Exciting enhancements are coming soon to eCode360! Learn more 🡪
Borough of Pine Grove, PA
Schuylkill County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
All wood or coal burning stoves or appliances shall be at least 36 inches from all combustible materials. Where clearance is less than 36 inches but more than 18 inches, the combustible surface shall be protected by 1/4 inch asbestos millboard spaced one inch or more from the combustible surface. Adequate space shall be provided to permit air circulation. If clearance is less than 18 inches but more than 12 inches, the combustible wall shall be protected with a four-inch brick veneer wall extending two feet above and two feet beyond each side. All other installation shall be as follows:
A. 
All wood or coal burning stoves or appliances that have circulating devices shall be at least 24 inches from a combustible surface unless the appliance has a rating for lesser distance from combustible surface.
B. 
If the distance of any circulating wood or coal burning stove or appliance is 12 inches to 24 inches from the noncombustible surface, the surface shall be protected by 1/4 inch asbestos millboard spaced one inch or more from the walls with adequate one-inch spacing from the floor to permit air circulation between wall and shield.
C. 
If the circulating wood or coal burning stove or appliance is eight inches to 12 inches from the noncombustible surface, the surface shall be protected by 1/4 inch asbestos millboard covered with 28 gauge metal spaced one inch or more from the wall and floor to permit air circulation.
D. 
Noncombustible floor material shall extend at least 18 inches beyond the opening from which ashes are removed, and at least six inches beyond the sides and rear.
E. 
Where stove legs are at least 18 inches above a combustible surface, a 24 gauge sheet metal shall be used.
F. 
Where stove legs are between six inches and 18 inches above a combustible surface, a 24 gauge sheet metal over 1/4 inch layer of asbestos millboard or other approved noncombustible material shall be used.
G. 
Where stove legs are six inches or less above a combustible surface, a four-inch hollow masonry pad should be laid or an approved noncombustible surface of an inch thickness shall be used.
A. 
All stove pipes shall be equal to or larger than the appliance flue connector.
B. 
All connector pipe shall be of a minimum of 24 gauge black pipe or heavier.
C. 
All connector pipe shall rise from the stove toward the chimney at least 1/4 inch per foot or more.
D. 
Crimped end of chimney connector pipe shall point toward stove.
E. 
Single wall connector pipe shall not pass through the floor or wall. However, when necessary, a connector may pass through a wall under the following conditions:
(1) 
Where a ventilated type metal thimble is used and is 12 inches greater in diameter than the chimney connector.
(2) 
Where a metal or burned fireclay thimble is used and the thimble is surrounded on all sides by not less than eight inches of brickwork or equivalent fireproofing material.
(3) 
When all combustible material is removed for a sufficient distance to provide not less than 18 inches clearance on all sides of the connector. Any materials used to close this opening must be noncombustible insulating material.
(4) 
When the section of the connector pipe passing through the combustible material is replaced by a properly installed section of factory built insulated Class A pipe for solid fuels.
(5) 
All stove pipe shall be a minimum of 18 inches from a combustible surface.
(6) 
If stove pipe is 12 inches to 18 inches from combustible surface, the surface shall be covered with 1/4 inch asbestos millboard spaced one inch from the wall or ceiling used as a shield.
(7) 
If stove pipe is nine inches to 12 inches from combustible surface, the surface shall be covered with 1/4 inch asbestos millboard with a 28 gauge sheet metal spaced one inch from wall or ceiling.
A. 
Except as herein provided, all chimneys in every building hereafter erected and all chimneys hereafter altered or rebuilt shall be constructed of brick, stone or reinforced concrete or UL listed Class A Chimney. No masonry chimneys shall have walls less than four inches in thickness and all chimneys shall be lined on the inside with fire clay chimney tile set in Portland Cement mortar. The lining shall be continuous from the bottom of the flue to its extreme height. No chimney shall be corbeled out more than six inches from a brick wall and such corbeling shall consist of not less than five courses of brick, unless the chimney requires special construction, and then any special constructed chimney shall not be corbeled out to such extent that the center of gravity of the chimney would be located so as to endanger the structure.
B. 
All chimneys shall project at least three feet above the point of contact with a flat roof or two feet above any roof surface within 10 feet horizontally of the chimney. Portland cement may be used in the construction of chimneys with the addition of not more than 10% by volume of hydrated lime. No chimney in any building shall have wooded supports of any kind. Supports shall be noncombustible and shall rest upon the ground or foundation walls. Concrete footings under new chimneys shall be as hereinbefore specified for concrete footings under foundation walls. All chimneys which are dangerous from any cause shall be repaired and made safe or taken down.
C. 
The fireback of every fireplace hereafter erected shall not be less than eight inches in thickness of solid brickwork, or air cell construction, nor less than 12 inches of stone lined with fire brick. When a grate is set in fireplace, a lining of fire brick at least two inches in thickness shall be added to the fireback, or soapstone, fireclay, or cast iron may be used, if solidly backed with brick or concrete. All smoke pipes shall enter the chimney through a flue thimble or its equivalent such that the construction shall make a fire tight joint with the chimney tile flue liner.
D. 
All flue holes when not in use shall be closed with tight-fitting metal covers. No wooden beams or joists shall be placed within one inch of the outside face of the chimney or flue whether the same be for smoke, air or any purpose, except for hot air flues for heating purposes. No wood work shall be within four inches of the back wall of any fireplace except if a chimney is built such that the thickness from the flue line is eight inches or more. Necessary wood work may be placed against the chimney by using asbestos sheeting between and around the wood so placed under the approval of the Fire Marshal.