[HISTORY: Adopted by the City Council of the City of Galax 10-13-1992. Amendments noted where applicable.]
GENERAL REFERENCES
Building construction — See Ch. 36.
Health and sanitation — See Ch. 71.
Mechanical workers — See Ch. 94.
Subdivision of land — See Ch. 130.
Water and sewers — See Ch. 153.
Zoning — See Ch. 160.
ATTACHMENTS
044a Table 1
The purpose of this chapter is to eliminate cross-connections and to protect the public health. This chapter provides for establishment and enforcement of a program of cross-connection control and backflow prevention in accordance with the Commonwealth of Virginia, State Board of Health, Waterworks Regulations 1974, as amended.
A.
Commonwealth of Virginia
Department of Health
Waterworks Regulations
Part II, Article 3
Cross Connection Control and Backflow Prevention in Waterworks
B.
Uniform Statewide Building Code, Volume I;
Uniform Statewide Building Code, Volume II.
A. 
The Director, the City Engineer or his designated agent shall administer and enforce the provisions of this chapter under the direction of the City Manager.
B. 
It shall be the duty of the Director to cause inspections to be made of properties served by the waterworks where cross-connection with the waterworks is deemed possible. The method of determining potential cross-connection with the waterworks and the administrative procedures shall be established by the Director in a cross-connection control program (programs) approved by the Commonwealth of Virginia, Department of Health, Division of Water Supply Engineering.
C. 
The responsibility to carry out the program lies with the local Building Official. The program shall be carried out in accordance with the Uniform Statewide Building Code and the Commonwealth of Virginia, State Board of Health, Waterworks Regulations and shall be a continuing program.
A. 
The local Building Official shall have the right to enter at any reasonable time premises served by a connection to the waterworks for the purpose of inspecting, observing, sampling and testing the water supply system or systems for a cross-connection. Upon request, the water supply system owner or occupants or the property served shall furnish to the Building Official pertinent information regarding the water supply system or systems on such property. The refusal of such information or refusal of access, when requested, shall be deemed evidence of the presence of a cross-connection.
B. 
The Building Official shall take positive action to ensure that the waterworks is adequately protected at all times. If a cross-connection exists or backflow occurs into a water supply system or if the pressure in the waterworks is lowered below 10 psig, water service to the water supply system shall be denied or discontinued upon continuation of any violation beyond the time provided in the notice of violation given pursuant to § 44-6C. Water service shall not be restored until the deficiencies have been corrected or eliminated to the satisfaction of the Building Official.
C. 
Any water supply system owner found to be in violation of any provision of this chapter shall be served a written notice of violation, sent certified mail to the water supply system owner's last known address, stating the nature of the violation, corrective action required and providing a reasonable time limit, not to exceed 30 days, from the date of receipt of the notice of violation to bring the water supply system into compliance with this chapter.
As used in this chapter, the following terms shall have the meanings indicated:
AIR GAP SEPARATION
The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying pure water to a tank, plumbing fixture or other device and the rim of the receptacle.
AUXILIARY WATER SYSTEM
Any water system on or available to the premises other than the waterworks. These auxiliary waters may include water from a source such as wells, lakes or streams; or process fluids; or used water. They may be polluted or contaminated or objectionable or constitute an unapproved water source or system over which the water purveyor does not have control.
BACKFLOW
The flow of water or other liquids, mixtures or substances into the distribution piping of a waterworks from any source or sources other than its intended source.
BACKFLOW PREVENTION DEVICE
Any approved device, method or type of construction intended to prevent backflow into a waterworks.
CONSUMER
Any person who drinks water from a waterworks.
CONSUMER'S WATER SYSTEM
Any water system located on the consumer's premises, supplied by or in any manner connected to a waterworks.
CONTAMINANT
Any objectionable or hazardous physical, chemical, biological or radiological substance or matter in water.
CROSS-CONNECTION
Any connection or structural arrangement, direct or indirect, to the waterworks whereby backflow can occur.
DEGREE OF HAZARD
The level of health hazard, as derived from an evaluation of the potential risk to health and the adverse effect upon the waterworks.
DISTRIBUTION MAIN
A water main whose primary purpose is to provide treated water to service connections.
DIVISION OF WATER SUPPLY ENGINEERING
The Commonwealth of Virginia, Virginia Department of Health, Office of Water Programs; Division of Water Supply Engineering.
DOMESTIC USE OR USAGE
Normal family or household use, including drinking, laundering, bathing, cooking, heating, cleaning and flushing toilets. (See Appendix A for Title 32.1, Article 2, Code of Virginia 1950, as amended.)
