[HISTORY: Adopted by the Town Board of the Town of Ithaca 6-14-2021 by L.L. No. 5-2021. Amendments noted where applicable.]
144-101. 
Title, purpose and objectives.
144-101.1. 
Title. This Chapter 144 of the Code of the Town of Ithaca shall be known as the "Energy Code Supplement" (ECS).
144-101.2. 
Purpose. The purpose of this chapter is to promote the public health, safety, and general welfare by establishing a local energy code supplement for all new construction, certain additions, and major renovations, with requirements above and beyond the state energy code that will become more stringent over time.
144-101.3. 
Objectives. The objectives of this chapter are to: (1) deliver measurable, immediate, and long-lasting reductions in greenhouse gas (GHG) emissions from all new construction, certain additions, and major renovations; (2) advance best practices in the design of affordable buildings that deliver reduced GHG emissions; and (3) provide a rapid but orderly transition to buildings that do not use fossil fuels on-site for major building energy needs, such as space heating and hot water heating, by 2026. The requirements set forth give priority to electrification, renewable energy, and affordability. Requirements for reductions in GHG emissions go into effect in three steps: 2021, 2023, and 2026.
144-102. 
Findings.
144-102.1. 
Findings of fact. The Town of Ithaca Town Board finds that:
A. 
Climate change is causing an increase in extreme weather events, such as storms, flooding, and heat waves that threaten human life, healthy communities, and critical infrastructure in the Town, New York State, and across the world.
B. 
There is a clear emerging international consensus that to avoid the most severe impacts of a changing climate, global warming should be limited to 1.5° C.
C. 
GHG emissions related to human activity are the main cause of global warming. Buildings within the Town of Ithaca are the most significant contributor to local GHG emissions, responsible for more than half of all community GHG emissions.
D. 
The Town Board unanimously adopted the Town's Green New Deal on March 23, 2020, which sets forth a goal to achieve an equitable transition to carbon-neutrality community-wide by 2030.
E. 
New York State, through its Climate Leadership and Community Protection Act, has set ambitious goals to combat climate change through GHG reduction. State goals are in line with many of the objectives of the Energy Code Supplement, including reducing emissions in buildings, electrifying space heating, water heating, and cooking systems, increasing the use of renewable energy, and reducing the use of fossil fuels.
F. 
The combustion of fossil fuels in homes and other buildings decreases internal air quality and has adverse impacts on human health.
G. 
For new buildings, the most affordable and cost-effective time to reduce greenhouse gas emissions is during the design and construction phases of a project, rather than at a time of later retrofit.
144-201. 
144-201.1. 
Pursuant to § 11-109 of the New York State Energy Law, and subject to the provisions and requirements of that section, the Town of Ithaca has the power to promulgate a local energy conservation construction code that is more stringent than the Energy Conservation Construction Code of New York State (ECCCNYS).
144-201.2. 
This ECS provides requirements and standards that are in addition to, and shall supplement, the requirements and standards set forth in the ECCCNYS and in Chapter 125, Building Construction and Fire Prevention, of the Code of the Town of Ithaca. If a requirement of the ECS is less stringent than that of the ECCCNYS in effect at the time of application for a building permit, then the more stringent ECCCNYS requirement shall take precedence. The ECS shall be followed to the greatest extent possible while meeting any more stringent requirements of the ECCCNYS. The plans, specifications, and other materials required by the Code Enforcement Officer relating to the ECS-related components of the building, structure, and/or property shall be submitted to the Code Enforcement Officer in conjunction with an application for a building permit pursuant to said Chapter 125 and pursuant to Chapter 270, Zoning, of the Code of the Town of Ithaca.
[Amended 4-25-2022 by L.L. No. 8-2022]
144-201.3. 
The Town shall enforce this chapter in addition to the Town's enforcement of the ECCCNYS. Chapter 125, Building Construction and Fire Prevention, of the Code of the Town of Ithaca sets forth the method for administration and enforcement of the ECS and establishes powers, duties and responsibilities in connection therewith, including penalties and other remedies for violations of the ECS.
144-201.4. 
Except as specified in this chapter, this chapter shall not be used to require the removal, alteration or abandonment of, nor prevent the continued use and maintenance of, an existing building or building system lawfully in existence at the time of adoption of this chapter.
144-202. 
Applicability.
144-202.1. 
Applicability.
A. 
Beginning on the compliance date, the requirements of this Energy Code Supplement shall apply to the following construction:
1. 
All new construction, excluding additions and renovations that are not specified in this list.
2. 
All additions 500 square feet or larger to single-family dwellings or two-family dwellings.
3. 
All additions 1,000 square feet or larger to buildings other than single-family dwellings or two-family dwellings.
4. 
All major renovations, as defined in § 144-3.
B. 
Exceptions to 144-202.1, Applicability.
1. 
The requirements of the ECS shall not apply to construction that does not include directly heated space.
2. 
The requirements of the ECS shall not apply to agricultural buildings, including barns, sheds, poultry houses and other buildings and equipment on the premises that are used directly and solely for agricultural purposes.
3. 
The requirements of the ECS shall not apply to construction for which all necessary building permits have been issued prior to the compliance date.
4. 
The requirements of the ECS shall not apply to construction for which completed applications for all necessary building permits have been submitted prior to the compliance date, if such applications are diligently prosecuted to conclusion.
a. 
For the purposes of this subsection only, a building permit application shall be deemed "completed" if all other necessary approvals, including but not limited to site plan, subdivision, special approval, special permit, and variance have been received prior to the compliance date, and if the building permit application contains all required information, materials, and fees normally and reasonably required by the Code Enforcement Officer to commence their building permit review process.
b. 
A building permit application shall be deemed "diligently prosecuted to conclusion" if the applicant promptly responds to any inquiries and promptly supplies any additional information reasonably required by the Code Enforcement Officer, and the applicant otherwise cooperates so as to permit and enable the Code Enforcement Officer to adequately and completely review the application and render a decision on same within a reasonable period of time of its submission, and in any event within three months of its submission.
144-202.2. 
Compliance. Code compliance as applied to types of buildings:
A. 
Commercial buildings shall meet the provisions of § 144-4, Commercial building provisions.
B. 
Residential buildings shall meet the provisions of § 144-5, Residential building provisions.
C. 
Mixed-use buildings where more than 50% of the heated floor area is residential shall meet the requirements for residential buildings set forth in § 144-5. Mixed-use buildings where 50% or more of the heated floor area is commercial shall meet the requirements for commercial buildings set forth in § 144-4. In mixed-use buildings, the whole building shall comply with all applicable requirements; no portion is exempt from requirements.
D. 
Additions. The applicant shall demonstrate compliance for additions in either of the following two ways:
1. 
Independent of the existing building: All applicable requirements shall be met for the addition alone, without considering the existing building. If the addition is complying independent of the existing building, then all references to "building" in §§ 144-4, 144-5 and 144-6 shall refer to the addition.
2. 
Together with the existing building: All applicable requirements shall be met for the addition and the existing building together, as a whole. If the addition is complying together with the existing building, then all references to "building" in §§ 144-4, 144-5, and 144-6 shall refer to the addition and the existing building together.
E. 
In major renovations, the whole building, including space outside of the work area, shall comply with all applicable requirements.
144-301. 
General.
144-301.1. 
Terms defined in other codes. Where terms are not defined in this code and are defined in the Energy Conservation Construction Code of New York State, such terms shall have the meanings ascribed to them as in that code. Where terms are not defined in this code and are defined in a New York State code other than the Energy Conservation Construction Code, and the applicable code is specifically referenced in relation to the terms, such term shall have the meanings ascribed to them in relation to the referenced code.
144-302. 
General definitions. As used in this chapter, the following terms shall have the meanings indicated:
ACCREDITED PASSIVE HOUSE CERTIFIER
An organization accredited by Passive House Institute or Passive House Institute US as a Passive House Certifier. A list of Accredited Passive House Certifiers can be found at www.passivehouse.com and www.phius.org.
ADAPTIVE REUSE
The repurposing of a building for a new permitted use or change in occupancy type.
AGRICULTURAL BUILDING
A structure designed and constructed to house farm equipment, farm implements, poultry, livestock, hay, grain, or other horticultural products. This structure shall not be a place of human habitation or a place of employment where agricultural products are processed, treated, or packaged, nor shall it be a place used by the public.
ASHRAE 90.1
The publication entitled "ANSI/ASHRAE/IES Standard 90.1, Energy Standard for Buildings Except Low-Rise Residential Buildings," published by ASHRAE, the American Society of Heating, Refrigerating and Air-Conditioning Engineers. In several provisions, a specific printing of the standard is specified, for example, ASHRAE 90.1-2013.
BIOMASS
Organic material that is processed and burned to provide energy, particularly for space heating, through direct thermal energy. Biomass for space heating purposes includes cord wood, pellets, and chips.
BUILDING THERMAL ENVELOPE
The insulated exterior walls (above and below grade), floors, ceilings, roofs, and any other building element assemblies that enclose heated space or provide a boundary between heated space and unheated space.
COMMERCIAL BUILDING
See also "mixed-use building." Any building that is not included in the definition of "residential building."
COMMUNITY RENEWABLE ENERGY FACILITY
An off-site renewable energy system or facility that is qualified as a community energy facility under applicable New York State and local utility statutes and rules.
COMPLIANCE DATE
The 91st day after Ithaca Town Board adoption of the local law containing the ECS.
DESIGN PROFESSIONAL
A professional engineer (PE) or a registered architect (RA) licensed to practice in the State of New York.
DIRECTLY HEATED FLOOR AREA
The horizontal projection of the floors associated with the directly heated space.
DIRECTLY HEATED SPACE
An area or room that is enclosed within the building thermal envelope and is directly heated using fossil fuel, electricity, or biomass as the energy source. Spaces are indirectly heated (and not directly heated) where they connect through openings with heated spaces, where they are separated from heated spaces by uninsulated walls, floors or ceilings, or where they contain uninsulated ducts, piping or other sources of heating using fossil fuel, electricity, or biomass.
DORMITORY
A multiple dwelling which provides sleeping accommodations and domestic facilities and services for a group of college, university or secondary school students.
EASY PATH
Also known as "prescriptive compliance path." One possible compliance path for this code, under which a certain number of points must be earned.
ECS
The Energy Code Supplement, which is Chapter 144 of the Ithaca Town Code.
ELECTRIC VEHICLE CHARGING STATION [ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE), EV CHARGING STATION, CHARGING POINT]
The element in an infrastructure that supplies electric energy for the recharging of plug-in electric vehicles.
ELECTRIC VEHICLE PARKING SPACE (EV PARKING SPACE or EV SPACE)
A parking space that includes access to a dedicated electric vehicle charging port and supporting electrical infrastructure, collectively referred to as "electric vehicle supply equipment (EVSE)."
ENERGY PROFESSIONAL
A professional holding a current accreditation in the energy field from BPI, AEE, ASHRAE, RESNET, or other body approved by the Director of Code Enforcement or their designee.
ENERGY USE
All references to energy use in this chapter refer to site energy use, which is the heat and electricity consumed by a building as reflected at the meter and/or in the utility bills.
FLOOR AREA
The total floor surface of all levels as measured from the inside perimeter of the exterior or separation walls, exclusive of vent shafts, courts, and unconditioned spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
FOSSIL FUELS
An energy source formed in the Earth's crust from decayed organic material. The common fossil fuels are petroleum, coal, and natural gas. For purposes of this ECS, fossil fuels shall also include common extracts, derivatives, and products of fossil fuels, including but not limited to propane, kerosene, and gasoline.
GREENHOUSE GAS (GHG)
Any of several gases, including carbon dioxide (CO2), methane (CH4), nitrous oxide (N2O), and fluorinated gases, that trap heat in the atmosphere.
HEAT PUMP, AIR SOURCE
Air source heat pumps extract heat from the ambient air. Water loop boiler/tower heat pumps are not considered air source heat pumps.
HEAT PUMP, GROUND SOURCE
Ground source heat pumps, also known as "geothermal heat pumps," are heat pumps that extract heat from the earth, groundwater, a body of water, or similar sources. Water loop boiler/tower heat pumps are not considered ground source heat pumps.
HEATED FLOOR AREA
The horizontal projection of the floors associated with the heated space.
HEATED SPACE
An area or room that is enclosed within the building thermal envelope and is directly or indirectly heated using fossil fuel, electricity, or biomass as the energy source. Spaces are indirectly heated where they connect through openings with heated spaces, where they are separated from heated spaces by uninsulated walls, floors or ceilings, or where they contain uninsulated ducts, piping or other sources of heating using fossil fuel, electricity, or biomass.
HEATING PLANT
One or more appliances that serve as the primary source of heating for the building or space, whether located in the building or not.
[Added 1-9-2023 by L.L. No. 1-2023]
HOTEL
A building containing rooms designed and originally planned to be rented or hired out for living or sleeping accommodations for transient occupancy.
LEADERSHIP IN ENERGY AND ENVIRONMENTAL DESIGN (LEED)
A green building rating/certification system, developed by the U.S. Green Building Council (USGBC) and administered by Green Business Certification, Inc. (GBCI).
LIGHTING POWER ALLOWANCE (LPA)
Maximum allowed lighting power density. Lighting power allowances for use in prescriptive compliance path/easy path point AI4 right lighting are given in Table 144-AA1 (Appendix A).
LIGHTING POWER DENSITY (LPD)
Lighting power consumption per square foot of floor area, measured in watts per square foot.
LIVABLE SPACE
A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered livable spaces.
MAJOR RENOVATION
Any construction or renovation to an existing structure, building, separated occupancy, tenant space, or unit under consideration, other than a repair or addition, that meets these two requirements:
[Amended 1-9-2023 by L.L. No. 1-2023]
A. 
The work area exceeds 75% of the floor area, and
B. 
The proposed work involves two or more of the following:
A. 
Replacement or new installation of 50% or more of the rated capacity of the heating plant that serves the floor area. Changes to air distribution, exhaust, or air conditioning systems are not considered renovations to the heating plant.
B. 
Construction that involves disassembly or uncovering of greater than 50% of the area of the above-grade portion(s) of the building thermal envelope that serves the floor area.
C. 
Changes to lighting, including but not limited to new installation, replacement, relocation, or removal, of lamps, lighting, or other illumination fixtures throughout 50% or more of the floor area. Floor area that is not currently lit, and is not proposed to be lit, shall not count toward the 50% calculation.
MIXED-USE BUILDING
See also "residential building" and "commercial building." Any building in which a portion of the use is residential, and a portion of the use is commercial. For purposes of this Supplement, any mixed-use building in which more than 50% of the heated floor area is for residential use shall be classified as a residential building. Any other mixed-use building shall be classified as a commercial building. When determining the size of residential spaces, include all dwelling units, as well as all shared amenity spaces (common areas) that serve only the dwelling units, including but not limited to shared lobbies, hallways, stairways, gyms and laundry areas.
NATIONAL GREEN BUILDING STANDARD (NGBS or ICC/ASHRAE 700)
A green building rating/certification system approved by the American National Standards Institute (ANSI), under which points can be earned for energy efficiency; water efficiency; resource efficiency; lot development; operation and maintenance; and indoor environmental quality.
OCCUPIABLE SPACE
A room or enclosed space designed for human occupancy in which individuals congregate for amusement, educational or similar purposes or in which occupants are engaged at labor, and which is equipped with means of egress and light and ventilation facilities meeting the requirements of the Building Code of New York State.
ON-SITE RENEWABLE ENERGY SYSTEM
A renewable energy system located on any of the following:
A. 
The building.
B. 
The property upon which the building is located.
C. 
A property that shares a boundary with and is under the same ownership or control as the property on which the building is located.
D. 
A property that is under the same ownership or control as the property on which the building is located and is separated only by a public right-of-way from the property on which the building is located.
PASSIVE HOUSE CERTIFICATION
A certification program for buildings, including commercial buildings, constructed to high-performance "passive building standards."
PERFORMANCE-BASED COMPLIANCE PATH
Also known as "whole building path." A compliance path for the Energy Code Supplement, under which a building must comply with specified standards of one of several certification programs and/or use modeling to show compliance.
PLUG LOAD
A device that is powered by means of an electrical plug and matching socket or receptacle. This excludes devices that are accounted for as part of major building end uses such as HVAC, lighting systems, and water heating.
