Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Smithfield, RI
Providence County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
As used in this article, the following term(s) shall have the meaning(s) indicated:
FUEL GAS
Acetylene, hydrogen, liquefied petroleum gas and other liquefied and nonliquefied flammable gases.
This article shall apply to:
A. 
Installation and operation of oxygen-fuel gas, gaseous fuels generated from flammable liquids under pressure, or electric-arc welding or cutting or any combination thereof; or
B. 
Storage of calcium carbide and gases used in welding, cutting or heat treating.
A. 
A permit shall be required of each company, corporation, copartnership or owner-operator performing welding or cutting operations except as provided in Subsection B. This permit shall not be required for each welding or cutting job location. The company, corporation, copartnership or owner-operator shall notify the Chief of the Fire Department in advance where such work is taking place, except where such work is done in response to an emergency call that does not allow time for the Chief of the Fire Department to be notified in advance of the work.
B. 
A permit shall not be required of any company, corporation, copartnership or owner-operator:
(1) 
Where the welding or cutting is performed in areas approved for the purpose; or
(2) 
Having an approved permit system established for control of the fire hazards involved.
C. 
Application for a permit required by this article shall be made by the company, corporation, copartnership or owner-operator performing the welding or cutting operation or by his duly authorized agent.
D. 
A permit for welding or cutting operations shall not be issued unless the individuals in charge of performing such operations are capable of doing such work in a safe manner. Demonstration of a working knowledge or the provisions of this article shall constitute acceptable evidence of compliance with this requirement.
E. 
Companies, corporations, copartnerships and owner-operators required to have a permit shall maintain a record of all locations where welding or cutting operations are performed and have it available for inspection by the Chief of the Fire Department.
A. 
Approved equipment shall be used in welding and cutting.
B. 
The use of liquid acetylene or liquid acetylenic compounds is prohibited unless properly stabilized.
A. 
Before welding or cutting operations are begun in areas not designed or approved for the purposes, specific authorization shall be obtained from the owner of the premises or his duly authorized agent.
B. 
When welding or cutting operations are performed above, or within 35 feet of combustible construction or material exposed to the operation, or within 35 feet of floor, ceiling or wall openings so exposed:
(1) 
Such combustible construction or material shall be protected by noncombustible shields or covers from possible sparks, hot metal or oxide.
(2) 
Such floor, ceiling or wall openings shall be protected by noncombustible shields or covers.
(3) 
A fire watcher shall be provided to watch for fires, make use of portable fire extinguishers or fire hose and perform similar fire prevention and protection duties. The fire watcher shall remain on the job at least 30 minutes after the welding or cutting operations have been completed to insure that no fire exists. A signed inspection report attesting to that fact shall be filed and available for inspection by the Chief of the Fire Department.
C. 
One or more portable fire extinguishers of approved type and size shall be kept at the location where welding or cutting is to be done.
D. 
Welding or cutting shall not be done in or near rooms or locations where flammable gases, liquids or vapors, lint, dust or loose combustible stocks are present when sparks or hot metal from the welding or cutting operations may cause ignition or explosion of such materials.
E. 
Except as provided in Subsection F, welding or cutting shall not be performed on containers and equipment which contain or have contained flammable liquids, gases or solids until these containers and equipment have been thoroughly cleaned or inerted or purged.
F. 
"Hot tapping" may be permitted on tanks and pipe lines, provided such operations are performed by companies, corporations, copartnerships or owner-operators not required to have a permit under Subsection B.
G. 
Sprinkler protection shall not be shut off while welding or cutting work is being performed. When welding or cutting is done close to automatic sprinkler heads, sheet asbestos or damp cloth guards may be used to shield the individual heads but shall be removed when the work is completed.