DOUBLE GATE-DOUBLE CHECK VALVE ASSEMBLY
An approved assembly composed of two single independently acting check valves, including tightly closing shutoff valves located at each end of the assembly, and petcocks and test gauges for testing the water tightness of each check valve.
ENTRY POINT
The place where water from the source is delivered to the distribution system.
HEALTH HAZARD
Any condition, device or practice in a waterworks or its operation that creates or may create a danger to the health and well-being of the water consumer.
MAXIMUM CONTAMINANT LEVEL
The maximum permissible level of a contaminant in water which is delivered to the free flowing outlet of the ultimate user of a waterworks, except, in the cases of turbidity and vocs, where the maximum permissible level is measured at each entry prior to the distribution system. Contaminants added to the water under circumstances controlled by the user, except those resulting from corrosion of piping and plumbing caused by water quality, are excluded from this definition. Maximum contaminant levels may be either primary (PMCL), meaning based on health considerations, or secondary (SMCL) meaning based on aesthetic considerations.
PLUMBING FIXTURE
A receptacle or device which is either permanently or temporarily connected to the water distribution system of the premises and which demands a supply of water therefrom; or discharges used water, waste materials or sewage, either directly or indirectly, to the drainage system of the premises; or requires both a water supply connection and a discharge to the drainage system of the premises.
POLLUTION
The presence of any foreign substance (chemical, physical, radiological or biological) in water that tends to degrade its quality so as to constitute an unnecessary risk or impair the usefulness of the water.
POLLUTION HAZARD
A condition through which an aesthetically objectionable or degrading material may enter the waterworks or a consumer's water system.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICE (RPZ DEVICE)
A device containing a minimum of two independently acting check valves, together with an automatically operated pressure differential relief valve located between the two check valves. During normal flow and at the cessation of normal flow, the pressure between these two checks shall be less than the supply pressure. In case of leakage of either check valve, the differential relief valve shall operate to maintain this reduced pressure by discharging to the atmosphere at less than the supply pressure. The unit must include tightly closing shut-off valves located at each end of the device, and each device shall be fitted with properly located test cocks. These devices must be of the approved type.
SERVICE CONNECTION
The point of delivery of water to a customer's building service line as follows:
A. 
If a meter is installed, the service connection is the downstream side of the meter.
B. 
If a meter is not installed, the service connection is the point of connection to the waterworks.
C. 
When the purveyor is all the building owner, their service connection is the entry point to the building.
PREMISES
A piece of real estate, house or building and its land.
PROCESS FLUIDS
Any kind of fluid or solution which may be chemically, biologically or otherwise contaminated or polluted which would constitute a health, pollutional or system hazard if introduced into the waterworks. This includes, but is not limited to:
A. 
Polluted or contaminated water;
B. 
Process waters;
C. 
Used water, originating from the waterworks which may have deteriorated in sanitary quality;
D. 
Cooling waters;
E. 
Contaminated natural waters taken from wells, lakes, streams or irrigation systems;
F. 
Chemical in solution or suspension; and
G. 
Oils, gases, acids, alkalis and other liquid and gaseous fluid used in industrial or other processes or for fire-fighting purposes.
PURE WATER OR POTABLE WATER
Water fit for human consumption and domestic use which is sanitary and normally free of minerals, organic substances and toxic agents in excess of reasonable amounts for domestic usage in the area served and normally adequate in quantity and quality for the minimum health requirements of the persons served. (See Title 32.1, Article 2, Code of Virginia 1950, as amended.)
SYSTEM HAZARD
A condition posing an actual or threat of damage to the physical properties of the waterworks or a customer's water supply system.
USED WATER
Any water supplied by a water purveyor from the waterworks to a consumer's water supply system after it has passed through the service connection.
WATER SUPPLY
The water that shall have been taken into a waterworks from all wells, streams, springs, lakes and other bodies of surface water (natural or impounded), and the tributaries thereto, and all impounded groundwater, but the term "water supply" shall not include any waters above the point of intake of such waterworks. (See Title 32.1, Article 2, Code of Virginia 1950, as amended.)
WATER SUPPLY SYSTEM
The water service pipe, water distributing pipes and necessary connecting pipes, fittings, control valves and all appurtenances in or adjacent to the building or premises.