PRESCRIPTIVE COMPLIANCE PATH
Also known as "easy path." A compliance path for the Energy Code Supplement, under which a certain number of points must be earned for the building to show compliance.
PROCESS ENERGY (PROCESS LOAD)
Energy consumed in support of a manufacturing, industrial, commercial, research, or educational process other than space heating, ventilating, air conditioning, service water heating, plug loads, lighting, and appliances. Examples of process loads include commercial cooking, commercial refrigeration, energy used by machinery in manufacturing, energy used by medical equipment, emergency generators, and energy used for agricultural needs. Examples of loads that are not considered process loads include electricity required for exhaust fans, heating and cooling for ventilation makeup air for any purpose, including kitchen and lab hoods, and energy used for clothes drying.
REC
See "Renewable Energy Credit (REC)."
RENEWABLE ENERGY CREDIT (REC)
A tradable instrument that represents the environmental attributes of one megawatt-hour of renewable electricity generation and is transacted separately from the electricity generated by the renewable energy source. Also known as "REC," "renewable energy certificate," "energy attribute" and "energy attribute certificate."
RESIDENTIAL BUILDING
See also "mixed-use building." Any building covered by the Residential Code of New York State, as well as any building that is classified in accordance with Chapter 3 of the Building Code of New York State in Group R-2, R-3, or R-4, including any residential building that has more than three stories above grade plane.
RESTAURANT
An establishment that prepares and serves meals or drinks to customers on site or delivers them off site.
SERVICE WATER HEATING
Also known as "domestic hot water heating." Supply of hot water for purposes other than comfort heating.
SPANDREL PANEL
The area of a curtain wall or screen located between vision areas of windows, which conceals structural building components such as columns, floors, HVAC equipment, and plumbing.
SPLIT SYSTEM
A heat pump or air conditioner in which one component is located outdoors and the other component(s) indoors, and which components are connected by refrigerant piping.
TOWN
The Town of Ithaca.
WHOLE BUILDING PATH
Also known as "performance-based compliance path." One possible compliance path for the Energy Code Supplement, under which a building must comply with specified standards of one of several certification programs and/or use modeling to show compliance.
WINDOW-TO-WALL RATIO
The total area of exterior glazing (windows) in a building divided by the total area of the above-grade walls, expressed as a percentage.
WORK AREA
That portion or portions of a building consisting of all reconfigured spaces as indicated on the construction documents. Work area excludes other portions of the building where incidental work entailed by the intended work must be performed, and portions of the building where work not initially intended by the owner is specifically required by the provisions of the New York State Existing Building Code.
144-C401. 
General.
144-C401.1. 
Scope. The provisions in this subsection are applicable to commercial buildings and mixed-use buildings where 50% or more of the heated floor area is commercial, their building sites, and associated systems and equipment.
144-C401.2. 
Application. Commercial buildings shall comply with one of the following:
A. 
Prescriptive compliance path/easy path: the requirements of Subsection 144-C402.
1. 
As part of the application packet, the applicant shall submit a checklist and worksheet which the Town shall use as the basis for verifying and showing compliance with the ECS.
B. 
Performance-based compliance path/whole building path: the requirements of Subsection 144-C403.
1. 
As part of the application packet, the applicant shall submit the relevant documentation, which is detailed in Subsection 144-C403, which the Town shall use as the basis for verifying and showing compliance with the ECS.
144-C402. 
Prescriptive compliance path/easy path.
144-C402.1. 
General. Until January 1, 2023, to meet the requirements of this Subsection 144-C402, a building must achieve a minimum of six of the points described in this subsection. A summary table is provided in 144-C402.6. See Subsection 144-C404 for enhanced requirements beginning on and after January 1, 2023, and additional enhanced requirements beginning on and after January 1, 2026.
144-C402.2. 
Efficient Electrification (EE).
144-C402.2.1. 
EE1 Heat pumps for space heating. Two points shall be earned for using air source heat pumps or three points shall be earned for using ground source heat pumps, as described in 144-C402.2.1.
144-C402.2.1.1. 
Only air source heat pumps or ground source heat pumps shall be used for all space-heating needs, with exceptions for electric resistance heating as described in 144-402.2.1.4. A heating system that uses only ground source heat pumps (and electric resistance heating as allowed) shall earn three points. A heating system that uses only air source heat pumps or uses a combination of air source and ground source heat pumps (and electric resistance heating as allowed) shall earn two points.
144-C402.2.1.2. 
Fossil fuels shall not be used for any space heating, space cooling or ventilation systems in the building, including backup heating systems. Water loop boiler/tower heat pumps that use fossil fuels shall not earn credit under this point.
144-C402.2.1.3. 
Except as stated in the second sentence of this provision 144-C402.2.1.3, air source heat pumps shall be listed in the Northeast Energy Efficiency Partnerships (NEEP) Cold Climate Air Source Heat Pump Product List, for the product types and sizes covered. For any air source heat pump not covered by NEEP, the heat pump shall use a variable speed compressor(s) and the heat pump compressor(s) shall operate in temperatures below 0° F. (The compressor may be supplemented by electric resistance heat in accordance with the exceptions described in 144-402.2.1.4.).
144-C402.2.1.4. 
To allow flexibility, electric resistance heat is allowed for a portion of space heating needs. Applicants shall submit documentation showing that at least one of the following conditions is met:
A. 
Stand-alone electric resistance heating (not associated with heat pumps) is used to heat 10% or less of the building's heated floor area.
B. 
Stand-alone electric resistance heating (not associated with heat pumps) is used to meet 10% or less of the building's projected annual space heating load.
144-C402.2.2. 
EE2 Heat pumps for service water heating. One point shall be earned for meeting the requirements of 144-C402.2.2. Restrictions: This point may only be earned when all commercial portions of the building meet one of the following criteria:
A.
Are classified as hotel, restaurant, or in-patient health care.
B.
Collectively use more than 40 gallons of water per square foot on an annual basis, as cited in the latest Commercial Buildings Energy Consumption Survey (CBECS) or comparable source.
144-C402.2.2.1. 
All service water heating systems shall use heat pumps and shall not use fossil fuels. All heat pump water heaters shall be set on heat pump-only mode.
Exception: In commercial kitchens, booster heat units for dishwashing must be electric, but shall be exempt from the heat pump requirement. Units used to pre-heat water for dishwashing shall use heat pumps.
144-C402.2.3. 
EE3 Commercial cooking electrification. Three points shall be earned for meeting the requirements of 144-C402.2.3. Restrictions:
A.
Points may only be earned for buildings or portions thereof that are restaurants or other food service establishments that use a commercial kitchen hood; and
B.
Points may only be earned if the building does not use fossil fuels, except for process energy. For this point, process energy shall exclude commercial cooking.
144-C402.2.3.1. 
All cooking equipment, including but not limited to ranges, griddles, and fryers, shall be electric.
144-C402.3. 
Affordability Improvements (AI).
144-C402.3.1. 
AI1 Smaller building/room size. One or two points may be earned according to the requirements below. Restrictions:
A.
This point may only be earned for hotels.
B.
For additions, this point may only be earned if the applicant demonstrates ECS compliance for the addition together with the existing building. This point may not be earned when considering the addition independent of the existing building.
144-C402.3.1.1. 
For hotels, the average directly heated floor area of all guest rooms in the building shall not be greater than the maximum average guest room size listed in Table 144-C402.3.1.1. Individual guest rooms may exceed the maximum size.
Table 144-C402.3.1.1
Area Requirements for Hotels and Motels
Maximum average guest room size allowed to receive 1 point (SF)
280
Maximum average guest room size allowed to receive 2 points (SF)
230
144-C402.3.2. 
AI2 Heating system in heated space. One point may be earned according to the requirements below.
144-C402.3.2.1. 
A. 
All components of heating systems shall be installed inside space that meets all the following criteria:
1. 
Inside the building thermal envelope.
2. 
Directly heated space.
3. 
Livable space, occupiable space or contiguous to livable space or occupiable space.
4. 
On a building level where at least 50% of the floor area is directly heated floor area.
B. 
For purposes of this subsection, "heating system" includes all parts of the system except for exhaust components and dedicated air intake components, including but not limited to mechanical equipment and the distribution network. Examples of spaces that are not allowed for heating system installation include, but are not limited to: unheated or unfinished basements and attics, crawl spaces, outdoors, roofs, and exterior wall cavities. Rooftop systems, window-mounted systems, and "through-the wall" equipment, such as packaged terminal equipment, shall not be used.
C. 
Exceptions:
1. 
Outdoor units of split system heat pumps may be located outdoors.
2. 
There are no limitations on the location of refrigerant piping.
144-C402.3.3. 
AI3 Efficient building shape. One point may be earned according to the requirements below.
144-C402.3.3.1. 
The exterior surface area divided by the directly heated floor area shall be less than the maximum value provided in Table 144-C402.3.3.1.
144-C402.3.3.2. 
The exterior surface area shall be measured along the above-grade portion(s) of the building thermal envelope, including but not limited to walls, roofs/ceilings (depending on the location of insulation), and exposed floors (such as those below a cantilever). The area of windows, doors, and skylights shall be included as part of the exterior surface area. The areas of the building thermal envelope between directly heated spaces and indirectly heated spaces or unheated spaces, such as the wall between a heated building and an attached unheated garage, shall be included as part of the exterior surface area.
144-C402.3.3.3. 
For additions, the area of the building thermal envelope between directly heated space in the addition and directly heated space in the original building (including shared walls and, if the addition is above the original building, floors/ceilings) shall not be counted as part of the exterior surface area.
Table 144-C402.3.3.1
Directly Heated Floor Area
(Square Feet)
Maximum Value of Exterior Surface Area (Square Feet) Divided by Directly Heated Floor Area
(Square Feet)
Directly Heated Floor Area
(Square Feet)
Maximum Value of Exterior Surface Area (Square Feet) Divided by Directly Heated Floor Area
(Square Feet)
199 or less
4.69
3,000 - 3,999
1.60
200 - 299
3.88
4,000 - 4,999
1.48
300 - 399
3.45
5,000 - 5,999
1.39
400 - 499
3.17
6,000 - 6,999
1.31
500 - 599
2.98
7,000 - 7,999
1.25
600 - 699
2.83
8,000 - 8,999
1.19
700 - 799
2.71
9,000 - 9,999
1.15
800 - 899
2.68
10,000 - 14,999
1.05
900 - 999
2.57
15,000 - 19,999
0.94
1,000 - 1,099
2.47
20,000 - 29,999
0.84
1,100 - 1,199
2.38
30,000 - 39,999
0.75
1,200 - 1,299
2.31
40,000 - 49,999
0.68
1,300 - 1,399
2.24
50,000 - 59,999
0.64
1,400 - 1,499
2.18
60,000 - 69,999
0.61
1,500 - 1,599
2.13
70,000 - 79,999
0.58
1,600 - 1,699
2.08
80,000 - 89,999
0.55
1,700 - 1,799
2.04
90,000 - 99,999
0.53
1,800 - 1,899
2.00
100,000 - 199,999
0.46
1,900 - 1,999
1.96
200,000 - 299,999
0.39
2,000 - 2,499
1.86
300,000 - 399,999
0.35
2,500 - 2,999
1.74
400,000 or more
0.33
144-C402.3.4. 
AI4 Right lighting. One point may be earned according to the requirements below.
144-C402.3.4.1. 
Mixed-use buildings. For mixed-use buildings classified as "commercial," the entire commercial portion and all common areas serving the residential portion (all areas outside of dwelling units; e.g., hallways, lobbies) shall comply with the requirements in this subsection. Lighting inside the dwelling units does not need to comply with the requirements in this subsection.
144-C402.3.4.2. 
Lighting power allowance. The total connected interior lighting power shall not be greater than the interior lighting power allowance. The total connected interior lighting power shall be calculated using the method described in the Energy Conservation Construction Code of NYS. (Informative Note: The method can be found in the 2020 ECCCNYS in Section C405.3.1, Total Connected Interior Lighting Power.) The total interior lighting power allowance, in watts, shall be determined according to Table 144-AA1 (Appendix A), for all areas of the building covered in this permit. The lighting power allowance shall be determined by multiplying the floor area of each space times the lighting power density (LPD) value for the space type in Table 144-AA1 that most closely represents the proposed use of the space, and then summing the lighting power allowances for all spaces to calculate the total interior lighting power allowance. Trade-offs among spaces are permitted. Construction documents shall include a table of space-by-space as-designed lighting power densities along with the lighting power allowances from Table 144-AA1.
144-C402.3.4.3. 
Additional interior lighting power. An increase in the interior lighting power allowance is permitted for specific lighting functions. Additional power shall be permitted only where the specified lighting is installed and automatically controlled separately from the general lighting, to be turned off during non-business hours. This additional power shall be used only for the specified luminaires and shall not be used for any other purpose. An increase in the interior lighting power allowance is permitted in the following cases:
A. 
For lighting equipment to be installed in sales areas specifically to highlight merchandise, the additional lighting power shall be determined in accordance with Equation 144-4-1.
Equation 144-4-1: Additional interior lighting power allowance = 250 watts + (Retail Area 1 * 0.3 W/ft2) + (Retail Area 2 * 0.3 W/ft2) + (Retail Area 3 * 0.7 W/ft2) + (Retail Area 4 * 1.3 W/ft2)
Where:
Retail Area 1 = The floor area for all products not listed in Retail Area 2, 3 or 4.
Retail Area 2 = The floor area used for the sale of vehicles, sporting goods, and small electronics.
Retail Area 3 = The floor area used for the sale of furniture, clothing, cosmetics, and artwork.
Retail Area 4 = The floor area used for the sale of jewelry, crystal, and china.
Exception: Other merchandise categories are permitted to be included in Retail Areas 2 through 4, provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the Code Enforcement Officer.
B. 
For spaces in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative appearance or for highlighting art or exhibits, provided that the additional lighting power shall be not more than 0.5 w/ft2 of such spaces.
144-C402.3.4.4. 
Lighting controls.
Except where lighting is required to stay on by New York State or local code, motion sensors are required for interior lighting in the following space types: office, conference room, kitchenette, corridor, stairwell, restroom, lobby. Short off-delay (one minute or less) is required for motion sensors. Manual control that allows lights to be kept off shall be provided. Except where lighting is required to stay on by New York State or local code, all exterior lighting shall be controlled by motion sensors, as well as photocells that ensure lighting stays off during daylight hours.
Exception: Lighting for signs is exempt from the requirements of 144-C402.3.4.4.
144-C402.3.4.5. 
Other lighting standards. All exterior lighting shall comply with the Town of Ithaca Outdoor Lighting Law, Town Code Chapter 173.
144-C402.3.4.6. 
Commissioning.
A. 
Commissioning of lighting and lighting controls is required. A commissioning plan shall be developed by a design professional or an energy professional or approved agency (as defined in the state energy code) and shall include the following items:
1. 
A narrative description of the activities that will be accomplished during each phase of commissioning, including the personnel intended to accomplish each of the activities.
2. 
A listing of specific lighting and controls to be tested and a description of the tests to be performed.
3. 
Functions to be tested, including, but not limited to, lighting power density (to show compliance with lighting power allowance requirements) and control settings.
4. 
Conditions under which the tests will be performed.
5. 
Measurable criteria for performance.
B. 
The design professional or energy professional shall execute the commissioning plan. A commissioning report, consistent with the commissioning plan, shall be submitted prior to the certificate of occupancy being issued.
144-C402.3.5. 
AI5 Modest window-to-wall ratio. One point may be earned according to the requirements below.
144-C402.3.5.1. 
The vertical fenestration area, not including opaque doors and opaque spandrel panels, shall be not greater than 20% of the gross above-grade wall area.
144-C402.3.5.2. 
For additions, the area of above-grade walls that were part of the building thermal envelope of the original building but are not part of the building thermal envelope of the new building shall be counted towards the above-grade wall area of the addition.
144-C402.4. 
Renewable Energy (RE).
144-C402.4.1. 
RE1 Renewable energy systems. Up to three points may be earned according to the requirements below.
144-C402.4.1.1. 
Points available. On-site and off-site renewable energy systems that meet the requirements of this subsection shall earn up to three points based on their annual electrical or thermal energy production. Multiple renewable energy systems may be used to earn points, but no more than three total points may be earned for any combination of renewable energy systems.
