Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Mount Pleasant, NY
Westchester County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Amended 10-13-1981]
All main or branch soil, waste and vent piping within the building shall be of service-weight cast iron, galvanized steel or wrought iron, brass or copper, except that no galvanized steel or wrought iron pipe shall be used for underground soil or waste pipes. Extra-heavy weight cast iron may be used in place of service-weight cast iron at the direction of the Town Plumbing Inspector or Superintendent of Buildings, where deemed necessary. Short branches on water closets may be of lead only.
The following table based on the rate of discharge from a lavatory as the unit shall be employed to determine fixture equivalents:
Type of Fixture
Fixture Units
1 lavatory or washbasin
1
1 kitchen sink
1 1/2
1 bathtub, with or without shower
2
1 laundry tray
3
1 combination fixture
3
1 urinal
3
1 shower bath
3
1 floor drain (where permitted)
3
1 water closet
6
1 slop sink
4
Every building in which plumbing fixtures are installed shall have a soil or waste stack or stacks extending full size (four inches minimum) through the roof. Soil and waste stacks shall be as direct as possible and free from sharp bends and turns. The required size of a soil or waste stack shall be determined from the distribution and totals of all fixture units connected to the stack in accordance with Table No. 2 given below and to which reference is hereby made, except that no water closet shall discharge into a stack less than three inches in diameter.
Table No. 2
Maximum Fixture Units on One Stack
With Sanitary T-Inlets
With All 45-Degree Y or Combination Y-and-1/8-Bend Inlets
Diameter
(inches)
In 1 Branch Interval*
On Any 1 Stack
In 1 Branch Interval*
On Any 1 Stack
Maximum Length Including Extension as Vent Stack
(feet)
1 1/2
2
8
4
12
65
2
9
16
15
36
85
3
24
48
45
72
212
4
144
256
240
384
300
5
324
680
540
1,020
390
NOTES:
* The term "branch interval" shall be interpreted to mean a vertical length of stack, not less than eight feet, within which a branch or branches are connected, and the total fixture units on all branches connected to a stack within eight feet length shall not exceed the maximum permitted by the table in one branch interval.
No fixture connection shall be made to a lead bend or branch of a water closet. No soil or waste vent above the highest installed fixture on the branch or main shall thereafter be used as a soil or waste pipe unless vents are carried above the highest fixtures.
No soil or waste stack shall be installed or permitted outside of a building unless adequate provision is made to protect it from frost.
All roof extensions of soil and waste stacks shall be run full size and be of four-inch minimum diameter, at least one foot above the roof, and when the roof is used for other, such extension shall be not less than six feet above the roof. Long increasers at least one foot below the roof shall be provided where change in size to roof extensions occur.
The roof terminal of any stack or vent, if within 12 feet of any window or air shaft, shall extend at least three feet above the same and be terminated as directed by the Inspector.
A. 
No soil, vent or waste pipe extension from any new or existing building shall be run or placed on an adjoining wall, but it shall be carried up inside its own roof area to a level above the highest adjoining roof.
B. 
In the event that a new building is built higher than an adjoining building, the owner of the new building shall not locate windows within 12 feet of any existing vent stack on the lower building unless the owner of such new building shall extend the soil, waste or vent pipe of the lower existing building above the roof level of such new building at his own expense. It shall be the duty of the owner of the lower existing building to give reasonable cooperation to the adjoining building owner in carrying out the above requirements.
Any vertical branch rising more than 10 feet or any lateral branch running more than 25 feet from the main soil line shall be continued full size to a point above the roof in the same manner as required for main soil pipes or may be returned to the main vent pipe full size.
Every fixture trap shall be individually protected against siphonage and back pressure and air circulation assured by means of an individual back vent to a soil or waste stack vent. No crown vents shall be installed.
No trap shall be placed more than two feet horizontal developed length from its vent connection, except that the distance between the vent and trap may be 15 feet or less on the waste from a surgical operating table, dental cuspidor or other approved similar fixture. The distance shall be measured along the central line of the waste or soil pipe from the vertical inlet of the trap to the vent opening. The vent opening from the soil or waste pipe, except for water closets and similar fixtures, shall not be below the dip of the trap.
All main vents or vent stacks shall connect full size at their base, at a forty-five-degree maximum angle, to the main soil or waste pipe at or below the lowest fixture branch, and shall extend undiminished in size above the roof or shall be reconnected with the main soil or waste vent at least three feet above the highest fixture branch.
The required size of the main vents or vent stacks shall be determined on the basis of the size of the soil or waste stack, the number of fixtures or fixture units connected to the soil or waste stack and the developed length of the main vent or vent stack in accordance with Table No. 3 given below and to which reference is hereby made.
Table No. 3
Maximum Length of Vents (in feet) for
Soil and Waste Stacks
Diameter of Vent (in inches)
Diameter of Soil or Waste Stack
(inches)
Number of Fixture Units
(up to)
1 1/2
2
2 1/2
3
4
5
1 1/2
8
60
2
18
50
90
2 1/2
36
45
75
105
3
12
34
120
180
212
3
18
18
70
180
212
3
24
12
50
130
212
3
36
8
35
93
212
3
48
7
32
80
212
3
72
6
25
65
212
4
24
25
110
200
300
340
4
48
16
65
115
300
340
4
96
12
45
84
300
340
4
144
9
36
72
300
340
4
192
8
30
64
282
340
4
264
7
20
56
245
340
4
384
5
18
47
206
340
5
72
40
65
250
390
5
144
30
47
180
390
5
288
20
32
124
390
5
432
16
24
94
320
5
720
10
16
70
225
No vents shall be less than 1 1/2 inches in diameter. For one-and-one-half-inch wastes, the vent shall be 1 1/2 inches, and in no case shall a branch or main vent have a diameter of less than 1/2 that of the soil or waste pipe served, and in no case shall the length of a branch vent of given diameter exceed the maximum length permitted for the main vent serving the main size soil or vent stack. Water-closet vents shall be two inches.
All vent and branch vent pipes shall be properly graded. Where vent pipes connect to a horizontal soil or waste pipe as in cases for closets, tubs and showers, the vent branch shall be taken off above the center line of the pipe, and the vent must rise vertically or at an angle of 45° to the vertical to a point six inches above the top of the fixture it is venting before offsetting horizontally or connecting to the branch, main waste or soil vent. For showers, the height of permissible offset shall be 18 inches above the top of the drain. Branch vents for water-closet traps shall be taken off not more than two feet from the crown of the trap.
No vent will be required on a backwater trap.