Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Whitefish Bay, WI
Milwaukee County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
[Adopted by Ord. No. 1461 (Sec. 4.12 of the Codification)]
To provide early warning in the event of fire, detection systems shall be installed and maintained in operable condition in all occupancies and locations set forth in this article.
[Amended by Ord. No. 1681]
Smoke and heat detection systems shall be installed in all spaces in all new buildings regardless of size or construction except for one- and two-family dwellings. The detection systems shall be in all spaces, including, but not limited to, hidden spaces (e.g., attics, crawl spaces, truss-constructed areas), basements, store rooms, closets, occupied and unoccupied areas. One- and two-family dwellings shall have smoke detection systems as required by the Wisconsin Statutes and the Wisconsin Administrative Code. The Fire Department is authorized to modify any of the provisions of this chapter upon application by the owner, lessee, or a duly authorized representative where there are practical difficulties in the way of carrying out the provisions of the chapter, provided that the intent of the chapter shall be complied with, public safety secured, and substantial justice done.
All detection systems shall be monitored by an approved off-site central station monitoring service, except for one- and two-family dwellings.
A. 
All components of a fire or smoke detector system shall be listed by Underwriters Laboratories (UL) or the Factory Mutual System (FM). The entire installation shall conform to applicable provisions of NFPA Standards 71, 72A, 72C, 72D or 72E, the National Electrical Code Article 760, and the Wisconsin Electric Code.
B. 
The system shall monitor the integrity of all alarm initiating and indicating appliance circuits, shall be provided with automatically charged standby batteries to maintain system operation for 24 hours in the normal supervisory mode and have sufficient capacity to operate in the alarm mode for five minutes at the conclusion of this supervisory time period. Batteries shall be supervised for connection to the system and for a low voltage threshold. The automatic battery charger shall be capable of charging fully discharged system batteries at 100%.
C. 
A Remote Annunciator shall be provided at the main entrance of the building to indicate each of the designated alarm initiating zones via red LEDs which flash when in alarm and lock in upon acknowledging the alarm. The Remote Annunciator shall be electrically supervised from the main fire alarm control panel. Space shall be provided on the Remote Annunciator for custom zone labels. The zone labels shall plainly describe the location of the zones. Different occupancies in one building shall be zoned separately.
D. 
Wiring of required fire and smoke detection systems.
(1) 
All electrical wiring in connection with required fire alarm systems, including accessory devices, such as detectors, shall be installed in rigid metal conduit or surface metal raceway.
(2) 
Separate raceway. Raceways for required fire alarm system wiring shall contain no other circuits. All such raceways shall be colored red.
E. 
External devices.
(1) 
The system shall utilize UL or FM listed fire alarm-initiating devices (pull stations, smoke detectors, heat detectors, water flow switches, duct detectors, etc.) and UL or FM listed fire alarm indicating devices (horns, bells, visual lights, etc.). Smoke detectors shall possess a light-emitting diode (LED) lamp to indicate "ready" or "alarm" status.
(2) 
Smoke detectors (photoelectric, ionization) shall be installed approximately 30 feet on center, located on the ceiling or wall of the protected area. Smoke detection shall be provided but not limited to the following areas: basements, common hallways, stairwells, sleeping rooms and all other rooms over 50 square feet in size.
(3) 
Heat detectors shall be installed approximately 50 feet on center, located on the ceiling of the protected area. Heat detection shall be provided but not limited to the following areas: furnace rooms, engine rooms, garages, hidden spaces and kitchens and all other rooms under 50 square feet in area. Heat detectors shall also be installed as a substitution for smoke detectors in locations determined by the Fire Chief to be unsuitable for smoke detector installation.
(4) 
Horns/bells.
(a) 
Alarm system horns. Horns used as the audible alarm indicating appliance shall be 24-volt direct current (DC) horns of metal construction with a minimum sound pressure output of 87 db at 10 feet. Fire alarm horns shall be UL or FM listed for fire alarm use. Horns shall be adaptable for surface or semi-flush mounting and be suitable for use within combination audiovisual systems.
(b) 
Alarm system bells. Bells used as the audible-alarm-indicating appliance shall be 24-volt DC bells of the vibrating or single-stroke type with a minimum sound pressure output of 90 db at 10 feet. Bells shall be UL or FM listed for fire alarm use. Bells shall be suitable for surface or semi-flush mounting and be suitable for use within combination audiovisual systems.
(c) 
Visual flashing lamps. Visual indicating appliances shall be comprised of a strobe-type flash tube and be entirely solid state. These devices shall be UL or FM listed and be capable of either ceiling or wall mounting. Visual units shall incorporate a built-in reflector to improve lighting characteristics. Visual units shall be incorporated as part of the horn or bell assemble.
(d) 
Horns, bells, or visual flashing lamps shall be installed in each unit, living space or tenant space in the building.
A. 
Alarm-initiating devices shall be grouped in zones identified by zone LEDs on the control panel and at the remote annunciator.
B. 
Actuation of an alarm initiating device shall:
(1) 
Cause the respective red zone alarm LED on the control panel to flash until the "acknowledge" switch is actuated at the control panel. Once acknowledged, the zone LED shall be constantly illuminated until the actuating device is restored to normal and the system is reset or equivalent operation.
(2) 
The audible system indicating appliance shall sound through the entire facility until the system alarm acknowledge/silence switch is operated.
(3) 
Visual indicating appliances shall flash until the acknowledge/silence switch is operated.
(4) 
After the acknowledge switch is operated, subsequent activation of an initiating appliance shall cause the alarm bells or horns to resound and the visual indicating appliances to flash.
C. 
Each alarm circuit and indicating appliance circuit shall be electrically supervised. Any disarrangement of system wiring such as opens or grounds shall activate the audible and visual trouble indicators at the control panel. Actuation of the trouble silence switch shall silence the audible trouble indicator but the trouble LED shall remain lit. The trouble LED shall be noncanceling, except by an actual clearing of the trouble condition and restoring the trouble silence switch to normal.
D. 
The alarm system shall provide for the selection of:
(1) 
Desired type of signal operation; alarm signal tempos, area selective codes, zone codes, general alarm codes, and alarm silence inhibit.
(2) 
UL or FM approved alarm verification operation.
(3) 
Water flow/sprinkler supervisory operation on a distinct zone of the system.
E. 
Upon actuation of smoke detector, the LED on the smoke detector shall remain constantly illuminated until the system is reset.
No fire and smoke detection system shall be installed or altered in any building until plans have been submitted to and conditionally approved by the Building Inspector and the Fire Department. Two copies of the plans shall be submitted. The plans shall contain drawings showing locations of detectors, pull stations and horns. The plans shall contain a brief description of connections within the system.
A. 
The acceptance test of a fire and smoke detection system shall be conducted in the presence of an inspector from the Fire Department prior to being placed in service. All testing shall be conducted by the installer.
B. 
The installer shall give three working days' advanced notice to the Fire Department prior to the conduction of any test.
A. 
Maintenance. Fire detection and fire alarm systems shall be tested for efficient service as specified by NFPA requirements.
B. 
A current test/maintenance record shall be posted at the system control panel.
Any fire alarm system which has been installed pursuant to this section or in compliance with any other statute, ordinance or regulation shall be maintained in operative condition at all time. It shall be unlawful for any owner or occupant to reduce the effectiveness of the protection so required; provided, however, that the owner or occupant may temporarily reduce or discontinue the protection where necessary to make tests, repairs, alterations or additions to the system or appliance. The Fire Chief shall be notified before any system is reduced or discontinued for such repair, alteration or addition and shall be notified promptly upon the system's restoration to service.