144-C402.4.1.2. 
Determining the number of points earned. The number of points earned shall be determined according to the steps below. The applicant shall submit documentation of all related assumptions and calculations.
Step 1: Calculate Renewable Energy Production
The Renewable Energy Production (REP) is the projected annual energy production of the renewable energy system, expressed in kilowatt-hours per year (kWh/yr). For thermal systems, the conversion 1 kWh = 3.412 kBtu shall be used.
Step 2: Calculate the Number of Points Earned The number of points earned for a renewable energy system is based on the directly heated floor area of the building it serves. Points shall be earned based on a weighted average related to residential and commercial floor area, as described in Equation 144-4-2. For purposes of this 144-C402.4.1, residential space shall include dwelling units and common areas that serve only dwelling units.
Equation 144-4-2: Minimum Renewable Energy Production needed to earn each point =
(1.2 kWh/ft2 x RA) + (2.4 kWh/ft2 x CA)
CA = Directly heated floor area of Commercial space (ft2)
RA = Directly heated floor area of Residential space (ft2)
Note: For buildings that have no residential space, set RA equal to zero.
Example Calculation - For Informational Purposes Only
Assumptions: Mixed-use building with 2,000 ft2 of residential directly heated floor area and 5,000 ft2 of commercial directly heated floor area. A 25 kW solar array is being used.
Step 1: Using the PVWatts Calculator, it is projected that the 25 kW solar array will produce 30,000 kWh/year.
Renewable Energy Production is 30,000 kWh/year.
Step 2: Using Equation 144-4-2:
Minimum REP needed for each point = (1.2 kWh/ft2 x RA) + (2.4 kWh/ft2 x CA)
Minimum REP needed for each point = (1.2 kWh/ft2 x 2,000 ft2) + (2.4 kWh/ft2 x 5,000 ft2)
Minimum REP needed for each point = 2,400 kWh + 12,000 kWh
Minimum REP needed for each point = 14,400 kWh
Using the assumptions for this building and renewable energy system, two points may be earned.
144-C402.4.1.3. 
Energy sources.
A. 
Renewable energy systems shall produce electricity from solar, wind, or hydropower resources, or produce thermal energy from solar, geothermal, or hydrothermal resources. Thermal energy absorbed from or rejected to outdoor air/ground/water and used in conjunction with heat pumps does not count as renewable energy for the purposes of this subsection. Hydropower shall be from new generation capacity on a non-impoundment or new generation capacity on an existing impoundment. Hydropower shall meet one of the following conditions:
1. 
The hydropower facility complies with the Low Impact Hydropower Certification Handbook and is certified by a nationally recognized accreditation organization.
2. 
The hydropower facility complies with UL 2854 and is certified by an organization that has the standard in its ISO 17065 scope of accreditation.
3. 
The hydropower facility consists of a turbine in a pipeline or a turbine in an irrigation canal.
B. 
For facilities falling under condition A(1) or A(2), only output generated during the period of certification is eligible for RECs sale in accordance with the provisions of this subsection. Renewables from new impoundments of water are not eligible.
144-C402.4.1.4. 
Qualifying renewable energy systems. Renewable energy systems producing electricity or thermal energy that is delivered to or credited to the building to comply with 144-C402.4.1 shall meet the following requirements:
A. 
Renewable energy systems shall satisfy one of the following criteria:
1. 
On-site renewable energy system.
a. 
Self-generation.
b. 
Purchase contract, such as a power purchase agreement.
2. 
Off-site renewable energy system.
a. 
Self-generation (an off-site renewable energy system owned by the building owner).
b. 
Community renewable energy facility.
c. 
Purchase contract, such as a power purchase agreement.
B. 
The renewable energy system shall be located in New York Independent System Operator (NYISO) territory and shall be located where the energy can be delivered to the building site by any of the following:
1. 
Direct connection to the renewable energy system.
2. 
The local utility or distribution entity.
3. 
An interconnected electrical network where energy delivery capacity between the generator and the building site is available. (Informative Note: Examples of interconnected electrical networks include regional power pools and regions served by independent system operators or regional transmission organizations.)
C. 
The renewable energy system must have commenced operation on or after January 1, 2015, and before the date the certificate of occupancy for the building is issued.
Exception to 144-C402.4.1.4(C)
If the building owner can provide evidence that, for the duration of the planning process, it has made a good faith effort to have the renewable energy system constructed and operational by the time of certificate of occupancy, and due to circumstances out of the control of and not otherwise due to any negligence or willful misconduct on behalf of the building owner, the renewable energy system is not constructed or is not operational, then the building owner shall be allowed up to one year after the certificate of occupancy is issued to meet 144-C402.4.1.4(C).
D. 
Where the renewable energy system ceases operation, or the owner cannot legally claim the associated energy or RECs for any reason, the building owner shall produce or procure alternative qualifying renewable energy in an amount equal to or greater than the amount needed to earn the same number of points under the requirements of 144-C402.4.1.2.
144-C402.4.1.5. 
Reporting and documentation.
A. 
The building owner shall submit documentation of renewable energy system ownership or renewable energy procurement, which includes subscription to a community solar project. Records on power and thermal energy produced or purchased by the building owner from the renewable energy producer shall be retained by the building owner on behalf of the entity demonstrating financial or operational control over the building seeking compliance to this standard and submitted to the Code Enforcement Officer on an annual basis for no less than 15 years. Any period of noncompliance shall not count toward fulfillment of the fifteen-year requirement.
B. 
For systems generating electricity, documentation shall be provided to the Code Enforcement Officer that indicates an exclusive chain of custody and ownership of the RECs from the renewable energy system to the building owner, on an annual basis for no less than 15 years. RECs supplied from the renewable energy system shall be conveyed to and retired on behalf of the entity who has financial or operational control over the building's electricity consumption. The annual generation vintage date of delivered RECs shall be allocated to the same twelve-month reporting year, up to six months prior, or up to three months after the calendar year in which the electricity is used in the building. Any period of noncompliance shall not count toward fulfillment of the fifteen-year requirement. Exceptions to 144-C402.4.1.5(B):
1. 
If the total capacity of all renewable energy systems being used to earn points under 144-C402.4.1 is less than 25 kW, the requirements of 144-C402.4.1.5(B) shall be waived.
2. 
Where the building owner cannot provide documentation on the chain of custody or ownership of the RECs from the renewable energy system, the building owner shall provide documentation to the Code Enforcement Officer of an alternate supply contract for replacement RECs from an alternate renewable energy source. The quantity of RECs contracted for shall be equal to or greater than the amount needed to earn the desired number of points under the requirements of 144-C402.4.1.2. These RECs shall comply with the Green-e® Renewable Energy Standard for Canada and the United States (latest edition) and shall be conveyed to and retired on behalf of the entity who has financial or operational control over the building's electricity consumption.
C. 
Electricity, thermal energy and RECs from renewable energy systems may not be counted more than once for purposes of demonstrating compliance with this 144-C402.4.1. The reporting and documentation required in 144-C402.4.1.4 shall clearly state how the energy and RECs are allocated to specific buildings. The Town may request additional documentation to provide reasonable proof of ownership/procurement, and fulfillment of RECS and allocation requirements.
D. 
In the case of full or partial transfer of ownership of the building, the following must be provided: proof of transfer of ownership; a signed statement from the new owner stating they understand the requirements of this 144-C402.4.1 and the duty to fulfill them; and contact information for the person(s) responsible for submitting annual reporting.
144-C402.4.2. 
RE2 Biomass space heating. Three points may be earned according to the requirements below.
144-C402.4.2.1. 
Only biomass systems shall be used for all space-heating needs, with exceptions for electric resistance heating as described in 144-C402.4.2.4.
144-C402.4.2.2. 
Fossil fuels shall not be used for any space heating, space cooling or ventilation systems in the building, including backup heating systems.
144-C402.4.2.3. 
All biomass equipment must comply with the NYSERDA (New York State Energy Research and Development Authority) Renewable Heat NY program guidelines, available at www.nyserda.ny.gov/All-Programs/Programs/Renewable-Heat-NY.
144-C402.4.2.4. 
To allow flexibility, electric resistance heat is allowed for a portion of space heating needs. Applicants shall submit documentation showing that at least one of the following conditions is met:
A. 
Stand-alone electric resistance heating is used to heat 10% or less of the building's heated floor area.
B. 
Stand-alone electric resistance heating is used to meet 10% or less of the building's projected annual space heating load.
144-C402.5. 
Other Points (OP).
144-C402.5.1. 
OP1 Development density. One point may be earned according to the requirements below. Restrictions: A maximum of three points total may be earned using up to two (maximum) of the following: OP1 Development Density, OP2 Walkability, and OP3 Electric Vehicle Parking Spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
144-C402.5.1.1. 
One point shall be earned if (DU + CA) > (7 x Acreage), where:
DU = the number of all residential dwelling units on the entire parcel occupied by the building.
CA = the floor area of all commercial space, measured in units of 1,000 square feet, on the entire parcel occupied by the building.
Acreage = the land area, measured in acres, of the entire parcel occupied by the building.
144-C402.5.1.2. 
DU shall include all dwelling units on the parcel occupied by the building, including those in existing buildings. CA shall include all commercial space on the parcel occupied by the building, including that in existing buildings. CA shall not include common areas serving only dwelling units or other residential space. Acreage shall include all land area on the parcel occupied by the building.
144-C402.5.2. 
OP2 Walkability. One point may be earned according to the requirements below. Restrictions: A maximum of three points total may be earned for two (maximum) of the following: OP1 Development Density, OP2 Walkability, and OP3 Electric Vehicle Parking Spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
144-C402.5.2.1. 
This point shall be earned when either of the following two conditions is met, in addition to the other requirements in this 144-C402.5.2.
A. 
The building is within one quarter (0.25) mile of at least five of the Neighborhood Amenity Types listed in Table 144-C402.5.2.1.
1. 
No single Amenity Type shall be counted more than twice, even when more than two examples of the Amenity Type exist. For example, a building on Aurora Street's "Restaurant Row" could count two restaurants maximum.
2. 
At least two Amenity Categories shall be represented.
3. 
The one-quarter-mile measurement(s) may be taken from any part(s) of the building.
B. 
The building is within a Town development priority area for which a regulating plan has been developed and adopted.
144-C402.5.2.2. 
For all buildings, at the time of project completion, sidewalks, walkways and/or trails must be present on the property or within 75 feet of the property, and connect to an existing network of pedestrian infrastructure.
Table 144-C402.5.2.1
Neighborhood Amenity Types and Categories
Amenity Category
Amenity Type
Food retail
Supermarket
Grocery with produce section
Community-serving retail
Convenience store
Farmers' market
Hardware store
Pharmacy
Other retail
Services
Bank
Family entertainment venue (e.g., theater, sports)
Gym, health club, exercise studio
Hair care
Laundry, dry cleaner
Restaurant, cafe, diner (excluding those with only drive-through service)
Civic and community facilities
Adult or senior care (licensed)
Child care (licensed)
Community or recreation center
Cultural arts facility (museum, performing arts)
Education facility (e.g., K-12 school, university, adult education center, vocational school, community college)
Government office that serves public onsite
Medical facility that treats patients
Place of worship
Post office
Public library
Public park
Social services center
144-C402.5.3. 
OP3 Electric vehicle parking spaces. Up to two points may be earned for installing electric vehicle parking space(s) and related infrastructure that meet the requirements of this subsection. Restrictions: A maximum of three points total may be earned using up to two (maximum) of the following: OP1 Development Density, OP2 Walkability, and OP3 Electric Vehicle Parking Spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
144-C402.5.3.1. 
Required number of EV parking spaces. The number of required EV parking spaces shall be determined using Table 144-C402.5.3.1(1), based on the number of residential dwelling units (DU) and the area of commercial space (CA).
Energy Code Supplement (ECS) Adopted 2021-06-14
DU = the number of residential dwelling units in the building.
CA = the area of all commercial space, measured in units of 1,000 square feet, in the building. CA shall not include common areas serving only dwelling units or other portions of residential space.
When determining the total number of required spaces in mixed-use buildings, EV space requirements for residential dwelling units and for commercial space shall be calculated separately and summed.
Table 144-C402.5.3.1 (1)
Required Number of Electric Vehicle Parking Spaces
Residential Space
Commercial Space
Number of Dwelling Units (DU)
# of EV Spaces Required for Residential Portion
1 pt.
# of EV Spaces Required for Residential Portion
2 pt.
Area in units of 1,000 Square Feet (CA)
# of EV Spaces Required for Commercial Portion
1 pt.
# of EV Spaces Required for Commercial Portion
2 pt.
1 to 6
NA
1
5
1
2
7 to 12
1
2
10
2
4
13 to 18
2
3
15
3
5
19 to 24
2
4
20
4
7
25 to 27
3
5
25
4
8
28 to 35
3
6
30
5
10
36 to 42
4
7
35
6
11
43 to 49
4
8
40
7
13
The numbers listed above are examples.
The numbers listed above are examples.
For 1 to 24 Dwelling Units:
EV Spaces required for each point SR = 0.081 x DU
For all building sizes use the equation:
EV Spaces required for each point SC = 0.151 x CA
For 25 or more Dwelling Units:
SR = [(0.13 x DU) + 1] ÷ 1.853
Complete calculations for Residential and Commercial space separately, add results, then round up to the nearest whole number. SR + SC = ST (Total EV Parking Spaces required). To calculate how to earn two points, refer to Table C402.5.3.1(2) or Table R502.5.3.1(2) Sample Calculation for required number of EV Parking Spaces.
Table 144-C402.5.3.1 (2)
Sample Calculation for Required Number of EV Parking Spaces
Sample Calculation
44,300 sq ft mixed-use building. 26 Dwelling Units (DU) and 6,000 sq ft Commercial Area (CA).
To earn one point
SR = [(0.13 x 26) + 1] ÷ 1.853
SR = (3.38 + 1) ÷ 1.853
SR = 4.38 ÷ 1.853 = 2.364
2.364 EV spaces are required for Residential portion
SC = 0.151 x 6
SC = 0.906
0.906 EV spaces are required for Commercial portion
ST = SR + SC rounded up
ST = 2.364 + 0.906 = 3.27, round up
4 EV spaces are required for the building to earn one point.
To earn two points
SR = 2.364 x 2 = 4.728
SC = 0.906 x 2 = 1.812
ST = SR + SC rounded up
ST = 4.728 + 1.812 = 6.54, round up
7 EV spaces are required for the building to earn two points.
144-C402.5.3.2. 
The requirements for this point as set forth here and in Table 144-C402.6 are not intended to override or supplant existing zoning code provisions regarding parking requirements. To the extent that zoning permissible parking spaces cannot be accommodated on the building site, the building must seek off-site spaces in accordance with the provisions of this point and applicable zoning laws.
144-C402.5.3.3. 
All electric vehicle parking spaces shall be located on the same parcel as the building, in the same parking facilities as those used by one or more of the following target user groups: customers/clients; employees; and fleet vehicles. If no parking facilities exist on the same parcel, and off-site parking facilities do exist for one or more of the user groups, then EV parking spaces may be installed in those off-site parking facilities. Off-site parking must be within 0.25 miles of the building.
144-C402.5.3.4. 
All electric vehicle parking spaces shall be served by a dedicated electric vehicle charging port. Electric vehicle charging stations may have any number of ports.
144-C402.5.3.5. 
At least one accessible electric vehicle parking space is required in any parking facility that includes more than 10 electric vehicle parking spaces. Any parking facility with more than 50 electric vehicle parking spaces must provide at least two accessible electric vehicle parking spaces. The associated space(s) are not required to be designated only for accessible parking, as defined by the Building Code of NYS, but must meet all other accessibility requirements contained in New York State law.
144-C402.5.3.6. 
All buildings must install Level 2 EV charging stations that operate on a 240-volt AC circuit and/or direct current fast chargers.
144-C402.5.3.7. 
Electric vehicle parking spaces shall be provided with a dedicated branch circuit, raceways, and all other electric vehicle charging equipment. All electrical systems and equipment shall be installed to meet the standards of the National Electrical Code in effect at the time of application for a building or electrical permit. The branch circuit shall be identified for electric vehicle service in the service panel or subpanel directory. Electrical room(s) serving areas with EV parking spaces shall be designed to accommodate the electrical equipment and distribution required to serve all of the electric vehicle charging stations.