WATERWORKS
A system that serves piped water for drinking or domestic use to the public, at least 15 connections or an average of 25 individuals for at least 60 days out of the year. The term "waterworks" shall include all structures, equipment and appurtenances used in the storage, collection, purification, treatment and distribution of pure water except the piping and fixtures inside the building where such water is delivered. (See Title 32.1, Article 2, Code of Virginia 1950, as amended.)
WATERWORKS, OWNER OR WATER PURVEYOR
An individual, group of individuals, partnership, firm, association, institution, corporation, government, entity or the federal government which supplies or proposes to supply water to any person within this state from or by means of any waterworks. (See Title 32.1, Article 2, Code of Virginia 1950, as amended.) For this chapter it is the City of Galax Water Plant.
A. 
General. Effective cross-connection control requires the cooperation of the water purveyor, the Director, the Building Official, the water system owner and the backflow prevention device tester.
B. 
Water purveyor and director.
(1) 
This program shall be carried out in accordance with the Uniform Statewide Building Code and the Commonwealth of Virginia, State Board of Health, Waterworks Regulations, and shall be a continuing program.
(2) 
The purveyor has full responsibility for water quality and for the construction, maintenance and operation of the waterworks beginning at the water source and ending at the downstream end of the service connection.
(3) 
The purveyor shall not install or maintain a water service connection to a water supply system where cross-connections may exist unless such cross-connections are abated or controlled to the satisfaction of the Director.
(4) 
The purveyor shall not install or allow any connection which would allow water from an auxiliary water system to enter a waterworks, either directly or through a water supply system, unless the auxiliary water system and the method of connection and use of such system have been approved by the Division of Water Supply Engineering, Office of Water Program, Virginia Department of Health.
(5) 
The Director shall have thorough inspections and operational tests made at least annually of backflow prevention devices or low-pressure cutoff devices which are required and installed. Copies of results of these inspections and tests shall be kept on file and made available to the Division of Water Supply Engineering. The devices shall be repaired, overhauled or replaced by the water supply system owner as directed by the Director, as outlined in the program. Nothing in this section shall prevent the purveyor from installing and operating approved devices or making repairs.
(6) 
The purveyor shall review certified plans for fire service connections and lawn or irrigation systems served by the waterworks and recommend to the Director if the plans are acceptable. If unacceptable, the designer and the Director shall consult with the Division of Water Supply Engineering for a determination of what will be acceptable. The revised design shall be resubmitted for additional review. Only after final approval by the Director will it be permissible to proceed with the final construction. All plans should be submitted to the Director, with sufficient copies for the purveyor to forward an approved copy of the plans to the Division of Water Supply Engineering.
(7) 
In the event of backflow of pollution or contamination into the waterworks, the Director shall promptly take or cause corrective action to confine and eliminate the pollution or contamination. The Director shall immediately notify the Division of Water Supply Engineering when backflow occurs.
(8) 
The Director shall take positive action to ensure that the waterworks is adequately protected at all times. If a cross-connection exists or backflow occurs into a water supply system or if the pressure in the waterworks is lowered below 10 psi gauge, the Director may discontinue the water service to the water supply system and water service shall not be restored until the deficiencies have been corrected or eliminated to the satisfaction of the Director.
(9) 
At premises where, in the view of the Director, the complexity of the plumbing system would best be surveyed by commercial, industrial or institutional personnel experienced in such processes and having successfully completed a course recognized by the American Water Works Association, the Virginia Department of Health or the Virginia Cross Connection Control Association for testing backflow prevention devices, those personnel may, upon approval of the Director and the Division of Water Supply Engineering, carry out the requirement of the cross-connection control program pertaining to cross-connection surveys, cross-connection inspections and device testing, repair and maintenance, in addition to the requirements of the water supply system owner and backflow prevention device tester. The local Building Official shall review the records of surveys, inspections, tests, repairs and maintenance and make inspections of areas within the premises and test devices, all on a (quarterly) basis.
C. 
Local Building Official.
(1) 
The local Building Official's responsibility generally begins at the downstream end of the service connection and carries throughout the entire length of the water supply system in accordance with the Uniform Statewide Building Code. This chapter requires the local Building Official to enter, survey, inspect, etc. all premises as directed by the Director in order to carry out the program.
(2) 
The local Building Official reviews building plans and inspects new plumbing as it is installed. Where the review of building plans or the inspection of a water supply system suggests or detects an actual or potential cross-connection, the local Building Official shall ensure that such cross-connections are either eliminated or abated with approved backflow prevention devices as outlined in the program.
D. 
Water supply system owner.
