A dosing tank shall be provided for a leaching chamber and leaching field system where the volume of waste to be disposed of is an excess of 2,000 gallons per day.
Dosing shall alternate when the total volume of waste to be disposed of exceeds 5,000 gallons per day. Alternating siphons and pumps shall discharge to separate disposal areas of equal size.
Dosing tanks shall have the capacity to discharge a volume adequate to cover the dosed leaching area to a depth of at least one inch in not over 15 minutes.
Dosing tanks shall be constructed of concrete or other material as approved by the Department of Environmental Quality Engineering and shall conform to § 223-60 of this chapter and shall be cast without joints and shall be watertight if installed below groundwater level.
Dosing tanks shall be constructed on a level, stable base that will not settle.
Dosing tanks shall be constructed in a manner that will permit venting through the building sewer or other suitable outlet.
The invert elevation of the inlet shall be at least one foot above maximum groundwater elevation, and the tank shall be waterproof and watertight.
To provide access and to facilitate repair or adjustment of the siphons or pumps, dosing tanks should be provided with manholes at least 24 inches in diameter, with metal frames and covers to grade over each pump or siphon.
Annual inspections are recommended to determine if the pumps or siphons are in working order.