[Amended 4-25-2022 by L.L. No. 8-2022]
144-C402.5.3.8. 
Electric vehicle charging station equipment shall be maintained in all respects, including the functioning of the charging equipment. A phone number or other contact information shall be provided on the charging station equipment for reporting when the equipment is not functioning, or other problems are encountered.
144-C402.5.3.9. 
The electric vehicle charging station, including the charging cord, shall be installed so as to not interfere with pedestrian walkways at any time.
144-C402.5.3.10. 
Except for accessible EV parking spaces, each EV parking space shall be posted with signage indicating that the space is only to be used for electric vehicle charging purposes. Days and hours of operations and any other restrictions on use of the parking space shall be included if time limits or tow-away provisions are to be enforced.
144-C402.5.4. 
OP4 Adaptive reuse. One point may be earned according to the requirements below.
[Amended 4-25-2022 by L.L. No. 8-2022]
144-C402.5.4.1. 
The building must maintain 50% or more of the following five existing building elements, based on their total combined surface area:
A. 
Exterior of above-grade and below-grade exterior walls.
B. 
Interior of above-grade and below-grade exterior walls.
C. 
Floors.
D. 
Ceilings.
E. 
Roof decks as defined by the Building Code of New York State (exterior surface area).
The 50% threshold relates to the total combined surface area of all listed building elements. Any individual elements, or portions thereof, may be replaced, as long as the total surface area of all the unaltered elements is at least 50% of the starting (pre-construction) total surface area of the elements.
144-C402.5.4.2. 
Any insulation may be altered to the extent allowed by the ECCCNYS in effect at the time of building permit application. The existing building structure must be repurposed for a different permitted use (for example, when an old school is adapted for use as apartments). A major renovation of a building and reuse for the same purpose shall not be eligible for this point.
144-C402.5.4.3. 
Examples. The diagrams and example calculation below are for informational purposes only. All requirements are included in 144-C402.5.4.1 and 144-C402.5.4.2, above. The simplified diagrams in Figure 144-C402.5.4.3 highlight which surface areas should be counted for two example buildings. An example calculation is provided in Table 144-C402.5.4.3. The diagram on the left shows a small residential building with a basement and an attic with insulation on the floor. The exterior surface area of the roof deck is counted, and the ceiling of the second story is counted; note that the floor of the attic is not counted. The diagram on the right shows a two-story commercial building with a flat roof and no basement or attic. Insulation is between the roof deck and the ceiling of the second story.
Figure 144-C402.5.4.3
Figure 144-C402-5-4-3.tif
Table 144-C402.5.4.3
Adaptive Reuse Example Calculation - Single-Family Home
Home Dimensions
Building width
30
feet
Building length
30
feet
Stories
2
Height/story
10
feet
Height of basement
8
feet
Height of roof peak from 2nd floor ceiling
10
feet
A. Exterior of above-grade and below-grade exterior walls
8 above-grade walls (N, S, E, W walls of 2 stories)
8
Surface area of each above-grade wall
300
square feet
Total surface area above-grade exterior walls
2,400
square feet
4 below grade walls (N, S, E, W walls of basement)
4
Surface area of each below-grade wall
240
square feet
Total surface area below-grade exterior walls
960
square feet
Total surface area, exterior of above-grade and below-grade exterior walls
3,360
square feet
B. Interior of above-grade and below-grade exterior walls
Use same calculations as for exterior side (above)
Total surface area, interior of above-grade and below-grade exterior walls
3,360
square feet
C. Floors
3 floors (1st story, 2nd story, basement)
3
Surface area of floor
900
square feet
Total surface area, floors
2,700
square feet
D. Ceilings
3 ceilings (1st story, 2nd story, basement)
3
Surface area of ceiling
900
square feet
Total surface area, ceilings
2,700
square feet
E. Roof decks (exterior surface area)
Roof height
10
feet
Roof triangle base (half of house)
15
feet
Hypotenuse (H) is roof length (1 side)
18
feet
Roof width = house width
30
feet
Roof area (1 side only) = H* roof width
540
square feet
Total surface area, roof
1,080
square feet
Total surface area, all building elements
13,200
square feet
50% of total surface area
6,600
square feet
If at least 6,600 square feet of the building elements are kept, the building will earn the adaptive reuse point.
144-C402.5.5. 
OP5 NY Stretch Code. One point may be earned according to the requirements below.
144-C402.5.5.1. 
The building shall comply with all requirements of the NY Stretch Energy Code - 2020 Version 1.0, which is available at: www.nyserda.ny.gov/All-Programs/Programs/Energy-Code-Training/NYStretch-Energy-Code-2020
144-C402.5.6. 
OP6 Custom energy improvement. Up to two points may be earned according to the requirements below.
144-C402.5.6.1. 
To earn one point, both of the following conditions must be met:
A. 
Reduce energy use by 1.2 kWh/SF/year or 4.1 kbtu/SF/year for all residential heated floor area in the building.
B. 
Reduce energy use by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all commercial heated floor area in the building.
144-C402.5.6.2. 
To earn two points, both of the following conditions must be met:
A. 
Reduce energy use by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all residential heated floor area in the building.
B. 
Reduce energy use by 4.8 kWh/SF/year or 16.4 kbtu/SF/year for all commercial heated floor area in the building.
144-C402.5.6.3. 
Multiple improvements may be combined to achieve each point under this improvement. Improvements may be made anywhere in the building as long as they meet the thresholds of energy use reduction. The proposed energy improvement(s) shall be submitted to the Code Enforcement Officer in writing, signed by the design professional or energy professional. Energy reduction must be shown through energy analysis performed by a design professional or energy professional. Simplified calculations (e.g., spreadsheet) are acceptable.
144-C402.5.6.4. 
For a baseline, use the 2016 Energy Conservation Construction Code of New York State. If the baseline condition is not addressed by the ECCCNYS, use baseline conditions as defined in Appendix G of ASHRAE Standard 90.1-2013.
144-C402.5.6.5. 
Production of renewable energy shall not count toward energy reduction. Energy reduction must be calculated after applying all other proposed energy improvements to the proposed design. In other words, interactive energy savings must be performed. Savings cannot be taken for improvements made with other points, such as right-lighting or the NY Stretch Energy Code.
144-C402.6. 
Summary Table for Prescriptive Compliance Path/Easy Path. The following Table 144-C402.6 is a summary of the Prescriptive Compliance Path/Easy Path for commercial buildings. This is a summary for informational purposes only. To earn points, all applicable requirements in Subsections 144-C402.1, 144-C402.2, 144-C402.3, 144-C402.4 and 144-C402.5 must be met. In case of discrepancies between Table 144-C402.6 and the requirements in Subsections 144-C402.1, 144-C402.2, 144-C402.3, 144-C402.4 and 144-C402.5, the latter shall hold precedence.
Table 144-C402.6
Commercial Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least six points.
Category
Improvement
Points
Details
EFFICIENT ELECTRIFICATION
EE1
Heat pumps for space heating
2 - 3
2 points for air source heat pumps.
3 points for ground source heat pumps.
EE2
Heat pumps for domestic hot water heating
1
1 point for water heating systems that use heat pumps. Available to hotels and restaurants only.
EE3
Commercial cooking electrification
3
3 points for electric cooking equipment in restaurants and other food service buildings. Prerequisite: no fossil fuel use in the building.
AFFORDABILITY IMPROVEMENTS
AI1
Smaller building/room size
1 - 2
Up to 2 points for smaller room sizes. Available for hotel and residential portions only.
AI2
Heating systems in heated space
1
1 point for installing heating systems in directly heated spaces.
AI3
Efficient building shape
1
1 point if exterior surface area divided by directly heated floor area is less than the maximum allowed value.
AI4
Right-lighting
1
1 point for reducing overlighting and implementing other lighting improvements.
AI5
Modest window-to-wall ratio
1
1 point for overall window-to-wall ratio less than 20% (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE1
Renewable energy systems
1 - 3
Up to 3 points for on-site or off-site renewable electric systems or on-site renewable thermal systems.
RE2
Biomass systems
3
3 points for biomass space heating systems.
OTHER POINTS
OP1
Development density
1
1 point for achieving sufficient development density on the building parcel. A maximum of 2 points total may be earned for points OP1, OP2, and OP3 combined.
OP2
Walkability
1
1 point if the building meets the walkability criteria. A maximum of 2 points total may be earned for points OP1, OP2, and OP3 combined.
OP3
Electric vehicle parking spaces
1
1 point for installing electric vehicle parking spaces and related infrastructure. A maximum of 2 points total may be earned for points OP1, OP2, and OP3 combined.
OP4
Adaptive reuse
1
1 point for substantial repurpose of existing building.
OP5
Meet NY Stretch Code
1
1 point for complying with NY Stretch Energy Code.
OP6
Custom energy improvement
1 - 2
Up to 2 points for reduction in energy use.
144-C403. 
Performance-based compliance path/whole building path.
144-C403.1. 
General. Until January 1, 2023, to meet the requirements of this Subsection 144-C403, a building must comply with any one of the high-performance building approaches described in 144-C403.2, 144-C403.3, 144-C403.4, and 144-C403.5. See Subsection 144-C404 for enhanced requirements beginning on and after January 1, 2023, and additional enhanced requirements beginning on and after January 1, 2026.
144-C403.2. 
LEED-based and energy calculation-based compliance.
144-C403.2.1. 
Buildings shall comply with one of the following:
A. 
Using LEED v4 for Building Design + Construction, the building shall earn no less than 17 LEED points total in the Optimize Energy Performance credit and the Renewable Energy Production credit of the Energy and Atmosphere section.
1. 
LEED certification is not necessary.
2. 
Renewable energy generation that meets all applicable requirements for renewable energy systems described in 144-C402.4.1 may be used to meet the requirements of the Renewable Energy Production credit.
B. 
Demonstrate 40% savings relative to ASHRAE Standard 90.1-2013, using the energy cost budget method or demonstrate 46% savings relative to ASHRAE Standard 90.1-2010, using the energy cost budget method.
1. 
Renewable energy generation may be used. All applicable requirements for renewable energy systems described in 144-C402.4.1 must be met. Renewable energy generation used to achieve the 40%/46% savings is capped at 25% of the baseline energy use.
2. 
The energy cost reduction assessment and requirement shall exclude energy use by process loads. However, the energy model shall include the energy used for process loads because energy used by heating, cooling, and ventilation (including exhaust fans/hoods, makeup air fans, and heating/cooling for makeup air) is subject to the energy cost reduction requirement. After the baseline and proposed energy models are run, for the energy cost reduction calculation, subtract out the process energy use from both the baseline and the proposed building energy model results, and use the resulting without-process-energy results for the energy cost calculations.
144-C403.2.2. 
Documentation shall include either:
A. 
Design approval by Green Business Certification Inc.TM (GBCI), through the Split Review process, that shows the building is eligible to receive no less than 17 LEED points as described in 144- C403.2.1(A); or both of the following:
B. 
Complete input and output reports of the energy model showing that the energy model meets the requirements of this Subsection 144-C403.
C. 
Approval of the energy model by NYSERDA, U.S. Department of Energy, Energize NY, or another agency approved by the Code Enforcement Officer.
144-C403.3. 
Passive house-based compliance.
144-C403.3.1. 
A. 
Buildings shall meet the design requirements of one of the following:
1. 
PHIUS+ Passive Building Standard from Passive House Institute US.
2. 
Passive House Classic Standard from Passive House Institute.
B. 
Actual certification is not required. The most recent version of the chosen standard in effect at the time of building permit application shall be used.
144-C403.3.2. 
Documentation shall include at least one of the following:
A. 
Pre-certification letter (or other formal communication) from an accredited passive house certifier, stating that design review has been completed and the building is designed to meet all requirements of the chosen standard. All documentation used to show achievement of the requirements must be submitted to the Code Enforcement Officer.
B. 
Documentation of passive house certification. All documentation used to achieve certification must be submitted to the Code Enforcement Officer.
144-C403.4. 
Greenhouse gas emissions calculation-based compliance. The building shall demonstrate a reduction in greenhouse gas (GHG) emissions of not less than 40% as compared to the baseline building.
144-C403.4.1. 
Energy modeling standards. GHG emissions reductions shall be shown through energy modeling that complies with Appendix G of ASHRAE Standard 90.1-2013.
144-C403.4.2. 
Process loads. The GHG emissions reduction assessment and requirement shall exclude energy use by process loads. However, the energy model shall include the energy used for process loads because energy used by heating, cooling, and ventilation (including exhaust fans/hoods, makeup air fans, and heating/cooling for makeup air) is subject to the GHG emissions reduction requirement. After the baseline and proposed energy models are run, for the GHG emissions reduction calculation, subtract out the process energy use from both the baseline and the proposed building energy model results, and use the resulting without-process-energy results for the GHG emissions calculations.
144-C403.4.3. 
Renewable energy. Renewable energy generation may be used. All applicable requirements for renewable energy systems described in 144-C402.4.1 must be met. Renewable energy generation used to achieve the 40% reduction in GHG emissions is capped at 25% of the baseline energy use. The GHG emissions factor for electricity produced by renewable energy systems shall be zero lb CO2e/MWh.
144-C403.4.4. 
GHG emissions factor for electricity. For buildings not served by combined heat and power plants, the GHG emissions factor for electricity used for all calculations shall be 548.37 lb CO2e/MWh.
144-C403.4.5. 
GHG emissions factor for electricity for buildings served by combined heat and power plants.
A. 
For buildings using electricity generated by combined heat and power (CHP) plants, the GHG emissions factor for electricity shall be determined in one of the following ways:
1. 
The most recent heat rate data available at the time of building permit application shall be used from www.eia.gov/electricity/annual/html/epa_08_02.html, for the specific type of generation plant used, for electricity to be used in the proposed building, and the heat rate shall be multiplied by the EPA emissions factor for the fuel used at the CHP plant. The result shall be used as the GHG emissions factor for electricity from CHP plants.
2. 
Data gathered from actual operation of the CHP plant and its distribution network shall be used to determine the site-specific GHG emissions factor for electricity to be used in the building. All data used shall be made publicly available before the time of building permit application.
B. 
For buildings served by CHP plants, the baseline (reference building) electricity use GHG emissions factor shall be the same as for buildings not served by a CHP plant.
144-C403.4.6. 
If a facility uses electricity from a combination of sources (e.g., utility, off-site renewable energy system, and CHP plant), a weighted average of GHG emissions factors shall be used.
144-C403.4.7. 
Documentation. The following documentation shall be submitted to show compliance with 144-C403.4 in sufficient clarity and detail:
A. 
A report, signed and stamped by an accredited third-party energy professional, showing the results of all calculations, assumptions, inputs, and outputs for the energy model.
B. 
A letter, signed and stamped by an accredited third-party energy professional, stating that proposed total GHG emissions for the building are at least 40% less than the GHG emissions of the baseline building.
C. 
The Town reserves the right to require additional documentation and/or additional third-party review and analysis by a consultant selected by the Town, at the expense of the applicant. All such documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
144-C403.5. 
Greenhouse gas emissions calculation-based compliance for additions. Compliance using the requirements of this provision 144-C403.5 may only be used for additions that are showing compliance together with the existing building. See also 144-202.2.
144-C403.5.1. 
The addition and the existing building, together as a whole, shall be shown to have lower total GHG emissions than the original existing building.
144-C403.5.2. 
Current and proposed GHG emissions shall be calculated following the requirements of the GHG Emissions Calculation Method (144-C403.4).
144-C403.5.3. 
Documentation.
A. 
The following documentation shall be submitted to show compliance with 144-C403.5 in sufficient clarity and detail:
1. 
An energy study of the existing building that includes energy use from at least 12 consecutive months of the most recent 24 months at the time of building permit application;
2. 
An energy study that shows anticipated energy use for the new addition and modified existing building;
3. 
A report, signed and stamped by an accredited energy professional, showing the results of all calculations, assumptions, inputs, and outputs for the energy model; and
4. 
A letter, signed and stamped by an accredited third-party energy professional, stating that proposed total GHG emissions for the building and addition together are less than the GHG emissions for the existing building.
B. 
The Town reserves the right to require additional documentation and/or additional third-party review and analysis by a consultant selected by the Town, at the expense of the applicant. All such documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
144-C404. 
