[Adopted 8-13-1991 by Ch. No. 983 as §§ 16-30 through 16-38 of the 1991 Code (Ch. No. 1090)]
As used in this article, the following terms shall have the meanings indicated:
APPROVED BACKFLOW PREVENTION DEVICE
A device to counteract back pressures or prevent back siphonage. This device must be in conformance with the latest revision of the AWWA Standard C506.
AUXILIARY SUPPLY
Any water source or system, other than the public water system, that may be available in the building or on the premises.
BACKFLOW
The flow of liquids in the direction opposite to the normal flow or the introduction of any foreign liquids, gases, or substances into the water system of the Town.
CONTAMINATION
The entry into or presence in a public water supply system of any substance which may be deleterious to health and/or quality of the water.
CROSS CONNECTION
Any physical arrangement where a public water system is connected, directly or indirectly, with any other nondrinkable water system or auxiliary system, sewer, drain conduit, swimming pool, storage reservoir, plumbing fixture, or any other device which contains, or may contain, contaminated water, sewage, or other liquid of unknown or unsafe quality which may be capable of imparting contamination to the public water system as a result of backflow. Bypass arrangements, jumper connections, removable sections, swivel or change-over devices, or other temporary or permanent devices through which, or because of which, backflow may occur are considered to be cross connections.
DEGREE OF HAZARD
Derived from the evaluation of a health, system, plumbing or pollutional hazard.
DIRECTOR
The Director of Public Works of the Town of Westerly, or authorized agent.
HEALTH HAZARD
An actual or potential threat of contamination of a physical or toxic nature to the public potable water system or the consumer's potable water system that would be a danger to health.
PLUMBING HAZARD
An internal or plumbing-type cross connection in a consumer's potable water system that may be either a pollutional or a contamination-type hazard. This includes, but is not limited to, cross connections to toilets, sinks, lavatories, wash trays, domestic washing machines and lawn sprinkling systems. Plumbing-type cross connections can be located in many types of structures including homes, apartment houses, hotels and commercial or industrial establishments.
POLLUTIONAL HAZARD
An actual or potential threat to the physical properties of the water system or the potability of the public or the consumer's potable water system but which would not constitute a health or system hazard, as defined. The maximum degree of intensity of pollution to which the potable water system could be degraded under this definition would cause a nuisance or be aesthetically objectionable or could cause minor damage to the system or its appurtenances.
POTABLE WATER SUPPLY
Any system of water supply intended or used for human consumption or other domestic use.
PREMISES
Any piece of land to which water is provided including all improvements, mobile home(s) and structures located on it.
REDUCED PRESSURE PRINCIPLE DEVICE
An assembly containing two independently acting approved check valves together with a hydraulically operated mechanically independent pressure differential relief valve located between the check valves and at the same time below the first check valve. The device shall include properly located test cocks and tightly closing shutoff valves at the end of the assembly.
SYSTEM HAZARD
An actual or potential threat of severe danger to the physical properties of the public or consumer's potable water system or of a pollution or contamination which would have a detrimental effect on the quality of the potable water in the system.
TOWN or THE TOWN
The Town of Westerly Water Department.
The purpose of this article is to protect the water supply of the Town water system from contamination or pollution due to any existing or potential cross connections.
No cross connections shall be created, installed, used or maintained with the distribution system or having jurisdiction over the area served and/or serviced by the Town water system except in accordance with this article.
A. 
All industrial and commercial users connected to the Town water system shall install approved backflow prevention devices at the expense of the user, either at the service connection or within the premises, as determined by a certified cross connection inspector employed by the Town Water Department. The type and number of devices shall be determined and approved by the Director in accordance with AWWA Standards and based on the degree of hazard and the type of equipment in use.
B. 
All residential properties that are not currently connected to the Town water system shall be fitted with an approved backflow prevention device prior to making such connection. The property owner shall assume all responsibility for any backflow that should occur.
To ensure proper operation and accessibility of all backflow prevention devices, the following requirements shall apply to the installation of these devices:
A. 