(1) 
The water supply system owner has the responsibility of preventing pollutants and contaminants from entering his potable water supply system(s) or the waterworks. The water supply system owner's responsibility starts at the point of delivery (downstream end of service connection) and includes all of his water supply systems.
(2) 
The water supply system owner, at his own expense unless otherwise directed by the Director, shall install, operate, test and maintain approved backflow prevention devices installed at the service connection and shall install, operate, test and maintain approved backflow prevention devices in his water supply system as directed by the local Building Official as outlined in the program.
(3) 
The water supply system owner shall maintain accurate records of tests and repairs made to backflow prevention devices and provide the local Building Official with copies of such records on request. The records shall be on forms approved by the Director as outlined in the program and shall include the list of materials or replacement parts used. Following any repair, overhaul, repiping or relocation of a device, the water supply system owner shall have it tested to ensure that it is in good operating condition and will prevent backflow. Tests, maintenance and repairs of backflow prevention devices shall be made by a backflow prevention device tester acceptable to the Director as outlined in the program.
(4) 
In the event of pollution or contamination of the waterworks or a water supply system due to backflow into the water supply system, the water supply system owner shall promptly take steps to confine further spread of the pollution or contamination within the system and shall notify the water purveyor of the condition. The water supply system owner shall make free his water supply system(s) of any pollutants or contaminants.
E. 
Backflow prevention device tester.
(1) 
The tester is responsible for making competent inspections and for repairing or overhauling backflow prevention devices and making reports of such repair to the water supply system owner on forms approved by the Director as outlined in the program. The tester shall include the list of materials or replacement parts used and ensure that original manufactured parts are used in the repair of or replacement of parts in a backflow prevention device. The tester shall not change the design or operational characteristics of a device during repair or maintenance without prior written approval of the water supply system owner, water purveyor and local Building Official.
(2) 
The tester shall be equipped with and be competent in the use of all the necessary tools, gauges, manometers and other equipment necessary to properly test, repair and maintain backflow prevention devices.
A. 
Protection.
(1) 
An approved backflow prevention device shall be installed at each service connection to a water supply system where, in the judgment of the Director, a health, pollutional or system hazard to the waterworks exists.
(2) 
All potable water openings or outlets shall be protected against backflow where, in the judgment of the Director, a health, pollutional or system hazard to the waterworks exists.
B. 
Method. The required method of protection provided, containment and/or isolation, shall be, in the best judgment of the Director, the method which best provides protection of health, pollution or system hazards.
C. 
Special conditions. When, as a matter of practicality, the backflow prevention device cannot be installed at the service connection, the device may be located downstream of the service connection but prior to any unprotected takeoffs.
D. 
A backflow prevention device shall be installed at each service connection to a water supply system serving the premises or shall be installed where the plumbing fixture connects to the premises water supply system, as appropriate, where the following conditions exist:
(1) 
Premises on which any substance is handled in such a manner as to create an actual or potential hazard to a waterworks. (This shall include premises having sources or systems containing process fluids or waters originating from a waterworks which are no longer under the control of the water purveyor.)
(2) 
Premises having internal cross-connections that, in the judgment of the Director, may not easily be correctable or intricate plumbing arrangements which make it impracticable to determine whether or not cross-connections exist.
(3) 
Premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impracticable to make a complete cross-connection survey.
(4) 
Premises having a repeated history of cross-connections being established or reestablished.
(5) 
Other premises specified by the Director where cause can be shown that a potential cross hazard not enumerated above exists. Examples may include multi-use commercial, office, warehouse or other premises where the degree of hazard is subject to change without knowledge of the Director.
E. 
A backflow prevention device shall be installed at fire protection system connections to the premises' water supply system or to the waterworks in accordance with the following:
(1) 
Additives or nonpotable source: where systems have chemical additives, antifreeze or are connected to a nonpotable secondary water supply, the potable water supply shall be protected by a reduced pressure principle backflow preventer. Where chemical additives or antifreeze are added to only a portion of an automatic fire sprinkler or standpipe system, the reduced pressure principle backflow preventer shall be permitted to be so located to isolate that portion of the system.
(2) 
Fire Department connection (siamese connections): where systems have Fire Department connections, the potable water supply shall be protected by a double gate-double check valve assembly or double detector check valve assembly.
(3) 
Piping not approved for water distribution: where systems are installed with piping, joint and connections not approved for water distribution systems, the potable water supply shall be protected by a double gate-double check valve assembly or double detector check valve assembly.