Future requirements.
144-C404.1. 
General.
A. 
On January 1, 2023, the requirements of Subsections 144-C402 and 144-C403 shall change as described in 144-C404.2, 144-C404.3, 144-C404.4, and 144-C404.6. Where no changes are listed, the requirements shall remain as described in Subsections 144-C402 and 144-C403.
B. 
On January 1, 2026, the requirements of Subsections 144-C401, 144-C402 and 144-C403 shall change as described in 144-C404.7. Where no changes are listed, the requirements shall remain as described in Subsections 144-C401, 144-C402 and 144-C403.
144-C404.2. 
Changes in 2023 to general requirements of prescriptive compliance path/easy path. Effective January 1, 2023, to meet the requirements of Subsection 144-C402, a building must achieve a minimum of 12 of the points described in Subsection 144-C402. A summary table is provided in 144-C404.5.
144-C404.3. 
Changes in 2023 to efficient electrification points. Effective January 1, 2023, all points awarded from 144-C402.2, Efficient electrification, shall be doubled.
144-C404.3.1. 
Four points shall be earned for using air source heat pumps and meeting the requirements of 144-C402.2.1, Heat pumps for space heating. Six points shall be earned for using ground source heat pumps and meeting the requirements of 144-C402.2.1, Heat pumps for space heating.
144-C404.3.2. 
Two points shall be earned for meeting the requirements of 144-C402.2.2, EE2 Heat pumps for service water heating.
144-C404.3.3. 
Six points shall be earned for meeting the requirements of 144-C402.2.3, EE3 Commercial cooking electrification.
144-C404.4. 
Changes in 2023 to RE1 Renewable Energy Systems. Effective January 1, 2023, the maximum number of points allowed under 144-402.4.1, RE1 Renewable energy systems, shall increase to six points. The criteria for earning points shall remain as described in 144-C402.4.1.
144-C404.5. 
Changes in 2023 to summary table for prescriptive compliance path/easy path.
[Amended 1-9-2023 by L.L. No. 1-2023]
Commercial Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least 12 points.
Category
Improvement
Points
Details
EFFICIENT ELECTRIFICATION
EE1
Heat pumps for space heating
4 - 6
4 points for air source heat pumps.
6 points for ground source heat pumps.
EE2
Heat pumps for service water heating
2
2 points for water heating systems that use heat pumps.
Available to hotels and restaurants only.
EE3
Commercial cooking electrification
6
6 points for electric cooking equipment in restaurants and other food service buildings. Prerequisite: no fossil fuel use in the building.
AFFORDABILITY IMPROVEMENTS
AI1
Smaller building/room size
1 - 2
Up to 2 points for smaller room sizes. Available for hotel and residential portions only.
AI2
Heating systems in heated space
1
1 point for installing heating systems in directly heated spaces.
AI3
Efficient building shape
1
1 point if exterior surface area divided by directly heated floor area is less than the maximum allowed value.
AI4
Right-lighting
1
1 point for reducing overlighting and implementing other lighting improvements.
AI5
Modest window-to-wall ratio
1
1 point for overall window-to-wall ratio less than 20% (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE1
Renewable energy systems
1 - 6
Up to 6 points for on-site or off-site renewable electric systems or on-site renewable thermal systems.
RE2
Biomass systems
3
3 points for biomass space heating systems.
OTHER POINTS
OP1
Development density
1
1 point for achieving sufficient development density on the building parcel. A maximum of 3 points total may be earned for points OP1, OP2, and OP3 combined.
OP2
Walkability
1
1 point if the building meets the walkability criteria. A maximum of 3 points total may be earned for points OP1, OP2, and OP3 combined.
OP3
Electric vehicle parking spaces
1 - 2
Up to 2 points for installing electric vehicle parking spaces and related infrastructure. A maximum of 3points total may be earned for points OP1, OP2, and OP3 combined.
OP4
Adaptive reuse
1
1 point for substantial repurpose of existing building.
OP5
Meet NY Stretch Code
1
1 point for complying with NY Stretch Energy Code.
OP6
Custom energy improvement
1 - 2
Up to 2 points for reduction in energy use.
144-C404.6. 
Changes in 2023 to performance-based compliance path/whole building path. Effective January 1, 2023, the requirements of Subsection 144-C403, Performance-based compliance path/whole building path, shall change as described in 144-C404.6.1 and 144-C404.6.2. Where no changes are listed, the requirements shall remain as described in Subsection 144-C403.
144-C404.6.1. 
Changes to LEED-based and energy calculation-based compliance. Effective January 1, 2023:
A. 
Compliance method 1 (LEED points): In addition to all existing requirements, seven ECS points from Subsection C402, Prescriptive compliance path/easy path, must be earned. Points from AI4 Right-Lighting and OP5 Meet NY Stretch Code may not be counted toward the seven ECS points.
B. 
Compliance method 2 (savings relative to ASHRAE 90.1-2013): An 80% savings relative to ASHRAE Standard 90.1-2013 shall be required.
1. 
Renewable energy generation used to achieve the savings shall be capped at 50% of the baseline energy use.
C. 
Compliance method thbree (savings relative to ASHRAE 90.1-2010): A 92% savings relative to ASHRAE Standard 90.1-2010 shall be required.
1. 
Renewable energy generation used to achieve the savings shall be capped at 50% of the baseline energy use.
144-C404.6.2. 
Changes to greenhouse gas emissions calculation-based compliance. Effective January 1, 2023, the building shall demonstrate a reduction in greenhouse gas (GHG) emissions of not less than 80% as compared to the baseline building.
144-C404.6.2.1. 
Renewable energy generation used to achieve the 80% reduction in GHG emissions is capped at 50% of the baseline energy use.
144-C404.6.2.2. 
For buildings not served by combined heat and power plants or renewable energy systems, the GHG emissions factor for electricity used for all calculations shall be 295.9 lb CO2e/MWh.
144-C404.7. 
Changes in 2026. Effective January 1, 2026, all buildings shall be built to have net-zero GHG emissions and shall not use fossil fuels for space heating, water heating, or clothes drying.
144-C404.7.1. 
The language in 144-C401.2, Application, shall be replaced with:
Commercial buildings shall comply with the requirements of the ZERO Code, using the most recent version of the ZERO Code available at the time of permit application. The ZERO Code, an Architecture 2030 initiative, is available at https://zero-code.org.
An ECS Compliance Plan shall be the basis for evaluating compliance.
144-C404.7.2. 
Fossil fuels shall not be used for space heating, water heating or clothes drying. Fossil fuels may be used for process energy and for cooking.
144-R501. 
General.
144-R501.1. 
Scope. The provisions in this section are applicable to residential buildings and mixed-use buildings where more than 50% of the heated floor area is residential, their building sites, and associated systems and equipment.
144-R501.2. 
Application. Residential buildings shall comply with one of the following:
A. 
Prescriptive compliance path/easy path: The requirements of Subsection 144-R502.
1. 
As part of the application packet, the applicant shall submit a checklist and worksheet which the Town shall use as the basis for verifying and showing compliance with the ECS.
B. 
Performance-based compliance path/whole building path: The requirements of Subsection 144-R503.
1. 
As part of the applicat ion packet, the applicant shall submit the relevant documentation, which is detailed in Subsection 144-R503, which the Town shall use as the basis for verifying and showing compliance with the ECS.
144-R502. 
Prescriptive compliance path/easy path.
144-R502.1. 
General. Until January 1, 2023, to meet the requirements of this Subsection 144-R502, a building must achieve a minimum of six of the points described in this subsection. A summary table is provided in 144-R502.6. See Subsection 144-R504 for enhanced requirements beginning on and after January 1, 2023, and additional enhanced requirements beginning on and after January 1, 2026.
144-R502.2. 
Efficient electrification (EE).
144-R502.2.1. 
EE1 Heat pumps for space heating. Three points shall be earned for using air source heat pumps or five points shall be earned for using ground source heat pumps, as described in 144-R502.2.1.
144-R502.2.1.1. 
Only air source heat pumps or ground source heat pumps shall be used for all space-heating needs, with exceptions for electric resistance heating as described in 144-R502.2.1.4. A heating system that uses only ground source heat pumps (and electric resistance heating as allowed) shall earn five points. A heating system that uses only air source heat pumps or uses a combination of air source and ground source heat pumps (and electric resistance heating as allowed) shall earn three points.
144-R502.2.1.2. 
Fossil fuels shall not be used for any space heating, space cooling or ventilation systems in the building, including backup heating systems. Water loop boiler/tower heat pumps that use fossil fuels shall not earn credit under this point.
144-R502.2.1.3. 
Except as stated in the second sentence of this provision 144-R502.2.1.3, air source heat pumps shall be listed in the Northeast Energy Efficiency Partnerships (NEEP) Cold Climate Air Source Heat Pump Product List, for the product types and sizes covered. For any air source heat pump not covered by NEEP, the heat pump shall use a variable speed compressor(s) and the heat pump compressor(s) shall operate in temperatures below 0° F. (The compressor may be supplemented by electric resistance heat in accordance with the exceptions described in 144-R502.2.1.4).
144-R502.2.1.4. 
To allow flexibility, electric resistance heat is allowed for a portion of space heating needs. Applicants shall submit documentation showing that at least one of the following conditions is met:
A. 
Stand-alone electric resistance heating (not associated with heat pumps) is used to heat 10% or less of the building heated floor area.
B. 
Stand-alone electric resistance heating (not associated with heat pumps) is used to meet 10% or less of the building's projected annual space heating load.
144-R502.2.2. 
EE2 Heat pumps for service water heating. One point shall be earned for meeting the requirements of 144-R502.2.2.
144-R502.2.2.1. 
All service water heating systems shall use heat pumps and shall not use fossil fuels. All heat pump water heaters shall be set on heat-pump-only mode.
Exception: In commercial kitchens, booster heat units for dishwashing must be electric, but shall be exempt from the heat pump requirement. Units used to pre-heat water for dishwashing shall use heat pumps.
144-R502.2.3. 
EE3 Commercial cooking electrification. Three points shall be earned for meeting the requirements of 144-R502.2.3. Restrictions:
A.
Points may only be earned for portions of buildings that are restaurants or other food service establishments that use a commercial kitchen hood; and
B.
Points may only be earned if the building does not use fossil fuels, except for process energy. For this point, process energy shall exclude commercial cooking.
144-R502.2.3.1. 
All commercial cooking equipment in the building, including but not limited to ranges, ovens, griddles, and fryers, shall be electric.
144-R502.2.4. 
EE4 Residential cooking and clothes drying electrification. One point shall be earned for meeting the requirements of 144-R502.2.4. Restrictions: Point may only be earned if the building does not use fossil fuels except for process energy.
144-R502.2.4.1. 
All residential cooking equipment in the building, including but not limited to ranges, cooktops and ovens, shall be electric.
144-R502.2.4.2. 
All clothes drying equipment in the building shall be ventless heat pump clothes dryers.
144-R502.3. 
Affordability Improvements (AI).
144-R502.3.1. 
AI1 Smaller building/room size. One or two points may be earned according to the requirements below. Restrictions:
A.
For mixed-use buildings, this point may only be earned when all portions of the building are classified as residential or hotel.
B.
Dormitories are not eligible for this point.
C.
For additions, this point may only be earned if the applicant demonstrates ECS compliance for the addition together with the existing building. This point may not be earned when considering the addition independent of the existing building.
144-R502.3.1.1. 
For single-family dwellings, the directly heated floor area of the building shall not be greater than the maximum home size listed in Table 144-R502.3.1.1 relating to the number of bedrooms in the dwelling. For two-family dwellings and townhouses, the total directly heated floor area of the building shall not be greater than the total building size allowance. The total building size allowance, in square feet, shall be determined by multiplying the quantity of each type of dwelling unit (1-BR, 2-BR, etc.) times the "maximum home size" value for that dwelling unit type in Table 144-R502.3.1.1, and then summing the home size allowances for all unit types to calculate the total building size allowance. This method is summarized in Equation 144-5-1.
Equation 144-5-1:
Total Building Size Allowance =
[(Number of 1-BR units in the building) x (Maximum home size for 1-BR units listed in Table 144-R502.3.1.1)] + [(# of 2-BR units in the building) x (Maximum home size for 2-BR units)] + . . . + [(# of 6-BR units in the building) x (Maximum home size for 6-BR units)]
Individual dwelling units may exceed the maximum home size allowance for that unit type given in Table 144-R502.3.1.1.
Table 144-R502.3.1.1
Size Allowances for Single-Family Dwellings, Two-family Dwellings, and Townhouses
Number of Bedrooms
1
2
3
4
5
6
7 or more
Maximum home size allowed to receive 1 point (SF)
850
1,360
1,870
2,380
2,890
3,400
+510 for each additional bedroom
Maximum home size allowed to receive 2 points (SF)
700
1,120
1,540
1,960
2,380
2,800
+420 for each additional bedroom
Example Calculation - For Informational Purposes Only
Duplex, building contains 3,100 square feet of directly heated floor area, two dwelling units (3 bedrooms each)
From Table 144-R502.3.1.1
Maximum home size allowed to receive 1 point for 3-BR units: 1,870 square feet
Total Building Size Allowance = (2 x 1,870 square feet) = 3,740 square feet
Building size of 3,100 square feet does not exceed size allowance, so 1 point can be earned.
From Table 144-R502.3.1.1
Maximum home size allowed to receive two points for 3-BR units: 1,540 square feet
Total Building Size Allowance = (2 x 1,540 square feet) = 3,080 square feet
Building size of 3,100 square feet exceeds size allowance, so two points cannot be earned.
144-R502.3.1.2. 
For residential buildings other than single-family dwellings, two-family dwellings, and townhouses, the total directly heated floor area of all dwelling units in the building shall not be greater than the total unit size allowance. The directly heated floor area of dwelling units refers to in-unit areas only and shall not include common areas. The total unit size allowance, in square feet, shall be determined by multiplying the quantity of each type of dwelling unit (studio, 1-BR, etc.) times the "dwelling unit size allowance" value for that dwelling unit type in Table 144-R502.3.1.2, and then summing the unit size allowances for all unit types to calculate the total unit size allowance. This method is summarized in Equation 144-5-2.
Equation 144-5-2:
Total Unit Size Allowance =
[(Number of studio units in the building) x (Dwelling unit size allowance for studio units listed in Table 144-R502.3.1.2)] +
[(# of 1-BR units in the building) x (Dwelling unit size allowance for 1-BR units)]+
[(# of 2-BR units in the building) x (Dwelling unit size allowance for 2-BR units)]+ . . . +
[(# of 7-BR units in the building) x (Dwelling unit size allowance for 7-BR units)]
Individual dwelling units may exceed the allowance for that unit type given in Table 144-R502.3.1.2.
Table 144-R502.3.1.2
Dwelling Unit Size Allowances for Residential Buildings other than Single-Family Dwellings, Two-Family Dwellings, and Townhouses
Number of Bedrooms
Studio
1
2
3
4
5
6
7
Dwelling unit size allowance to receive 1 point (square feet)
408
600
842
986
1,156
1,326
1,496
1,666
Dwelling unit size allowance to receive 2 points (square feet)
336
490
693
812
952
1,092
1,232
1,372
144-R502.3.1.3. 
For hotels, the average directly heated floor area of all guest rooms in the building shall not be greater than the maximum average guest room size listed in Table 144-R502.3.1.3. Individual guest rooms may exceed the maximum size.
Table 144-R502.3.1.3
Area Requirements for Hotels and Motels
Maximum average guest room size allowed to receive 1 point (SF)
280
Maximum average guest room size allowed to receive 2 points (SF)
230
144-R502.3.2. 
AI2 Heating system in heated space. One point may be earned according to the requirements below.
144-R502.3.2.1. 
A. 
All components of heating systems shall be installed inside space that meets all the following criteria:
1. 
Inside the building thermal envelope.
2. 
Directly heated space.
3. 
Livable space, occupiable space or contiguous to livable space or occupiable space.
4. 
On a building level where at least 50% of the floor area is directly heated floor area.
B. 
For purposes of this subsection, "heating system" includes all parts of the system except for exhaust components and dedicated air intake components, including but not limited to mechanical equipment and the distribution network. Examples of spaces that are not allowed for heating system installation include, but are not limited to: unheated or unfinished basements and attics, crawl spaces, outdoors, roofs, and exterior wall cavities. Rooftop systems, window-mounted systems, and "through-the wall" equipment such as packaged terminal equipment shall not be used.