No part of the backflow prevention device shall be submerged in water or installed in a location subject to flooding. If installed in a vault or basement, adequate drainage shall be provided.
B. 
Devices must be installed at the point of the water supply, before any branch in the line, on private property located just inside the property line. Alternate locations must be approved in writing by the Director prior to installations.
C. 
The device must be protected from freezing and other severe weather conditions.
D. 
All backflow prevention assemblies shall be of a type and model approved by the Town.
E. 
Only devices specifically designed and approved by the Town for vertical installation may be installed vertically.
F. 
The device shall be readily accessible with adequate room for maintenance and testing. Devices two inches and smaller shall have at least six-inch clearance on all sides of the device. All devices larger than two inches shall have a minimum clearance of 12 inches on the backside, 24 inches on the test cock side, 12 inches below the device and 36 inches above the device. Y-pattern double check valve assemblies shall be installed so that the checks are horizontal and the test cocks face upward.
G. 
The property owner assumes all responsibility for all maintenance of the device, as determined and required by the Director.
H. 
If written permission is granted to install the backflow device inside of the building, the device shall be readily accessible during working hours of 8:00 a.m. to 4:00 p.m., Monday through Friday.
I. 
If a device, with written permission, is installed inside of a premises and is four inches or larger and is installed four feet above the floor, it must be equipped with a rigidly and permanently installed scaffolding acceptable to the Director. This installation must also meet the requirements of the OSHA and Rhode Island Health Codes.
J. 
RPD device may be installed in a vault only if authorized by the Director and the relief valve discharge can be drained to daylight through a "boresite" type drain. The drain shall be of adequate capacity to carry the full rated flow of the device and shall be screened at both ends.
K. 
An approved air gap shall be located at the relief valve orifice. This air gap shall be at least twice the inside diameter of the incoming supply line as measured vertically above the top of the rim of the drain and in no case less than one inch.
L. 
Upon completion of the installation, the Director shall be notified and all devices must be inspected and tested. All backflow devices must be registered with the Town. Registration shall consist of date of installation, make, model and serial number of the backflow device, and the initial test report.
M. 
Any water pressure drop caused by the installation of a backflow device is not the responsibility of the Town.
N. 
All new construction shall install an approved backflow device prior to connection to the Town water system in accordance with § 251-20 above.
O. 
A licensed plumber or fire sprinkler installer must install all testable devices.
[Added 8-15-2011 by Ch. No. 1755]
P. 
The Westerly Water Department is not responsible for any damage to the premises caused by the backflow preventer, such as, but not limited to, thermal expansion in a closed-loop system.
[Added 8-15-2011 by Ch. No. 1755]
[Amended 5-27-2003 by Ord. No. 1449]
Authorized employees of and inspector/testers contracted by the Town, with proper identification, shall have access during reasonable hours to all parts of a premises and within the building to which water is supplied for the purpose of cross connection inspection and backflow device testing.
[Amended 5-27-2003 by Ord. No. 1449; 8-15-2011 by Ch. No. 1755]
All testable backflow devices installed within the distribution system having jurisdiction over the distribution system served or serviced by the Town shall be tested annually by a certified tester employed by or contracted by the Town, the cost of which will be charged to the customer. All such devices found not functioning properly shall be promptly repaired or replaced by the water user. All devices found not functioning properly shall be repaired or replaced by the water user within 30 days for high-level hazard uses and 90 days for low-level hazard uses unless an extension is granted by the Westerly Water Department. In cases of imminent or actual contamination of the water system, the water service may be terminated until corrected.
Any variances from these requirements shall be requested in writing by the owner and approved by the Director prior to device installation.
[Amended 8-15-2011 by Ch. No. 1755]]
Failure on the part of any customer upon due notification to discontinue the use of all cross connections and physically separate cross connections may result in termination of public water service to the premises. Failure to repair or replace nonfunctioning devices pursuant to § 251-23 may result in termination of public water service to the premises. Public water service to the premises may be terminated immediately for refusal of access pursuant to § 251-22 or if an immediate hazard is posed.