(4) 
Piping approved for water distribution: where systems are installed with piping, joints and connections approved for water distribution systems, isolation of the water supply shall not be required where the premises water supply system design provides freely flowing potable water through the fire protection system and the potable water is not allowed to stagnate or deteriorate in water quality.
F. 
Premises having booster pumps connected to the waterworks shall be equipped with a low pressure regulating or cut-off device to shut off the booster pump when the pressure in the waterworks drops to a minimum of 10 psi gauge.
G. 
An approved backflow prevention device shall be installed at each service connection to a water supply system serving, but not necessarily limited to, the following types of facilities:
(1) 
Hospitals, mortuaries, clinics, veterinary establishments, nursing homes and medical buildings.
(2) 
Laboratories.
(3) 
Piers, docks, waterfront facilities.
(4) 
Sewage treatment plants, sewage pumping stations or stormwater pumping stations.
(5) 
Food and beverage processing plants.
(6) 
Chemical plants, dyeing plants and pharmaceutical plants.
(7) 
Metal plating industries.
(8) 
Petroleum processing or storage plants.
(9) 
Radioactive materials processing plants or nuclear reactors.
(10) 
Car washes and laundries.
(11) 
Lawn sprinkler systems, irrigation systems.
(12) 
Fire service systems.
(13) 
Slaughterhouses and poultry processing plants.
(14) 
Farms where the water is used for other than household purposes.
(15) 
Commercial greenhouses and nurseries.
(16) 
Health clubs with swimming pools, therapeutic baths, hot tubs or saunas.
(17) 
Paper and paper products plants and printing plants.
(18) 
Pesticide or exterminating companies and their vehicles with storage or mixing tanks.
(19) 
Schools or colleges with laboratory facilities.
(20) 
High-rise buildings (four or more stories).
(21) 
Others specified by the Director and/or Division of Water Supply Engineering when reasonable cause can be shown for a potential backflow or cross-connection hazard.
H. 
Auxiliary water systems shall not be permitted to physically connect with the public water system at the service point or at any location within the consumer's private water system. Public water system consumption to supplement an auxiliary water system, by means of an air gap, may be permitted if approved by the Director, Division of Water Supply Engineering, and the Department of Health. Backflow prevention devices shall not be permitted for the connection of the public water system to an auxiliary water system located on private premises.
[Added 11-14-2011]
The type of protection required shall depend on the degree of hazard which exists or may exist and on the method of potential backflow. Backflow occurs either by back pressure or by backsiphonage. The degree of hazard, either high, moderate or low, is based on the nature of the contaminant, the potential of the health hazard, the probability of the backflow occurrence and the effect on waterworks structures, equipment and appurtenances used in the storage, collection, purification, treatment and distribution of pure water. Table 1 shall be used as a guide to determine the degree of hazard for any situation.[1]
A. 
Air gaps give the highest degree of protection and shall be used whenever practical to do so in high-hazard situations subject to back pressure.
B. 
An air gap separation and a reduced pressure principle backflow prevention device will protect against back pressure when operating properly.
C. 
Vacuum breakers will not protect against back pressure, but will protect against backsiphonage when operating properly. Vacuum breakers may be used in high-hazard situations subject to backsiphonage only.
D. 
Backflow prevention devices consisting of dual independent check valves with or without an intermediate atmospheric vent shall only be used in low-hazard situations.
E. 
Barometric loops are not acceptable.
F. 
An interchangeable connection or change-over device is not acceptable.
G. 
Reduced pressure principle type backflow preventers shall not be installed in pits or areas subject to flooding.
A. 
Any backflow prevention device shall be of the approved type and shall comply with the Uniform Statewide Building Code.
B. 
Any backflow prevention device shall be installed in a manner approved by the local Building Official and in accordance with the Uniform Statewide Building Code.
C. 
Existing backflow prevention devices approved by the Director and the Division of Water Supply Engineering prior to the effective date of this chapter shall, except for inspection, testing and maintenance requirements, be excluded from the requirements of Subsections A and B if the Director and the Division of Water Supply Engineering are assured that the devices will protect the waterworks.
A. 
It shall be the responsibility of water supply system owners to maintain all backflow prevention devices within the building or on the premises in good working order and to make no piping or other arrangements for the purpose of bypassing backflow prevention devices.
B. 
Periodic testing and inspection schedules shall be established by the Director as outlined in the program for all backflow prevention devices and the interval between testing and inspections and overhauls of each device shall be established in accordance with the age and condition of the device. Inspection and testing intervals shall not exceed one year, and overhaul intervals shall not exceed five years. The testing procedures shall be in accordance with the manufacturer's instructions.