Exceptions:
A.
Outdoor units of split system heat pumps may be located outdoors.
B.
There are no limitations on the location of refrigerant piping.
144-R502.3.3. 
AI3 Efficient building shape. One point may be earned according to the requirements below.
144-R502.3.3.1. 
The exterior surface area divided by the directly heated floor area shall be less than the maximum value provided in Table 144-R502.3.3.1.
144-R502.3.3.2. 
The exterior surface area shall be measured along the above-grade portions of the building thermal envelope, including but not limited to walls, roofs/ceilings (depending on the location of insulation), and exposed floors (such as those below a cantilever). The area of windows, doors, and skylights shall be included as part of the exterior surface area. The areas of the building thermal envelope between directly heated spaces and indirectly heated spaces or unheated spaces, such as the wall between a heated building and an attached unheated garage, shall be included as part of the exterior surface area.
144-R502.3.3.3. 
For additions, the area of the building thermal envelope between directly heated space in the addition and directly heated space in the original building (including shared walls and, if the addition is above the original building, floors/ceilings) shall not be counted as part of the exterior surface area.
Table 144-R502.3.3.1
Directly Heated Floor Area
(SF)
Maximum Value of Exterior Surface Area (SF) Divided by Directly Heated Floor Area
(SF)
Directly Heated Floor Area
(SF)
Maximum Value of Exterior Surface Area (SF) Divided by Directly Heated Floor Area
(SF)
199 or less
4.69
3,000 - 3,999
1.60
200 - 299
3.88
4,000 - 4,999
1.48
300 - 399
3.45
5,000 - 5,999
1.39
400 - 499
3.17
6,000 - 6,999
1.31
500 - 599
2.98
7,000 - 7,999
1.25
600 - 699
2.83
8,000 - 8,999
1.19
700 - 799
2.71
9,000 - 9,999
1.15
800 - 899
2.68
10,000 - 14,999
1.05
900 - 999
2.57
15,000 - 19,999
0.94
1,000 - 1,099
2.47
20,000 - 29,999
0.84
1,100 - 1,199
2.38
30,000 - 39,999
0.75
1,200 - 1,299
2.31
40,000 - 49,999
0.68
1,300 - 1,399
2.24
50,000 - 59,999
0.64
1,400 - 1,499
2.18
60,000 - 69,999
0.61
1,500 - 1,599
2.13
70,000 - 79,999
0.58
1,600 - 1,699
2.08
80,000 - 89,999
0.55
1,700 - 1,799
2.04
90,000 - 99,999
0.53
1,800 - 1,899
2.00
100,000 - 199,999
0.46
1,900 - 1,999
1.96
200,000 - 299,999
0.39
2,000 - 2,499
1.86
300,000 - 399,999
0.35
2,500 - 2,999
1.74
400,000 or more
0.33
144-R502.3.4. 
AI5 Modest window-to-wall ratio. One point may be earned according to the requirements below.
144-R502.3.4.1. 
The vertical fenestration area, not including opaque doors and opaque spandrel panels, shall be not greater than 20% of the gross above-grade wall area.
144-R502.3.4.2. 
For additions, the area of above-grade walls that were part of the building thermal envelope of the original building but are not part of the building thermal envelope of the new building shall be counted towards the above-grade wall area of the addition.
144-R502.4. 
Renewable energy (RE).
144-R502.4.1. 
RE1 Renewable energy systems. Up to three points may be earned according to the requirements below.
144-R502.4.1.1. 
Points available. On-site and off-site renewable energy systems that meet the requirements of this subsection shall earn up to three points based on their annual electrical or thermal energy production. Multiple renewable energy systems may be used to earn points, but no more than three total points may be earned for any combination of renewable energy systems.
144-R502.4.1.2. 
Determining the number of points earned. The number of points earned shall be determined according to the steps below. The applicant shall submit documentation of all related assumptions and calculations.
Step 1: Calculate Renewable Energy Production
The Renewable Energy Production (REP) is the projected annual energy production of the renewable energy system, expressed in kilowatt-hours per year (kWh/yr). For thermal systems, the conversion 1 kWh = 3.412 kBtu shall be used.
Step 2: Calculate the Number of Points Earned
The number of points earned for a renewable energy system is based on the directly heated floor area of the building it serves. Points shall be earned based on a weighted average related to residential and commercial floor area, as described in Equation 144-5-2. For purposes of this 144-R502.4.1, residential space shall include dwelling units and common areas that serve only dwelling units.
Equation 144-5-2: Minimum Renewable Energy Production needed to earn each point = (1.2 kWh/ft2 x RA) + (2.4 kWh/ft2 x CA)
CA = Directly heated floor area of Commercial space (ft2)
RA = Directly heated floor area of Residential space (ft2)
Note: For buildings that have no commercial space, set CA equal to zero.
Example Calculation - For Informational Purposes Only
Assumptions: Mixed-use building with 2,000 ft2 of residential directly heated floor area and 5,000 ft2 of commercial directly heated floor area. A 25 kW solar array is being used.
Step 1: Using the PVWatts Calculator, it is projected that the 25 kW solar array will produce 30,000 kWh/year.
Renewable Energy Production is 30,000 kWh/year
Step 2: Using Equation 144-5-2:
Minimum REP needed for each point = (1.2 kWh/ft2 x RA) + (2.4 kWh/ft2 x CA)
Minimum REP needed for each point = (1.2 kWh/ft2 x 2,000 ft2) + (2.4 kWh/ft2 x 5,000 ft2)
Minimum REP needed for each point = 2,400 kWh + 12,000 kWh
Minimum REP needed for each point = 14,400 kWh
Using the assumptions for this building and renewable energy system, two points may be earned.
144-R502.4.1.3. 
Energy sources.
A. 
Renewable energy systems shall produce electricity from solar, wind, or hydropower resources, or produce thermal energy from solar, geothermal, or hydrothermal resources. Thermal energy absorbed from or rejected to outdoor air/ground/water and used in conjunction with heat pumps does not count as renewable energy for the purposes of this subsection. Hydropower shall be from new generation capacity on a nonimpoundment or new generation capacity on an existing impoundment. Hydropower shall meet one of the following conditions:
1. 
The hydropower facility complies with the Low Impact Hydropower Certification Handbook and is certified by a nationally recognized accreditation organization.
2. 
The hydropower facility complies with UL 2854 and is certified by an organization that has the standard in its ISO 17065 scope of accreditation.
3. 
The hydropower facility consists of a turbine in a pipeline or a turbine in an irrigation canal.
B. 
For facilities falling under condition A(1) or A(2), only output generated during the period of certification is eligible for RECs sale in accordance with the provisions of this subsection. Renewables from new impoundments of water are not eligible.
144-R502.4.1.4. 
Qualifying renewable energy systems. Renewable energy systems producing electricity or thermal energy that is delivered to or credited to the building to comply with 144-R502.4.1 shall meet the following requirements:
A. 
Renewable energy systems shall satisfy one of the following criteria:
1. 
On-site renewable energy system.
a. 
Self-generation.
b. 
Purchase contract, such as a power purchase agreement.
2. 
Off-site renewable energy system.
a. 
Self-generation (an off-site renewable energy system owned by the building owner).
b. 
Community renewable energy facility.
c. 
Purchase contract, such as a power purchase agreement.
B. 
The renewable energy system shall be located in New York Independent System Operator (NYISO) territory and shall be located where the energy can be delivered to the building site by any of the following:
1. 
Direct connection to the renewable energy system.
2. 
The local utility or distribution entity.
3. 
An interconnected electrical network where energy delivery capacity between the generator and the building site is available. (Informative Note: Examples of interconnected electrical networks include regional power pools and regions served by independent system operators or regional transmission organizations.)
C. 
The renewable energy system must have commenced operation on or after January 1, 2015, and before the date the certificate of occupancy for the building is issued.
Exception to 144-R502.4.1.4(C). If the building owner can provide evidence that, for the duration of the planning process, it has made a good faith effort to have the renewable energy system constructed and operational by the time of certificate of occupancy, and due to circumstances out of the control of and not otherwise due to the negligence or willful misconduct on behalf of the building owner, the renewable energy system is not constructed or is not operational, then the building owner shall be allowed up to one year after the certificate of occupancy is issued to meet 144-R502.4.1.4(C).
D. 
Where the renewable energy system ceases operation, or the owner cannot legally claim the associated energy or RECs for any reason, the building owner shall produce or procure alternative qualifying renewable energy in an amount equal to or greater than the amount needed to earn the same number of points under the requirements of 144-R502.4.1.2.
144-R502.4.1.5. 
Reporting and documentation.
A. 
The building owner shall submit documentation of renewable energy system ownership or renewable energy procurement, which includes subscription to a community solar project. Records on power and thermal energy produced or purchased by the building owner from the renewable energy producer shall be retained by the building owner on behalf of the entity demonstrating financial or operational control over the building seeking compliance to this standard and submitted to the Code Enforcement Officer on an annual basis for no less than 15 years. Any period of noncompliance shall not count toward fulfillment of the fifteen-year requirement.
B. 
For systems generating electricity, documentation shall be provided to the Code Enforcement Officer that indicates an exclusive chain of custody and ownership of the RECs from the renewable energy system to the building owner, on an annual basis for no less than 15 years. RECs supplied from the renewable energy system shall be conveyed to and retired on behalf of the entity who has financial or operational control over the building's electricity consumption. The annual generation vintage date of delivered RECs shall be allocated to the same twelve-month reporting year, up to six months prior, or up to three months after the calendar year in which the electricity is used in the building. Any period of noncompliance shall not count toward fulfillment of the fifteen-year requirement. Exceptions to 144-R502.4.1.5(B):
1. 
If the total capacity of all renewable energy systems being used to earn points under 144-R502.4.1 is less than 25 kW, the requirements of 144-R502.4.1.5(B) shall be waived.
2. 
Where the building owner cannot provide documentation on the chain of custody or ownership of the RECs from the renewable energy system, the building owner shall provide documentation to the Code Enforcement Officer of an alternate supply contract for replacement RECs from an alternate renewable energy source. The quantity of RECs contracted for shall be equal to or greater than the amount needed to earn the desired number of points under the requirements of 144-R502.4.1.2. These RECs shall comply with the Green-e® Renewable Energy Standard for Canada and the United States (latest edition) and shall be conveyed to and retired on behalf of the entity who has financial or operational control over the building's electricity consumption.
C. 
Electricity, thermal energy and RECs from renewable energy systems may not be counted more than once for purposes of demonstrating compliance with this 144-R502.4.1. The reporting and documentation required in 144-R502.4.1.4 shall clearly state how the energy and RECs are allocated to specific buildings. The Town may request additional documentation to provide reasonable proof of ownership/procurement, and fulfillment of RECS and allocation requirements.
D. 
In the case of full or partial transfer of ownership of the building, the following must be provided: proof of transfer of ownership; a signed statement from the new owner stating they understand the requirements of this 144-R502.4.1 and the duty to fulfill them; and contact information for the person(s) responsible for submitting annual reporting.
144-R502.4.2. 
RE2 Biomass space heating. Five points may be earned according to the requirements below.
144-R502.4.2.1. 
Only biomass systems shall be used for all space-heating needs, with exceptions for electric resistance heating as described in 144-R502.4.2.4.
144-R502.4.2.2. 
Fossil fuels shall not be used for any space heating, space cooling or ventilation systems in the building, including backup heating systems.
144-R502.4.2.3. 
All biomass equipment must comply with the NYSERDA Renewable Heat NY program guidelines, available at www.nyserda.ny.gov/All-Programs/Programs/Renewable-Heat-NY.
144-R502.4.2.4. 
To allow flexibility, electric resistance heat is allowed for a portion of space heating needs. Applicants shall submit documentation showing that at least one of the following conditions is met.
A. 
Stand-alone electric resistance heating is used to heat 10% or less of the building heated floor area.
B. 
Stand-alone electric resistance heating is used to meet 10% or less of the building's projected annual space heating load.
144-R502.5. 
Other points (OP).
144-R502.5.1. 
OP1 Development density. One point may be earned according to the requirements below. Restrictions: A maximum of three points total may be earned using up to two (maximum) of the following: OP1 Development Density, OP2 Walkability, and OP3 Electric Vehicle Parking Spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
144-R502.5.1.1. 
One point shall be earned if (DU + CA) > (7 x Acreage), where:
DU = the number of all residential dwelling units on the entire parcel occupied by the building.
CA = the floor area of all commercial space, measured in units of 1,000 square feet, on the entire parcel occupied by the building.
Acreage = the land area, measured in acres, of the entire parcel occupied by the building.
144-R502.5.1.2. 
DU shall include all dwelling units on the parcel occupied by the building, including those in existing buildings. CA shall include all commercial space on the parcel occupied by the building, including that in existing buildings. CA shall not include common areas serving only dwelling units or other residential space. Acreage shall include all land area on the parcel occupied by the building.
144-R502.5.2. 
OP2 Walkability. One point may be earned according to the requirements below. Restrictions: A maximum of three points total may be earned using up to two (maximum) of the following: OP1 Development Density, OP2 Walkability, and OP3 Electric Vehicle Parking Spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
144-R502.5.2.1. 
This point shall be earned when either of the following two conditions is met, in addition to the other requirements in this 144-R502.5.2:
A. 
The building is within one quarter (0.25) mile of at least five of the Neighborhood Amenity Types listed in Table 144-R502.5.2.1.
1. 
No single Amenity Type shall be counted more than twice, even when more than two examples of the Amenity Type exist. For example, a building on Aurora Street's "Restaurant Row" could count two restaurants maximum.
2. 
At least two Amenity Categories shall be represented.
3. 
The one-quarter-mile measurement(s) may be taken from any part(s) of the building.
B. 
The building is within a Town development priority area for which a regulating plan has been developed and adopted.
144-R502.5.2.2. 
For all buildings, at the time of project completion, sidewalks, walkways and/or trails must be present on the property or within 75 feet of the property, and connect to an existing network of pedestrian infrastructure.
Table 144-R502.5.2.1
Neighborhood Amenity Types and Categories
Amenity Category
Amenity Type
Food retail
Supermarket
Grocery with produce section
Community-serving retail
Convenience store
Farmers' market
Hardware store
Pharmacy
Other retail
Services
Bank
Family entertainment venue (e.g., theater, sports)
Gym, health club, exercise studio
Hair care
Laundry, dry cleaner
Restaurant, cafe, diner (excluding those with only drive-through service)
Civic and community facilities
Adult or senior care (licensed)
Child care (licensed)
Community or recreation center
Cultural arts facility (museum, performing arts)
Education facility (e.g., K-12 school, university, adult education center, vocational school, community college)
Government office that serves public on-site
Medical facility that treats patients
Place of worship
Post office
Public library
Public park
Social services center
144-R502.5.3. 
OP3 Electric vehicle parking spaces. Up to two points may be earned for installing electric vehicle parking space(s) and related infrastructure that meet the requirements of this subsection. Restrictions: A maximum of three points total may be earned using up to two (maximum) of the following: OP1 Development Density, OP2 Walkability, and OP3 Electric Vehicle Parking Spaces.
[Amended 1-9-2023 by L.L. No. 1-2023]
144-R502.5.3.1. 
Required number of EV parking spaces. The number of required EV parking spaces shall be determined using Table 144-R502.5.3.1(1), based on the number of residential dwelling units (DU) and the area of commercial space (CA).
DU = the number of residential dwelling units in the building.
CA = the area of all commercial space, measured in units of 1,000 square feet, in the building. CA shall not include common areas serving only dwelling units or other portions of residential space.
When determining the total number of required spaces in mixed-use buildings, EV space requirements for residential dwelling units and for commercial space shall be calculated separately and summed.
Table 144-R502.5.3.1(1)
Required Number of Electric Vehicle Parking Spaces
Residential Space
Commercial Space
Number of Dwelling Units (DU)
# of EV Spaces Required for Residential Portion
1 pt.
# of EV Spaces Required for Residential Portion
2 pt.
Area in units of 1,000 Sq. Ft (CA)
# of EV Spaces Required for Commercial Portion
1 pt.
# of EV Spaces Required for Commercial Portion
2 pt.
