No person shall cause, suffer, allow or permit visible smoke to be emitted into the outdoor air from combustion of fuel in any stationary indirect heat exchanger except as provided in § 105-7 of this chapter.
No person shall cause, suffer, allow or permit smoke, the shade or appearance of which is darker than No. 1 on the Ringelmann smoke chart, or greater than twenty-percent capacity, exclusive of water vapor, to be emitted into the outdoor air from the combustion of fuel in any stationary indirect heat exchanger having a rated hourly capacity of two hundred million (200,000,000) BTU or greater gross heat input and discharging through a stack or chimney having all internal cross-sectional dimensions of sixty (60) inches or greater.
The provisions of §§ 105-6 and 105-7 shall not apply to smoke which is visible for a period of not longer than three (3) minutes in any consecutive thirty-minute period.
The provisions of this Article shall not apply to direct heat exchangers or manufacturing processes or to any motor vehicle while operating on the public highways.
Any person responsible for the construction, installation, alteration or use of an indirect heat exchanger shall, when requested by the Director, provide the facilities and necessary equipment for determining the density or opacity of smoke being discharged into the open air.