Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Evans, NY
Erie County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Amended 12-15-1993 by L.L. No. 13-1993]
All structures shall be maintained in conformity with the New York State Uniform Fire Prevention and Building Code.
[Added 12-15-1993 by L.L. No. 13-1993]
A. 
Firesafety equipment, including but not limited to fire-extinguishing, fire-warning and standpipe systems, shall be maintained operable at all times and under all weather conditions, except during regular repairs. The Code Enforcement Official and the Fire Department shall be notified when such equipment is placed out of service or placed back in service.
B. 
It shall be prohibited for any person to render a fire-extinguishing or fire-warning device or system inoperable or inaccessible, except during drills, maintenance periods, emergencies or prescribed testing.
C. 
All hardware and smoke detectors shall have battery backup.
(1) 
One- or two-family dwellings. At least one single-station smoke-detecting device, as described in the reference standard of the National Fire Protection Association (RS 56-Z), shall be installed on or near the ceiling in every existing one- or two-family dwelling in the state used as a residence, in conformity with Section 1060.10 of the New York State Uniform Fire Prevention and Building Code, except that battery-operated devices are permitted. Further, an affidavit shall be submitted by the grantor of such dwelling or apartment at the time of conveyance indicating that such smoke-detecting alarm device has been installed and is operable.
(2) 
Multiple dwellings. At least one single-station smoke-detecting alarm device shall be installed on or near the ceiling in each apartment or other sleeping unit of multiple dwellings, in conformity with Section 1060.10 of the New York State Uniform Fire Prevention and Building Code. Battery-operated devices are permitted as described in reference standard National Fire Protection Association 74.
(3) 
All transient-occupied housing, hotels, lodging houses and lodging units shall have portable smoke detectors of both audible and visual design. The number of detectors shall be 3% of the number of sleeping rooms, with a minimum of one operational detector per building. Proprietors shall post conspicuously a sign, with letters at least three inches in height, at the main desk or other similar station, advising of the availability of such detectors. Such detectors shall be in accordance with Part 850 of the New York State Uniform Fire Prevention and Building Code, shall have a flash-frequency range of 60 to 120 flashes per minute and shall have a minimum visible effective intensity as set forth in Section 3-z.4.3 of reference standard National Fire Protection Association 72G. Hardwiring of audible/visual detectors into an existing central closed circuit alarm system shall be permitted in lieu of such portable detectors.
D. 
Ground fault interrupters shall be installed in all electrical outlets in kitchens and bathrooms to reduce possibility of electrocution.