1 to 6
NA
1
5
1
2
7 to 12
1
2
10
2
4
13 to 18
2
3
15
3
5
19 to 24
2
4
20
4
7
25 to 27
3
5
25
4
8
28 to 35
3
6
30
5
10
36 to 42
4
7
35
6
11
43 to 49
4
8
40
7
13
The numbers listed above are examples.
The numbers listed above are examples.
For 1 to 24 Dwelling Units:
EV Spaces required for each point SR = 0.081 x DU
For all building sizes use the equation:
EV Spaces required for each point SC = 0.151 x CA
For 25 or more Dwelling Units:
SR = [(0.13 x DU) + 1] ÷ 1.853
Complete calculations for Residential and Commercial space separately, add results, then round up to the nearest whole number. SR + SC = ST (Total EV Parking Spaces required). To calculate how to earn two points, refer to Table C402.5.3.1(2) or Table R502.5.3.1(2) Sample Calculation for required number of EV Parking Spaces.
Table 144-R502.5.3.1(2)
Sample Calculation for Required Number of EV Parking Spaces
Sample Calculation
44,300 sq ft mixed-use building. 26 Dwelling Units (DU) and 6,000 sq ft Commercial Area (CA).
To earn one point
SR = [(0.13 x 26) + 1] ÷ 1.853
SR = (3.38 + 1) ÷ 1.853
SR = 4.38 ÷ 1.853 = 2.364
2.364 EV spaces are required for Residential portion
SC = 0.151 x 6
SC = 0.906
0.906 EV spaces are required for Commercial portion
ST = SR + SC rounded up
ST = 2.364 + 0.906 = 3.27, round up
4 EV spaces are required for the building to earn one point.
To earn two points
SR = 2.364 x 2 = 4.728
SC = 0.906 x 2 = 1.812
ST = SR + SC rounded up
ST = 4.728 + 1.812 = 6.54, round up
7 EV spaces are required for the building to earn two points.
144-R502.5.3.2. 
The requirements for this point as set forth here and in Table 144-R502.6 are not intended to override or supplant existing zoning code provisions regarding parking requirements. To the extent that zoning permissible parking spaces cannot be accommodated on the building site, the building must seek off-site spaces in accordance with the provisions of this point and applicable zoning laws, where zoning allows off-site parking spaces.
144-R502.5.3.3. 
All electric vehicle parking spaces shall be located on the same parcel as the building, in the same parking facilities as those used by one or more of the following target user groups: customers/clients; employees; and fleet vehicles. If no parking facilities exist on the same parcel, and off-site parking facilities do exist for one or more of the user groups, then EV parking spaces may be installed in those off-site parking facilities. Off-site parking must be within 0.25 mile of the building.
144-R502.5.3.4. 
All Electric vehicle parking spaces shall be served by a dedicated electric vehicle charging port. Electric vehicle charging stations may have any number of ports.
144-R502.5.3.5. 
At least one accessible electric vehicle parking space is required in any parking facility that includes more than 10 electric vehicle parking spaces. Any parking facility with more than 50 electric vehicle parking spaces must provide at least two accessible electric vehicle parking spaces. The associated space(s) are not required to be designated only for accessible parking, as defined by the Building Code of NYS, but must meet all other accessibility requirements contained in New York State law.
144-R502.5.3.6. 
All buildings must install Level 2 EV charging stations that operate on a 240-volt AC circuit and/or direct current fast chargers.
144-R502.5.3.7. 
Electric vehicle parking spaces shall be provided with a dedicated branch circuit, raceways, and all other electric vehicle charging equipment. All electrical systems and equipment shall be installed to meet the standards of the National Electrical Code in effect at the time of application for a building or electrical permit. The branch circuit shall be identified for electric vehicle service in the service panel or subpanel directory. Electrical room(s) serving areas with EV parking spaces shall be designed to accommodate the electrical equipment and distribution required to serve all of the electric vehicle charging stations.
[Amended 4-25-2022 by L.L. No. 8-2022]
144-R502.5.3.8. 
Electric vehicle charging station equipment shall be maintained in all respects, including the functioning of the charging equipment. A phone number or other contact information shall be provided on the charging station equipment for reporting when the equipment is not functioning, or other problems are encountered.
144-R502.5.3.9. 
The electric vehicle charging station, including the charging cord, shall be installed so as to not interfere with pedestrian walkways at any time.
144-R502.5.3.10. 
Except for accessible EV parking spaces and EV parking spaces used for single-family dwellings or two-family dwellings, each EV parking space shall be posted with signage indicating that the space is only to be used for electric vehicle charging purposes. Days and hours of operations and any other restrictions on use of the parking space shall be included if time limits or tow-away provisions are to be enforced.
[Amended 4-25-2022 by L.L. No. 8-2022]
144-R502.5.4. 
OP4 Adaptive reuse. One point may be earned according to the requirements below.
[Amended 4-25-2022 by L.L. No. 8-2022]
144-R502.5.4.1. 
The building must maintain 50% or more of the following five existing building elements, based on their total combined surface area:
A. 
Exterior of above-grade and below-grade exterior walls.
B. 
Interior of above-grade and below-grade exterior walls.
C. 
Floors.
D. 
Ceilings.
E. 
Roof decks as defined by the Building Code of New York State (exterior surface area).
The 50% threshold relates to the total combined surface area of all listed building elements. Any individual elements, or portions thereof, may be replaced, as long as the total surface area of all the unaltered elements is at least 50% of the starting (pre-construction) total surface area of the elements.
144-R502.5.4.2. 
Any insulation may be altered to the extent allowed by the ECCCNYS in effect at the time of building permit application. The existing building structure must be repurposed for a different permitted use (for example, when an old school is adapted for use as apartments). A major renovation of a building and reuse for the same purpose shall not be eligible for this point.
144-R502.5.4.3. 
Examples. The diagrams and example calculation below are for informational purposes only. All requirements are included in 144-R502.5.4.1 and 144-R502.5.4.2, above. The simplified diagrams in Figure 144-R502.5.4.3 highlight which surface areas should be counted for two example buildings. An example calculation is provided in Table 144-R502.5.4.3. The diagram on the left shows a small residential building with a basement and an attic with insulation on the floor. The exterior surface area of the roof deck is counted, and the ceiling of the second story is counted; note that the floor of the attic is not counted. The diagram on the right shows a two-story commercial building with a flat roof and no basement or attic. Insulation is between the roof deck and the ceiling of the second story.
Figure 144-R502.5.4.3
Figure 144-C502-5-4-3.tif
Table 144-R502.5.4.3
Adaptive Reuse Example Calculation - Single-Family Home
Home Dimensions
Building width
30
feet
Building length
30
feet
Stories
2
Height/story
10
feet
Height of basement
8
feet
Height of roof peak from 2nd floor ceiling
10
feet
A. Exterior of above-grade and below-grade exterior walls
8 above grade walls (N, S, E, W walls of 2 stories)
8
Surface area of each above-grade wall
300
square feet
Total surface area above-grade exterior walls
2,400
square feet
4 below-grade walls (N, S, E, W walls of basement)
4
Surface area of each below-grade wall
240
square feet
Total surface area below-grade exterior walls
960
square feet
Total surface area, exterior of above-grade and below-grade exterior walls
3,360
square feet
B. Interior of above-grade and below-grade exterior walls
Use same calculations as for exterior side (above)
Total surface area, interior of above-grade and below-grade exterior walls
3,360
square feet
C. Floors
3 floors (1st story, 2nd story, basement)
3
Surface area of floor
900
square feet
Total surface area, floors
2,700
square feet
D. Ceilings
3 ceilings (1st story, 2nd story, basement)
3
Surface area of ceiling
900
square feet
Total surface area, ceilings
2,700
square feet
E. Roof decks (exterior surface area)
Roof height
10
feet
Roof triangle base (half of house)
15
feet
Hypotenuse (H) is roof length (1 side)
18
feet
Roof width = house width
30
feet
Roof area (1 side only) = H* roof width
540
square feet
Total surface area, roof
1,080
square feet
Total surface area, all building elements
13,200
square feet
50% of total surface area
6,600
square feet
If at least 6,600 square feet of the building elements are kept, the building will earn the adaptive reuse point.
144-R502.5.5. 
OP5 NY Stretch Code. Two points may be earned according to the requirements below.
144-R502.5.5.1. 
The building shall comply with all requirements of the NY Stretch Energy Code - 2020 Version 1.0, which is available at: www.nyserda.ny.gov/All-Programs/Programs/Energy-Code-Training/NYStretch-Energy-Code-2020
144-R502.5.6. 
OP6 Custom energy improvement. Up to two points may be earned according to the requirements below.
144-R502.5.6.1. 
To earn one point, both of the following conditions must be met:
A. 
Reduce energy use by 1.2 kWh/SF/year or 4.1 kbtu/SF/year for all residential heated floor area in the building.
B. 
Reduce energy use by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all commercial heated floor area in the building.
144-R502.5.6.2. 
To earn two points, both of the following conditions must be met:
A. 
Reduce energy use by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all residential heated floor area in the building.
B. 
Reduce energy use by 4.8 kWh/SF/year or 16.4 kbtu/SF/year for all commercial heated floor area in the building.
144-R502.5.6.3. 
Multiple improvements may be combined to achieve each point under this improvement. Improvements may be made anywhere in the building as long as they meet the thresholds of energy use reduction. The proposed energy improvement(s) shall be submitted to the Code Enforcement Officer in writing, signed by the design professional or energy professional. Energy reduction must be shown through energy analysis performed by a design professional or energy professional. Simplified calculations (e.g., spreadsheet) are acceptable.
144-R502.5.6.4. 
For a baseline, use the 2016 Energy Conservation Construction Code of New York State. If the baseline condition is not addressed by the ECCCNYS, use baseline conditions as defined in Appendix G of ASHRAE Standard 90.1-2013, or RESNET HERS (latest edition).
144-R502.5.6.5. 
Production of renewable energy shall not count toward energy reduction. Energy reduction must be calculated after applying all other proposed energy improvements to the proposed design. In other words, interactive energy savings must be performed. Savings cannot be taken for improvements made with other points, such as right-lighting or the NY Stretch Energy Code.
144-R502.6. 
Summary table for prescriptive compliance path/easy path. The following Table 144-R502.6 is a summary of the Prescriptive Compliance Path/Easy Path for Residential buildings. This is a summary for informational purposes only. To earn points, all applicable requirements in Subsections 144-R502.1, 144-R502.2, 144-R502.3, 144-R502.4 and 144-R502.5 must be met. In case of discrepancies between Table 144-R502.6 and the requirements in Subsections 144-R502.1, 144-R502.2, 144-R502.3, 144-R502.4 and 144-R502.5, the latter shall hold precedence.
Table 144-R502.6
Residential Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least six points.
Category
Improvement
Points
Details
EFFICIENT ELECTRIFICATION
EE1
Heat pumps for space heating
3 - 5
3 points for air source heat pumps.
5 points for ground source heat pumps.
EE2
Heat pumps for domestic hot water heating
1
1 point for water heating systems that use heat pumps.
EE3
Commercial cooking electrification
3
3 points for electric cooking equipment in restaurants and other food service buildings. Prerequisite: no fossil fuel use in the building.
EE4
Residential cooking and clothes drying electrification
1
1 point for electric stoves and ventless heat pump clothes dryers. Prerequisite: no fossil fuel use in the building.
AFFORDABILITY IMPROVEMENTS
AI1
Smaller building/room size
1 - 2
Up to 2 points for smaller room sizes. Available for hotel and residential portions only.
AI2
Heating systems in heated space
1
1 point for installing heating systems in directly heated spaces.
AI3
Efficient building shape
1
1 point if exterior surface area divided by directly heated floor area is less than the maximum allowed value.
AI5
Modest window-to-wall ratio
1
1 point for overall window-to-wall ratio less than 20% (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE1
Renewable energy systems
1 - 3
Up to 3 points for on-site or off-site renewable electric systems or on-site renewable thermal systems.
RE2
Biomass systems
5
5 points for biomass space heating systems.
OTHER POINTS
OP1
Development density
1
1 point for achieving sufficient development density on the building parcel. A maximum of 2 points total may be earned for points OP1, OP2, and OP3 combined.
OP2
Walkability
1
1 point if the building meets the walkability criteria. A maximum of 2 points total may be earned for points OP1, OP2, and OP3 combined.
OP3
Electric vehicle parking spaces
1
1 point for installing electric vehicle parking spaces and related infrastructure. A maximum of 2 points total may be earned for points OP1, OP2, and OP3 combined.
OP4
Adaptive reuse
1
1 point for substantial repurpose of existing building.
OP5
Meet NY Stretch Code
2
2 points for complying with NY Stretch Energy Code.
OP6
Custom energy improvement
1 - 2
Up to 2 points for reduction in energy use.
144-R503. 
Performance-based compliance path/whole building path.
144-R503.1. 
General. Until January 1, 2023, to meet the requirements of this Subsection 144-R503, a building must comply with any one of the high-performance building approaches described in 144-R503.2, 144-R503.3, 144-R503.4, 144-R503.5 and 144-R503.6. See Subsection 144-R504 for enhanced requirements beginning on and after January 1, 2023, and additional enhanced requirements beginning on and after January 1, 2026.
144-R503.2. 
Energy rating index-based compliance. Restrictions: This compliance method may only be used for Residential Buildings of not more than three stories.
144-R503.2.1. 
The building shall comply with all requirements of Subsection R406, Energy Rating Index Compliance Alternative, of the 2020 Energy Conservation Construction Code of NYS (ECCCNYS R406). Where the requirements of this Energy Code Supplement are more stringent than the requirements of ECCCNYS R406, ECS requirements shall prevail.
144-R503.2.2. 
The rated design shall be shown to have an Energy Rating Index (ERI) less than or equal to 40 when compared to the ERI reference design.
144-R503.2.3. 
Renewable energy generation that meets all applicable requirements for renewable energy systems described in 144-R502.4.1 may be used to meet the requirements.
144-R503.2.4. 
Documentation. Compliance documentation shall be submitted as detailed in ECCCNYS R406.
144-R503.3. 
National Green Building Standard-based compliance.
144-R503.3.1. 
Using the National Green Building Standard ("NGBS", also known as ICC/ASHRAE 700-2015), the building shall earn no less than 80 NGBS energy efficiency points. NGBS certification is not necessary.
144-R503.3.2. 
Renewable energy generation that meets all applicable requirements for renewable energy systems described in R502.4.1 may be used to meet the requirements.
144-R503.3.3. 
Documentation. The design professional or energy professional documenting compliance will provide a signed statement that the design meets the requirements of this subsection, and documentation showing compliance.
144-R503.4. 
Passive house-based compliance.
144-R503.4.1. 
A. 
Buildings shall meet the design requirements of one of the following:
1. 
PHIUS+ Passive Building Standard from Passive House Institute US.
2. 
Passive House Classic Standard from Passive House Institute.
B. 
Actual certification is not required. The most recent version of the chosen standard in effect at the time of building permit application shall be used.
C. 
Documentation shall include at least one of the following:
1. 
Pre-certification letter (or other formal communication) from an accredited passive house certifier, stating that design review has been completed and the building is designed to meet all requirements of the chosen standard. All documentation used to show achievement of the requirements must be submitted to the Code Enforcement Officer.
2. 
Documentation of passive house certification. All documentation used to achieve certification must be submitted to the Code Enforcement Officer.
144-R503.5. 
Greenhouse gas emissions calculation-based compliance. The building shall demonstrate a reduction in greenhouse gas (GHG) emissions of not less than 40% as compared to the baseline building.
144-R503.5.1. 
Energy modeling standards. GHG emissions reductions shall be shown through energy modeling.
A. 
For residential buildings four stories and greater and for mixed-use buildings classified as residential, energy modeling shall comply with Appendix G of ASHRAE Standard 90.1-2013.
B. 
For residential buildings of not more than three stories, energy modeling shall comply with RESNET-HERS.
144-R503.5.2. 
Process loads. The GHG emissions reduction assessment and requirement shall exclude energy use by process loads. However, the energy model shall include the energy used for process loads because energy used by heating, cooling, and ventilation (including exhaust fans/hoods, makeup air fans, and heating/cooling for makeup air) is subject to the GHG emissions reduction requirement. After the baseline and proposed energy models are run, for the GHG emissions reduction calculation, subtract out the process energy use from both the baseline and the proposed building energy model results, and use the resulting without-process-energy results for the GHG emissions calculations.
