the above shall be completed by a licensed electrical contractor. The electrical contractor shall be responsible for obtaining the electrical permit, scheduling an inspection, and the installations shall not be energized prior to approval by the electrical inspector.
kk. 
Article 600.6 is amended as follows: Article 600.6 Disconnects. (A)(1): Change the wording of the first sentence as follows "Disconnects for signs and for outline lighting shall be located at the point where the feeder or branch circuits(s) enters the sign enclosure or pole, and shall disconnect all ungrounded conductors where they enter the sign enclosure or pole."
ll. 
In Article 680.43 Indoor installations, delete Exception No. 2.
mm. 
In Article 680.74 Bonding, delete the last sentence.
[Ord. No. 2017-1241 § 3, 8-21-2017]
A. 
The punishment of a violation of this Article shall be as follows:
1. 
The maximum fine combined with the amount of court costs that can be imposed for the violation of any ordinance violation shall be two hundred dollars ($200.00) for the first violation, two hundred seventy-five dollars ($275.00) for the second violation, three hundred fifty dollars ($350.00) for the third violation, and four hundred fifty dollars ($450.00) for the fourth and any subsequent municipal ordinance violation.
2. 
Ordinance violations as defined below shall not be punishable by imprisonment, unless the violation:
a. 
Endangered the health or welfare of others; or
b. 
Involved eluding or giving false information to a Law Enforcement Officer.
3. 
A person convicted of an ordinance violation shall not be placed in confinement for failure to pay a fine unless such non-payment violates the terms of the person's probation or unless the due process procedures mandated by Missouri Supreme Court Rule 37.65 or its successor rule are strictly followed by the court.
4. 
Court costs that apply shall be assessed against such person unless the court finds that the defendant is indigent based on standards set forth in determining such by the presiding judge of the circuit. Such standards shall reflect model rules and requirements to be developed by the Missouri Supreme Court.
5. 
No court costs shall be assessed if the defendant is found to be indigent under Subsection (A)(4) or the case is dismissed.
[Ord. No. 2017-1241 § 4, 8-21-2017]
The portions of this Article shall be severable. In the event that any portion of this Article is found by a court of competent jurisdiction to be invalid, the remaining portions of this Article are valid, unless the court finds the valid portions of this Article are so essential and inseparably connected with and dependent upon the void portion that it cannot be presumed that the Town Council would have enacted the valid portions without the invalid one, or unless the court finds that the valid portions standing alone are incomplete and are incapable of being executed in accordance with the legislative intent.