144-R503.5.3. 
Renewable energy. Renewable energy generation may be used. All applicable requirements for renewable energy systems described in 144-R502.4.1 must be met. Renewable energy generation used to achieve the 40% reduction in GHG emissions is capped at 25% of the baseline energy use. The GHG emissions factor for electricity produced by renewable energy systems shall be 0 (zero) lb CO2e/MWh.
144-R503.5.4. 
GHG emissions factor for electricity. For buildings not served by combined heat and power plants, the GHG emissions factor for electricity used for all calculations shall be 548.37 lb CO2e/MWh.
144-R503.5.5. 
GHG emissions factor for electricity for buildings served by combined heat and power plants.
A. 
For buildings using electricity generated by combined heat and power (CHP) plants, the GHG emissions factor for electricity shall be determined in one of the following ways:
1. 
The most recent heat rate data available at the time of building application shall be used from www.eia.gov/electricity/annual/html/epa_08_02.html, for the specific type of generation plant used, for electricity to be used in the proposed building, and the heat rate shall be multiplied by the EPA emissions factor for the fuel used at the CHP plant. The result shall be used as the GHG emissions factor for electricity from CHP plants.
2. 
Data gathered from actual operation of the CHP plant and its distribution network shall be used to determine the site-specific GHG emissions factor for electricity to be used in the building. All data used shall be made publicly available before the time of building permit application.
B. 
For buildings served by CHP plants, the baseline (reference building) electricity use GHG emissions shall be the same as for buildings not served by a CHP plant.
144-R503.5.6. 
If a facility uses electricity from a combination of sources (e.g., utility, off-site renewable energy system, and CHP plants), a weighted average of GHG emissions factors shall be used.
144-R503.5.7. 
Documentation. The following documentation shall be submitted to show compliance with 144-R503.5 in sufficient clarity and detail:
A. 
A report, signed and stamped by an accredited third-party energy professional, showing the results of all calculations, assumptions, inputs, and outputs for the energy model.
B. 
A letter, signed and stamped by an accredited third-party energy professional, stating that proposed total GHG emissions for the building are at least 40% less than the GHG emissions of the baseline building.
C. 
The Town reserves the right to require additional documentation and/or additional third-party review and analysis by a consultant selected by the Town, at the expense of the applicant. All such documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
144-R503.6. 
Greenhouse gas emissions calculation-based compliance for additions. Compliance using the requirements of this provision 144-R503.6 may only be used for additions that are showing compliance together with the existing building. See also 144-202.2.
144-R503.6.1. 
The addition and the existing building, together as a whole, shall be shown to have lower total GHG emissions than the original existing building.
144-R503.6.2. 
Current and proposed GHG emissions shall be calculated following the requirements of the GHG emissions calculation method (R503.5).
144-R503.6.3. 
Documentation. The following documentation shall be submitted:
A. 
An energy study of the existing building that includes energy use from at least 12 consecutive months of the most recent 24 months at the time of building permit application.
B. 
An energy study that shows anticipated energy use for the new addition and modified existing building.
C. 
A report, signed and stamped by an accredited energy professional, showing the results of all calculations, assumptions, inputs, and outputs for the energy model.
D. 
A letter, signed and stamped by an accredited third-party energy professional, stating that proposed total GHG emissions for the building and addition together are less than the GHG emissions for the existing building.
E. 
The Town reserves the right to require additional documentation and/or additional third-party review and analysis by a consultant selected by the Town, at the expense of the applicant. All such documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
144-R504. 
Future requirements.
144-R504.1. 
General.
A. 
On January 1, 2023, the requirements of Subsections 144-R502 and 144-R503 shall change as described in 144-R504.2, 144-R504.3, 144-R504.4, and 144-R504.6. Where no changes are listed, the requirements shall remain as described in Subsections 144-R502 and 144-R503.
B. 
On January 1, 2026, the requirements of Subsections 144-R501, 144-R502 and 144-R503 shall change as described in 144-R504.7. Where no changes are listed, the requirements shall remain as described in Subsections 144-R501, 144-R502 and 144-R503.
144-R504.2. 
Changes in 2023 to general requirements of prescriptive compliance path/easy path. Effective January 1, 2023, to meet the requirements of Subsection 144-R502, a building must achieve a minimum of 12 of the points described in Subsection 144-R502. A summary table is provided in 144-R504.5.
144-R504.3. 
Changes in 2023 to efficient electrification points. Effective January 1, 2023, all points awarded from 144-R502.2, Efficient electrification shall be doubled.
144-R504.3.1. 
Six points shall be earned for using air source heat pumps and meeting the requirements of 144-R502.2.1, Heat pumps for space heating. Ten points shall be earned for using ground source heat pumps and meeting the requirements of 144-R502.2.1, Heat pumps for space heating.
144-R504.3.2. 
Two points shall be earned for meeting the requirements of 144-R502.2.2, EE2 Heat pumps for service water heating.
144-R504.3.3. 
Six points shall be earned for meeting the requirements of 144-R502.2.3, EE3 Commercial cooking electrification.
144-R504.3.4. 
Two points shall be earned for meeting the requirements of 144-R502.2.4, EE4 Residential cooking and clothes drying electrification.
144-R504.4. 
Changes in 2023 to RE1 renewable energy systems. Effective January 1, 2023, the maximum number of points allowed under 144-R502.4.1, RE1 Renewable energy systems, shall increase to six (6) points. The criteria for earning points shall remain as described in 144-R502.4.1.
144-R504.5. 
Changes in 2023 to Summary Table for Prescriptive Compliance Path/Easy Path.
[Amended 1-9-2023 by L.L. No. 1-2023]
Residential Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least 12 points.
Category
Improvement
Points
Details
EFFICIENT ELECTRIFICATION
EE1
Heat pumps for space heating
6 - 10
6 points for air source heat pumps. 10 points for ground source heat pumps.
EE2
Heat pumps for domestic hot water heating
2
2 points for water heating systems that use heat pumps.
EE3
Commercial cooking electrification
6
6 points for electric cooking equipment in restaurants and other food service buildings. Prerequisite: no fossil fuel use in the building.
EE4
Residential cooking and clothes drying electrification
2
2 points for electric stoves and ventless heat pump clothes dryers. Prerequisite: no fossil fuel use in the building.
AFFORDABILITY IMPROVEMENTS
AI1
Smaller building/room size
1 - 2
Up to 2 points for smaller room sizes. Available for hotel and residential portions only.
AI2
Heating systems in heated space
1
1 point for installing heating systems in directly heated spaces.
AI3
Efficient building shape
1
1 point if exterior surface area divided by directly heated floor area is less than the maximum allowed value.
AI5
Modest window-to-wall ratio
1
1 point for overall window-to-wall ratio less than 20% (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE1
Renewable energy systems
1 - 6
Up to 6 points for on-site or off-site renewable electric systems or on-site renewable thermal systems.
RE2
Biomass systems
5
5 points for biomass space heating systems.
OTHER POINTS
OP1
Development density
1
1 point for achieving sufficient development density on the building parcel. A maximum of 3 points total may be earned for points OP1, OP2, and OP3 combined.
OP2
Walkability
1
1 point if the building meets the walkability criteria. A maximum of 3 points total may be earned for points OP1, OP2, and OP3 combined.
OP3
Electric vehicle parking spaces
1
Up to 2 points for installing electric vehicle parking spaces and related infrastructure. A maximum of 3points total may be earned for points OP1, OP2, and OP3 combined.
OP4
Adaptive reuse
1
1 point for substantial repurpose of existing building.
OP5
Meet NY Stretch Code
2
2 points for complying with NY Stretch Energy Code.
OP6
Custom energy improvement
1 - 2
Up to 2 points for reduction in energy use.
144-R504.6. 
Changes in 2023 to performance-based compliance path/whole building path. Effective January 1, 2023, the requirements of Subsection 144-R503, Performance-based compliance path/whole building path, shall change as described in 144-R504.6.1, 144-R504.6.2, and 144-R504.6.3. Where no changes are listed, the requirements shall remain as described in Subsection 144-R503.
144-R504.6.1. 
Changes to energy rating index-based compliance.
Effective January 1, 2023, the language of 144-R503.2.2 shall be replaced with the following language:
The building must satisfy one of the following criteria:
A. 
The rated design shall be shown to have an Energy Rating Index (ERI) less than or equal to 20 when compared to the ERI reference design.
B. 
The rated design shall be shown to have an Energy Rating Index (ERI) less than or equal to 40 when compared to the ERI reference design AND seven ECS points from Subsection 144-R502, Prescriptive compliance path/easy path, shall be earned. Points from AI4 Right-lighting and OP5 Meet NY Stretch Code may not be counted toward the seven ECS points.
144-R504.6.2. 
Changes to National Green Building Standard-based compliance. In addition to all existing requirements, seven ECS points from Subsection 144-R502, Prescriptive compliance path/easy path, must be earned. Points from AI4 Right-lighting and OP5 Meet NY Stretch Code may not be counted toward the seven ECS points.
144-R504.6.3. 
Changes to greenhouse gas emissions calculation-based compliance. Effective January 1, 2023, the building shall demonstrate a reduction in greenhouse gas (GHG) emissions of not less than 80% as compared to the baseline building.
144-R504.6.3.1. 
Renewable energy generation used to achieve the 80% reduction in GHG emissions is capped at 50% of the baseline energy use.
144-R504.6.3.2. 
For buildings not served by combined heat and power plants or renewable energy systems, the GHG emissions factor for electricity used for all calculations shall be 295.9 lb CO2e/MWh.
144-R504.7. 
Changes in 2026. Effective January 1, 2026, all buildings shall be built to have net-zero GHG emissions and shall not use FOSSIL FUELS for space heating, water heating, or clothes drying.
144-R504.7.1. 
The language in 144-R501.2, Application, shall be replaced with:
A. 
Residential buildings of not more than three stories shall comply with all requirements of 144-R503.2, Energy Rating Index-based compliance, except 144-R503.2.2. The rated design shall be shown to have an Energy Rating Index (ERI) less than or equal to 5 when compared to the ERI reference design.
B. 
Residential Buildings four stories and greater shall comply with the requirements of the ZERO Code, using the most recent version of the ZERO Code available at the time of permit application. The ZERO Code, an Architecture 2030 initiative, is available at https://zero-code.org.
C. 
An ECS compliance plan shall be the basis for evaluating compliance.
144-R504.7.2. 
Fossil fuels shall not be used for space heating, water heating or clothes drying. Fossil fuels may be used for process energy and for cooking.
144-601. 
Compliance documentation.
144-601.1. 
144-601.1.1. 
The following compliance documentation shall be submitted:
A. 
For the proposed point system, a checklist that shows which points are sought, and support for each point. For example, if a developer is seeking the size credit for a house design, the checklist would show the house area (square feet), number of bedrooms, required house size, and proposed house size, to show that the house meets the size requirement.
B. 
For the proposed whole-building compliance, a report by a design professional or energy professional, at the time of planning review and again when applying for a building permit.
144-601.1.2. 
Compliance documents are available from the Town of Ithaca website and from the Town Code Enforcement Department.
144-601.1.3. 
At the planning review phase, a preliminary green building checklist shall be submitted, indicating which green compliance items are proposed/planned. A checklist shall be submitted with the construction documents, prior to the Building Department issuing the building permit.
144-602. 
Variances.
144-602.1. 
144-602.1.1. 
Any person aggrieved by an order, interpretation, or decision of a Code Enforcement Officer concerning the application or requirements of the provisions of this chapter may take an appeal to the Zoning Board of Appeals.
144-602.1.2. 
An application for an interpretation or variance shall be submitted to the Building and Code Enforcement Department in a form substantially indicating the name and owner of the real property, the nature of the condition for which an interpretation or variance waiver is sought, and the reasons for which an interpretation or variance is sought.
144-602.1.3. 
The applicant shall pay the Town the same fee as that set from time to time by Town Board resolution for appeals to the Zoning Board of Appeals for area variances from zoning requirements.
144-602.1.4. 
The Zoning Board of Appeals shall, in accordance with the provisions of this chapter, review any order, interpretation, or decision (including refusals of a building permit or certificate of occupancy or certificate of compliance) of said Code Enforcement Officer where such order, interpretation, or decision is based upon the requirements of this chapter.
144-602.1.5. 
The Zoning Board of Appeals, in hearing an appeal from the order, interpretation, or decision of the Code Enforcement Officer, shall have the power to make its own interpretation (where an interpretation is requested), and to grant variances from the standards and requirements of this chapter. Any standard or requirement of this chapter may be varied, in whole or part, with regard to specific construction upon application made by or on behalf of an owner, where the applicant meets its burden of demonstrating strict compliance with such standard or requirement would entail practical difficulty or cause any unnecessary hardship in relation to such construction; provided, however, that any such variance shall provide for alternative energy conservation standards or requirements to achieve, to the extent practicable, the purpose of this chapter to reduce greenhouse gas emissions.
144-602.1.6. 
In determining whether to grant a variance from a standard or requirement of this chapter, the Zoning Board of Appeals shall take into consideration the benefit to the applicant if the variance is granted, as weighed against the detriment to the health, safety and welfare of the community that would result by such grant. In making such determination, the Zoning Board of Appeals shall also consider and make findings on the following:
A. 
Whether the benefits sought by the applicant can be achieved by some method, feasible for the applicant to pursue, other than a variance;
B. 
Whether the applicant has proposed to implement other energy or construction options, in place of the standard or requirement that is the subject of the variance request, that will result in the least amount practicable of additional greenhouse gas emissions.
C. 
Whether the variance request will result in a substantial amount of greenhouse gas emissions if the request is granted.
D. 
Whether the variance request is unique to the building, project, or site and does not apply to a substantial portion of the neighborhood or community.
E. 
Whether the requested variance is the minimum necessary.
F. 
Whether the alleged difficulty was self-created, which consideration shall be relevant to the decision of the Zoning Board of Appeals but shall not necessarily preclude the granting of the variance.
144-602.1.7. 
If the Zoning Board of Appeals grants a variance, it shall grant the minimum variance necessary, condition such grant on the imposition of alternative energy conservation standards or requirements to achieve to the extent practicable the purpose of this chapter to reduce greenhouse gas emissions, and impose other conditions as such Board may reasonably determine necessary to mitigate the consequences of the grant of the variance.
144-602.1.8. 
The procedures relating to variances in Chapter 270, Zoning, of the Town of Ithaca Code, and the procedures set forth in New York Town Law § 267-a(5) through (9) and (11) through (13) shall apply, except to the extent expressly provided otherwise herein or superseded hereby. Those subsections contain procedures and requirements for the filing of administrative decisions; the time for appeal to the Zoning Board of Appeals; stays upon appeal; hearings of appeals; time, filing and notice of Zoning Board of Appeals decisions; compliance with the New York State Environmental Quality Review Act; rehearings; and voting requirements. In addition to publication of the public hearing notice, the Zoning Board of Appeals notice of the application shall also be given to all landowners owning property adjoining the property for which an interpretation or variance is sought. The Zoning Board of Appeals notice shall also be posted on the property in accordance with the posting provisions of § 270-237 of the Town of Ithaca Code. To the extent a procedure is not provided herein, the Zoning Board of Appeals may administratively adopt procedures that are approved by the Town Board and published in the official minutes of the Town Board of the Town of Ithaca.
144-602.1.9. 
The actions and determinations of the Town of Ithaca, the Zoning Board of Appeals, the Town Board, and the Code Enforcement Officer, as referenced in this chapter, shall be deemed final determinations for purposes of Article 78 of the New York Civil Practice Laws and Rules (CPLR). Notwithstanding this, standing under said Article 78 of the CPLR shall only be appropriate after the exhaustion of any administrative reviews and/or appeals as provided for in this chapter.
144-602.1.10. 
Unless work has commenced in accordance with the variance granted by the Zoning Board of Appeals within one year from the issuance of the building permit authorizing such work, or within 18 months of the granting of such variance, whichever is earlier, not only the building permit but the variance shall expire and the construction on the property shall revert to those ECS standards and requirements in effect at the time of variance expiration.
144-602.1.11. 
If the building permit expires, the variance shall also expire at the same time.